Fluke 1555 FC 10 kV Insulation Tester Kit
Fluke

Fluke 1555 FC 10 kV Insulation Tester Kit

Part number4977469HS code9030.33
MOQ:1

Pricing

Request a quote

We reply within 24 hours

Product Description

The Fluke 1555 insulation resistance test kit lets you evaluate the trends and eliminate the doubt.

Technical Specifications

Manufacturer part number (MPN)
4977469
Brand
Fluke
Category
Tools
250 V Range
50 GΩ
250 V Accuracy (± reading)
Unspecified 5% 20% Unspecified
500 V Range
100 GΩ
500 V Accuracy (± reading)
Unspecified 5% 20% Unspecified
1000 V Range
200 GΩ
1000 V Accuracy (± reading)
Unspecified 5% 20% Unspecified
2500 V Range
500 GΩ
2500 V Accuracy (± reading)
Unspecified 5% 20% Unspecified
5000 V Range
1 TΩ
5000 V Accuracy (± reading)
Unspecified 5% 20% Unspecified
10000 V Range
2 TΩ
10000 V Accuracy (± reading)
Unspecified 5% 20% Unspecified
Bar graph range
0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)
Insulation test voltage accuracy
-0%, +10% at 1 mA load current
Induced AC mains current rejection
2 mA maximum
Charging rate for capacitive load
5 seconds per μF
Discharge rate for capacitive load
1.5 s/μF
Leakage current measurement Range
1 nA to 2 mA
Leakage current measurement Accuracy
±(5% + 2 nA)
Capacitance measurement Range
0.01 μF to 15.00 μF
Capacitance measurement Accuracy
±(15% rdg + 0.03 μF)
Timer Range
0 to 99 minutes
Timer Resolution setting
1 minute
Timer Resolution indication
1 second
Live circuit warning Warning range
30 V to 660 V AC/DC, 50/60 Hz
Live circuit warning Voltage accuracy
±(15% + 2 V)
Software specifications
FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.
Display
75 x 105 mm
Power
12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger Input (AC)
85 V to 250 V AC 50/60 Hz 20 VA
Dimensions
269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in)
Weight
3.7 kg (8.2 lb)
Temperature (operating)
-20°C to 50°C (-4°F to 122°F)
Temperature (storage)
-20°C to 65°C (-4°F to 149°F)
Humidity
80% to 31°C decreasing linearly to 50% at 50°C
Altitude
2000 m
Enclosure sealing
IP40
Input overload protection
1000 V AC
Electromagnetic compatibility
EN 61326
Safety compliance
IEC 61010-1: Overvoltage category II, Pollution Degree 2. IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III IEC 61557-1, IEC 61557-2

Standards & Compliance

HS Code
9030.33

Cross References

  • OEM-URL https://www.fluke.com/en-us/product/electrical-testing/insulation-testers/fluke-1555-kit

Catalogue entry last verified: 2026-10-03. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.

Frequently asked questions

Where can I buy 4977469?
4977469 can be ordered from cballast.com as a Fluke catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
What is the manufacturer part number for this Fluke product?
The manufacturer part number is 4977469.
What is the HS code for 4977469?
The customs tariff (HS) code for 4977469 is 9030.33.
Who manufactures 4977469?
4977469 is a Fluke product in the Safety & Detection range.
Is a datasheet available for 4977469?
Yes — the 4977469 datasheet can be viewed and downloaded on this page.
What is the minimum order quantity for 4977469?
The minimum order quantity is 1.
Is 4977469 available?
Yes — 4977469 is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).