Image not available for this product
Danfoss AVQMT-WE motorized flow and temperature controller (PICV), PN 25, DN 20, flow range 0.16–3.5 m³/h, Kvs 6.3 m³/h, External thread G 1 A (ISO 228/1), via tailpieces
Pricing
Request a quote
We reply within 24 hours
Product Description
Danfoss AVQMT-WE (003H7086) — self-acting flow and temperature controller with integrated, pressure-independent motorized control valve (PICV); holds the differential pressure across the built-in flow restrictor constant so the electric actuator stem position sets flow independent of system pressure; limits the flow to the set maximum and closes on rising media temperature, PN 25, DN 20, for district heating and cooling systems. Because the built-in differential-pressure controller keeps the pressure drop across the flow restrictor constant, the flow becomes pressure-independent: the position of the separately ordered Danfoss AMV(E) electric actuator directly sets the flow, and the valve limits the flow to the set maximum and closes on rising media temperature via an AVT thermostatic actuator or STM safety temperature monitor fitted to the second connection neck. Flow range 0.16 - 3.5 m³/h; Kvs 6.3 m³/h; flow-restrictor differential pressure (Δpb) 0.2 bar; maximum differential pressure 16 bar; media temperature 2–150 °C; seat leakage 0.05 % Kvs (IEC 60534). Valve body Dezincification-resistant brass; stainless-steel seat/cone; EPDM control diaphragm. Connection External thread G 1 A (ISO 228/1), via tailpieces. Mounting version Free. Permissible media: district-heating/cooling circulation water (glycolic water up to 30 %), pH 7–10. The controller is delivered completely assembled, including the impulse tube between valve and actuator; the AMV(E) electric actuator and the AVT/STM thermostatic actuator are ordered separately. OEM P/N 003H7086. Materials and function per Danfoss AVQM-WE / AVQMT-WE (new neck) data sheet; technical values verbatim from store.danfoss.com (code 003H7086). Contains lead per the REACH candidate list. differential pressure 16 bar); Temperature range: 2 to 150 °C (district heating/cooling water); Standards: ISO 228-1, IEC 60534; HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.
Technical Specifications
- Code number
- 003H7086
- Type
- AVQMT-WE
- Product group
- Pressure independent control valves (Pressure and flow controllers)
- Function
- Self-acting flow and temperature controller with integrated, pressure-independent motorized control valve (PICV); holds the differential pressure across the built-in flow restrictor constant so the electric actuator stem position sets flow independent of system pressure; limits the flow to the set maximum and closes on rising media temperature
- Valve size
- DN 20
- Pressure class
- PN 25
- Connection
- External thread G 1 A (ISO 228/1), via tailpieces
- Kvs value
- 6.3 m³/h
- Flow rate range
- 0.16 - 3.5 m³/h
- Flow restrictor differential pressure (Δpb)
- 0.2 bar
- Max. differential pressure
- 16 bar
- Media temperature
- 2 - 150 °C
- Media
- District heating / district cooling circulation water (glycolic water up to 30%), pH 7 - 10
- Seat leakage rate
- 0.05 % Kvs (IEC 60534)
- Electric actuator
- Danfoss AMV(E) (e.g. AMV/AME 110, 150, 435), ordered separately; controllable by ECL electronic controllers
- Thermostatic actuator (temperature limiting)
- Danfoss AVT thermostatic actuator or STM safety temperature monitor, ordered separately
- Delivery
- Delivered assembled, incl. impulse tube between valve and actuator; electric actuator ordered separately
- Mounting version
- Free
- Valve body material
- Dezincification-resistant brass
- Valve seat / cone
- Stainless steel
- Control diaphragm
- EPDM
- EU RoHS compliance
- Yes with exemptions (6(c))
- REACH Candidate List substance
- Lead (CAS no. 7439-92-1)
- China RoHS
- Out of scope
- Net weight
- 3.41 kg
- Gross weight
- 3.41 kg
- EAN
- 5710104093970
Standards & Compliance
- Material
- Valve body Dezincification-resistant brass; valve seat/cone Stainless steel; control diaphragm EPDM
- Pressure Rating
- PN 25 (max. differential pressure 16 bar)
- Temperature Range
- 2 to 150 °C (district heating/cooling water)
- HS Code
- 8481.80
Compatibility & Fitment
Danfoss AVQMT-WE for DN 20 district-heating/cooling combined flow limiting, pressure-independent flow control and temperature limiting at PN 25. Set the maximum flow within 0.16 - 3.5 m³/h using the adjustable flow restrictor (Kvs 6.3 m³/h); because control is pressure-independent, the flow follows the electric actuator position regardless of Δp swings (up to 16 bar). Fit a Danfoss AMV(E) electric actuator (ordered separately), controllable by an ECL electronic controller. For temperature limiting, fit a Danfoss AVT thermostatic actuator or an STM safety temperature monitor on the second neck (ordered separately). Confirm the connection (External thread G 1 A (ISO 228/1), via tailpieces) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut set separately. Media temperature up to 150 °C.
Product Documentation
More from Danfoss
Danfoss
Danfoss AVQMT-WE motorized flow and temperature controller (PICV), PN 25, DN 25, flow range 0.2–4.5 m³/h, Kvs 8 m³/h, External thread G 1 1/4 A (ISO 228/1), via tailpieces
003H7087

