Fluke 1555 FC 10 kV Insulation Tester Kit

Fluke · Safety & Detection · Tools · USA · fluke.com
Part Number
4977469  ·  HS 9030.33
Fluke 1555 FC 10 kV Insulation Tester Kit

The Fluke 1555 insulation resistance test kit lets you evaluate the trends and eliminate the doubt.

Technical Specifications

Manufacturer part number (MPN)4977469
BrandFluke
CategoryTools
250 V Range50 GΩ
250 V Accuracy (± reading)Unspecified 5% 20% Unspecified
500 V Range100 GΩ
500 V Accuracy (± reading)Unspecified 5% 20% Unspecified
1000 V Range200 GΩ
1000 V Accuracy (± reading)Unspecified 5% 20% Unspecified
2500 V Range500 GΩ
2500 V Accuracy (± reading)Unspecified 5% 20% Unspecified
5000 V Range1 TΩ
5000 V Accuracy (± reading)Unspecified 5% 20% Unspecified
10000 V Range2 TΩ
10000 V Accuracy (± reading)Unspecified 5% 20% Unspecified
Bar graph range0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)
Insulation test voltage accuracy-0%, +10% at 1 mA load current
Induced AC mains current rejection2 mA maximum
Charging rate for capacitive load5 seconds per μF
Discharge rate for capacitive load1.5 s/μF
Leakage current measurement Range1 nA to 2 mA
Leakage current measurement Accuracy±(5% + 2 nA)
Capacitance measurement Range0.01 μF to 15.00 μF
Capacitance measurement Accuracy±(15% rdg + 0.03 μF)
Timer Range0 to 99 minutes
Timer Resolution setting1 minute
Timer Resolution indication1 second
Live circuit warning Warning range30 V to 660 V AC/DC, 50/60 Hz
Live circuit warning Voltage accuracy±(15% + 2 V)
Software specificationsFlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.
Display75 x 105 mm
Power12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger Input (AC)85 V to 250 V AC 50/60 Hz 20 VA
Dimensions269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in)
Weight3.7 kg (8.2 lb)
Temperature (operating)-20°C to 50°C (-4°F to 122°F)
Temperature (storage)-20°C to 65°C (-4°F to 149°F)
Humidity80% to 31°C decreasing linearly to 50% at 50°C
Altitude2000 m
Enclosure sealingIP40
Input overload protection1000 V AC
Electromagnetic compatibilityEN 61326
Safety complianceIEC 61010-1: Overvoltage category II
Pollution Degree 2
IEC 61010-2-030Measurement 600V CAT IV / 1000V CAT III IEC 61557-1, IEC 61557-2