Schneider Acti 9 IC60N MCB 1P 40A C-Curve
Schneider Electric

Schneider Acti 9 IC60N MCB 1P 40A C-Curve

Part numberA9F77140Item numberCB-SCH-007EAN / GTIN3606480094088HS code8536.20
IEC 60898-1; IEC 60947-2
CE, CB, RoHS, EAC
Switchgear & Protection
Circuit Breakers
MOQ:1

Pricing

Request a quote

We reply within 24 hours

Product Description

Schneider Electric A9F77140 — Acti9 iC60 MCB. Miniature circuit breaker per IEC 60898, DIN-rail modular. Acti 9 iC60N single-pole 40A C-curve MCB. 10kA breaking at 415V. Used as sub-distribution incomer or for high-current single-phase loads. Installed as the primary motor branch-circuit protection device between the incoming feeder and the contactor.

Technical Specifications

Series
Acti 9 iC60N, Poles: 1P, Rated Current: 40A, Curve: C, Breaking Capacity: 10kA at 415V (IEC 60947-2), 6kA at 230/400V (IEC 60898-1), Rated Voltage: 230/400V AC, Width: 18mm (1 module), Mounting: 35mm DIN rail
Number of poles
1
Rated current
40 A
Range
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit-breaker
Device short name
IC60N
Device application
Distribution
Poles description
1P
Number of protected poles
1
[In] rated current
40 A
Network type
AC; DC
Trip unit technology
Thermal-magnetic
Curve code
C
Utilisation category
Category A conforming to EN/IEC 60947-2
Suitability for isolation
Yes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2
Standards
EN/IEC 60947-2; EN/IEC 60898-1
Quality labels
NF
Network frequency
50/60 Hz
[Ue] rated operational voltage
12...60 V AC 50/60 Hz; 100...133 V AC 50/60 Hz; 220...240 V AC 50/60 Hz; 12...60 V DC; 60...72 V DC
Magnetic tripping limit
8 x In +/- 20 %
Breaking capacity
36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2; 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2; 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
[Ics] rated service breaking capacity
27 kA 75 % x Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 7.5 kA 75 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 100 % x Icu at 12...60 V DC conforming to EN/IEC 60947-2; 10 kA 100 % x Icu at 60...72 V DC conforming to EN/IEC 60947-2
Limitation class
3 conforming to EN/IEC 60898-1
[Ui] rated insulation voltage
500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-2
Contact position indicator
Yes
Control type
Toggle
Local signalling
Trip indicator
mounting mode
Clip-on; Removable comb busbar installed
Mounting support
35 mm DIN rail
Comb busbar and distribution block compatibility
Top or bottom: YES
Connection pitch
18 mm between devices
9 mm pitches
2
Height
85 mm
Width
18 mm
Depth
78.5 mm
Product weight
0.215 kg
Colour
White
Mechanical durability
20000 cycles
Electrical durability
10000 cycles
Connections - terminals
Single terminal (top or bottom) , for 1 cable(s) , 1…35 mm², rigid, copper; Single terminal (top or bottom) , for 3.0 cable(s) , 16 mm², rigid, copper, with accessory; Single terminal (top or bottom) , for 1.0 cable(s) , 50 mm², rigid, aluminium, with accessory; Single terminal (top or bottom) , for 1.0 cable(s) , 1…25 mm², flexible, copper; Single terminal (top or bottom) , for 1.0 cable(s) , 1…25 mm², flexible with ferrule, copper; Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory; Single terminal (top or bottom) , for 3 cable(s) , 10 mm², flexible, copper, with accessory
Wire stripping length
14 mm for top or bottom connection
Tightening torque
3.5 N.m top or bottom
Earth-leakage protection
Without
IP degree of protection
IP20 conforming to IEC 60529; IP40 in modular enclosure (Insulation class II) conforming to IEC 60529
Pollution degree
3 conforming to EN/IEC 60947-2
Overvoltage category
IV
Tropicalisation
2 conforming to IEC 60068-1
Relative humidity
95 % at 55 °C
Operating altitude
0...2000 m
Ambient air temperature for operation
-35…70 °C
Ambient air temperature for storage
-40…85 °C
Number of Units in Package 1
1
Number of Units in Package 2
12
Number of Units in Package 3
132
Warranty (in months)
18
EAN
3606480094088

Standards & Compliance

Standard
IEC 60898-1; IEC 60947-2
Classification / Approval
CE, CB, RoHS, EAC
HS Code
8536.20

Compatibility & Fitment

Acti 9 modular system. Compatible with iOF/SD24 status contacts and Vigi RCD modules.

Not sure if it fits? Email sales@cballast.com with your equipment serial number or photos — we confirm fit before you order.

Product Documentation

Document preview: Schneider Electric A9F77140 — OEM Product Page

Catalogue entry last verified: 2026-08-24. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.

Frequently asked questions

Where can I buy A9F77140?
A9F77140 can be ordered from cballast.com as a Schneider Electric catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
What is the manufacturer part number for this Schneider Electric product?
The manufacturer part number is A9F77140.
What is the HS code for A9F77140?
The customs tariff (HS) code for A9F77140 is 8536.20.
Who manufactures A9F77140?
A9F77140 is a Schneider Electric product in the Switchgear & Protection range.
Is a datasheet available for A9F77140?
Yes — the A9F77140 datasheet can be viewed and downloaded on this page.
What is the minimum order quantity for A9F77140?
The minimum order quantity is 1.
Is A9F77140 available?
Yes — A9F77140 is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).