Danfoss logo

Image not available for this product

Danfoss

Danfoss AVQM-WE motorized flow controller (PICV), PN 25, DN 15, flow range 0.07–1.6 m³/h, Kvs 2.5 m³/h, External thread G 3/4 A (ISO 228/1), via tailpieces

Part number003H7080Item numberCB-DANF-003H7080EAN / GTIN5710104093918HS code8481.80
MaterialValve body Dezincification-resistant brass; valve seat/cone Stainless steel; control diaphragm EPDM
HVAC & Refrigeration
Balancing Valves
MOQ:1

Pricing

Request a quote

We reply within 24 hours

Product Description

Danfoss AVQM-WE (003H7080) — self-acting flow controller with integrated, pressure-independent motorized control valve (PICV); holds the differential pressure across the built-in flow restrictor constant so the electric actuator stem position sets flow independent of system pressure; limits the flow to the set maximum, PN 25, DN 15, for district heating and cooling systems. Because the built-in differential-pressure controller keeps the pressure drop across the flow restrictor constant, the flow becomes pressure-independent: the position of the separately ordered Danfoss AMV(E) electric actuator directly sets the flow, and the valve limits the flow to the set maximum. Flow range 0.07 - 1.6 m³/h; Kvs 2.5 m³/h; flow-restrictor differential pressure (Δpb) 0.2 bar; maximum differential pressure 16 bar; media temperature 2–150 °C; seat leakage 0.05 % Kvs (IEC 60534). Valve body Dezincification-resistant brass; stainless-steel seat/cone; EPDM control diaphragm. Connection External thread G 3/4 A (ISO 228/1), via tailpieces. Mounting version Free. Permissible media: district-heating/cooling circulation water (glycolic water up to 30 %), pH 7–10. The controller is delivered completely assembled, including the impulse tube between valve and actuator; the AMV(E) electric actuator are ordered separately. OEM P/N 003H7080. Materials and function per Danfoss AVQM-WE / AVQMT-WE (new neck) data sheet; technical values verbatim from store.danfoss.com (code 003H7080). Contains lead per the REACH candidate list. differential pressure 16 bar); Temperature range: 2 to 150 °C (district heating/cooling water); Standards: ISO 228-1, IEC 60534; HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants.

Technical Specifications

Code number
003H7080
Type
AVQM-WE
Product group
Pressure independent control valves (Pressure and flow controllers)
Function
Self-acting flow controller with integrated, pressure-independent motorized control valve (PICV); holds the differential pressure across the built-in flow restrictor constant so the electric actuator stem position sets flow independent of system pressure; limits the flow to the set maximum
Valve size
DN 15
Pressure class
PN 25
Connection
External thread G 3/4 A (ISO 228/1), via tailpieces
Kvs value
2.5 m³/h
Flow rate range
0.07 - 1.6 m³/h
Flow restrictor differential pressure (Δpb)
0.2 bar
Max. differential pressure
16 bar
Media temperature
2 - 150 °C
Media
District heating / district cooling circulation water (glycolic water up to 30%), pH 7 - 10
Cavitation factor z (100/75/50/25 %)
0.41 / 0.6 / 0.62 / 0.69
Seat leakage rate
0.05 % Kvs (IEC 60534)
Electric actuator
Danfoss AMV(E) (e.g. AMV/AME 110, 150, 435), ordered separately; controllable by ECL electronic controllers
Delivery
Delivered assembled, incl. impulse tube between valve and actuator; electric actuator ordered separately
Mounting version
Free
Valve body material
Dezincification-resistant brass
Valve seat / cone
Stainless steel
Control diaphragm
EPDM
EU RoHS compliance
Yes with exemptions (6(c))
REACH Candidate List substance
Lead (CAS no. 7439-92-1)
China RoHS
Out of scope
Net weight
2.906 kg
Gross weight
2.906 kg
Packed volume
9.59 L
EAN
5710104093918

Standards & Compliance

Material
Valve body Dezincification-resistant brass; valve seat/cone Stainless steel; control diaphragm EPDM
Pressure Rating
PN 25 (max. differential pressure 16 bar)
Temperature Range
2 to 150 °C (district heating/cooling water)
HS Code
8481.80

Compatibility & Fitment

Danfoss AVQM-WE for DN 15 district-heating/cooling combined flow limiting and pressure-independent flow control at PN 25. Set the maximum flow within 0.07 - 1.6 m³/h using the adjustable flow restrictor (Kvs 2.5 m³/h); because control is pressure-independent, the flow follows the electric actuator position regardless of Δp swings (up to 16 bar). Fit a Danfoss AMV(E) electric actuator (ordered separately), controllable by an ECL electronic controller. Confirm the connection (External thread G 3/4 A (ISO 228/1), via tailpieces) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut set separately. Media temperature up to 150 °C.

Not sure if it fits? Email sales@cballast.com with your equipment serial number or photos — we confirm fit before you order.

Product Documentation

Document preview: Danfoss 003H7080 — OEM Product Page

Catalogue entry last verified: 2026-08-29. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.

Frequently asked questions

Where can I buy 003H7080?
003H7080 can be ordered from cballast.com as a Danfoss catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
What is the manufacturer part number for this Danfoss product?
The manufacturer part number is 003H7080.
What is the HS code for 003H7080?
The customs tariff (HS) code for 003H7080 is 8481.80.
Who manufactures 003H7080?
003H7080 is a Danfoss product in the HVAC & Refrigeration range.
Is a datasheet available for 003H7080?
Yes — the 003H7080 datasheet can be viewed and downloaded on this page.
What is the minimum order quantity for 003H7080?
The minimum order quantity is 1.
Is 003H7080 available?
Yes — 003H7080 is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).