Danfoss CHV-X straightway check (non-return) valve, 125 mm (5 in) butt weld ASME B 36.10M Schedule 40, steel, 52 bar (code 148B6600)
Danfoss · HVAC & Refrigeration · Check Valves
Danfoss CHV-X straightway check (non-return) valve for industrial refrigeration, code 148B6600. Steel body with butt weld connections to ASME B 36.10M Schedule 40, nominal size 125 mm (5 in). Maximum working pressure 52 bar (754 psig); media temperature range -60 to 150 C (-76 to 302 F). Flow coefficient Kv 250 m3/h (Cv 290 gal/min). The cone lifts to allow forward flow and closes against reverse flow; an embossed one-way arrow marks the flow direction. Minimum opening differential pressure 0.04 bar. Part of the Danfoss SVL Flexline programme. For HCFC, non-flammable HFC, R717 (ammonia) and R744 (CO2) systems.
Specifications
- Part number
- 148B6600
- HS code
- 8481.30
- Material
- Steel
- Pressure rating
- 52 bar
- Temperature range
- -60 to 150 C
- Standard
- ASME B 36.10M Schedule 40
- Standard size
- 125 mm
Compatibility
Danfoss SVL Flexline CHV-X valve. This code is the straightway CHV-X with butt weld (ASME B 36.10M Schedule 40) ends. Confirm line size (125 mm (5 in)), connection type/standard, direction (straightway) and refrigerant before ordering.
Approvals
HVAC & Refrigeration · More Danfoss · Printable datasheet