Danfoss
Danfoss AVQM-WE motorized flow controller (PICV), PN 25, DN 32, flow range 0.4–10 m³/h, Kvs 12.5 m³/h, Flange DN 32 (EN 1092-2)
003H7088

Danfoss
Danfoss AVQM-WE motorized flow controller (PICV), PN 25, DN 40, flow range 0.8–10.5 m³/h, Kvs 20 m³/h, Flange DN 40 (EN 1092-2)
003H7089

Danfoss
Danfoss AVQM-WE motorized flow controller (PICV), PN 25, DN 50, flow range 0.8–14 m³/h, Kvs 25 m³/h, Flange DN 50 (EN 1092-2)
003H7090

Danfoss
Danfoss MMA (M28) thermostatic radiator sensor (operator head), liquid-charged, built-in sensor, 8–21 °C setting range, for M28 MMA valves
013G2760

Danfoss
Danfoss MMA (M28) thermostatic radiator sensor (operator head), liquid-charged, built-in sensor, 8–28 °C setting range, for M28 MMA valves
013G2761

Danfoss
Danfoss TA (M28) thermostatic radiator sensor (operator head), liquid-charged, built-in sensor, 8–21 °C setting range, for M28 TA valves
013G2770

Danfoss
Danfoss RA 2000 thermostatic radiator sensor (operator head), gas-charged, built-in sensor, 5–26 °C setting range, for RA valves (013G2910)
Technical guides
- Cross-Referencing Danfoss Refrigeration Components by IMPA and OEM Code
- Danfoss Product Code Decoder — 003Z, 013G, 017B, 023U, 027L, 032F, 060G, 060H, 065B, 065Z, 068Z, 084H, 132F, 148B Series (Complete Reference)
- Danfoss Maneurop MTZ Reciprocating Compressors — Model Range, Voltage Codes and Replacement Guide
Catalogue entry last verified: 2026-08-29. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.
Frequently asked questions
- Where can I buy 003H7086?
- 003H7086 can be ordered from cballast.com as a Danfoss catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
- What is the manufacturer part number for this Danfoss product?
- The manufacturer part number is 003H7086.
- What is the HS code for 003H7086?
- The customs tariff (HS) code for 003H7086 is 8481.80.
- Who manufactures 003H7086?
- 003H7086 is a Danfoss product in the HVAC & Refrigeration range.
- Is a datasheet available for 003H7086?
- Yes — the 003H7086 datasheet can be viewed and downloaded on this page.
- What is the minimum order quantity for 003H7086?
- The minimum order quantity is 1.
- Is 003H7086 available?
- Yes — 003H7086 is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).