Schneider Electric Motor circuit breaker, TeSys GV2, 3P, 6-10 A, thermal magnetic, spring terminals GV2ME143
Schneider Electric

Schneider Electric Motor circuit breaker, TeSys GV2, 3P, 6-10 A, thermal magnetic, spring terminals GV2ME143

Part numberGV2ME143EAN / GTIN3389110346459HS code8536.20
Electrical Components
Motor Protection Circuit Breakers
MOQ:1

Pricing

Request a quote

We reply within 24 hours

Product Description

Schneider Electric GV2ME143 — TeSys motor protection circuit breaker. Manual motor starter with thermal and magnetic protection. Motor protection MG/TRM Fj 6-10A.

Technical Specifications

Manufacturer part number (MPN)
GV2ME143
EAN / GTIN
3389110346459
Sales unit
pcs
Package quantity
20 pcs
Setting range
6.0-10.0 A
Range
TeSys Deca
Product name
TeSys GV2
Product or component type
Motor circuit breaker
Device short name
GV2ME
Device application
Motor protection
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1
Network frequency
50/60 Hz conforming to IEC 60947-2
Motor power kW
3 kW at 400/415 V AC 50/60 Hz; 4 kW at 400/415 V AC 50/60 Hz; 4 kW at 500 V AC 50/60 Hz; 5.5 kW at 500 V AC 50/60 Hz
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control type
Push-button
[In] rated current
10 A
Thermal protection adjustment range
6…10 A conforming to IEC 60947-2
Magnetic tripping current
149 A
[Ith] conventional free air thermal current
10 A conforming to IEC 60947-2
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
Suitability for isolation
Yes conforming to IEC 60947-1
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In
Rated duty
Uninterrupted conforming to IEC 60947-4-1
Connections - terminals
Power circuit: spring terminals 2 cable(s) 1…6 mm² - solid; Power circuit: spring terminals 2 cable(s) 1.5…4 mm² - flexible without cable end; Power circuit: spring terminals 2 cable(s) 1…4 mm² - flexible with cable end
Fixing mode
35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate)
Mounting position
Horizontal; Vertical
Width
45 mm
Height
101 mm
Depth
78.5 mm
Product weight
0.28 kg
Colour
Dark grey
Standards
EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ; IEC/EN 60335-1:Clause 30.2
Product certifications
CCC; UL; CSA; EAC; ATEX; LROS (Lloyds register of shipping); BV; RINA; DNV-GL; UKCA
IK degree of protection
IK04
IP degree of protection
IP20 conforming to IEC 60529
Climatic withstand
conforming to IACS E10
Ambient air temperature for storage
-40…80 °C
Fire resistance
960 °C conforming to IEC 60695-2-11
Ambient air temperature for operation
-20…60 °C
Mechanical robustness
Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz
Operating altitude
<= 2000 m
Number of Units in Package 1
1
Number of Units in Package 2
20
Number of Units in Package 3
320
Country of origin
FR
Warranty (in months)
18
Rated operation power at AC-3, 400 V
4 kW
With integrated auxiliary switch
No
Rated permanent current Iu
10 A
With integrated under voltage release
No
Number of poles
3
Rated operating voltage
690 V
Overload release current setting
6–10 A
Power loss
2.5 W
Degree of protection (IP)
IP20
With thermal overload protection
Yes
Type of electrical connection of main circuit
Spring clamp connection
Type of control element
Push button
Switch off technique
Thermomagnetic
Rated operation power at AC-3, 230 V
2.2 kW
Rated short-circuit breaking capacity Icu at 400 V, AC
100 kA
Adjustment range undelayed short-circuit release
138 A
Phase failure sensitive
Yes
Device construction
Complete device in housing

Standards & Compliance

HS Code
8536.20

Cross References

  • EAN 3389110346459
  • SAP 1000075224
  • Code 8800744

Product Documentation

Document preview: Schneider Electric GV2ME143 — OEM Product Page

Catalogue entry last verified: 2026-09-29. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.

Frequently asked questions

Where can I buy GV2ME143?
GV2ME143 can be ordered from cballast.com as a Schneider Electric catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
What is the manufacturer part number for this Schneider Electric product?
The manufacturer part number is GV2ME143.
What is the HS code for GV2ME143?
The customs tariff (HS) code for GV2ME143 is 8536.20.
Who manufactures GV2ME143?
GV2ME143 is a Schneider Electric product in the Electrical Components range.
Is a datasheet available for GV2ME143?
Yes — the GV2ME143 datasheet can be viewed and downloaded on this page.
What is the minimum order quantity for GV2ME143?
The minimum order quantity is 1.
Is GV2ME143 available?
Yes — GV2ME143 is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).