Danfoss GD Heavy Duty gas detection unit, ammonia (R717) electrochemical, 0–5000 ppm, LCD, wall-mount (148H6031)
Danfoss

Danfoss GD Heavy Duty gas detection unit, ammonia (R717) electrochemical, 0–5000 ppm, LCD, wall-mount

Part number148H6031Item numberCB-DANF-148H6031EAN / GTIN5714279919738HS code9027.10
Hazardous Area Equipment
Fixed Gas Detection
MOQ:1

Pricing

Request a quote

We reply within 24 hours

Product Description

Danfoss GD Heavy Duty fixed gas detection unit, code 148H6031, a factory-calibrated wall-mount detector for ammonia (R717) in refrigeration machinery rooms, cold stores and process plant. Electrochemical sensing element with a 0–5000 ppm measuring range and two-level alarm relays (pre-alarm 1000 ppm, main alarm 4500 ppm). On-board LCD display for local annunciation. Supplied as a complete unit with mounting kit, cable gland and a factory calibration certificate. Supply 16–28 V DC. Integrates with Danfoss AK-SM system managers and standard alarm panels. HS 9027.10. OEM P/N 148H6031.

Technical Specifications

Type
Gas detection unit — GD Heavy Duty
Code number
148H6031
Detected gas
ammonia (R717)
Sensor technology
electrochemical
Measuring range
0–5000 ppm
Pre-alarm (low) set point
1000 ppm
Main alarm (high) set point
4500 ppm
Local annunciation
LCD display
Supply voltage
16–28 V DC
Operating temperature
-20 to +50 °C
Enclosure
wall-mount, includes mounting kit and cable gland
Supplied with
factory calibration certificate
Approvals
EU RoHS; China RoHS
EAN
5714279919738
Net weight
1.3 Kilogram
Product group
Sensors
Alarmlimits high [ppm] sensor1
4500 ppm
Alarmlimits low [ppm] sensor1
1000 ppm
China RoHS compliance
Yes
Division
40
Equipment
LCD Display
EU RoHS compliance
Yes
Gas detecting sensor version
Heavy Duty
Parts included
ATEX/IECEx certificate
PFAS content [Yes/No]
No
Power consumption [A]
0.13 A
REACH Candidate List substances
No
Refrig. range [ppm] sensor1 [max]
5000 ppm
Refrig. range [ppm] sensor1 [min]
0 ppm
Refrigerants
R717
Relative humidity (RH) [%] [max]
90 %
Relative humidity (RH) [%] [min]
15 %
Response delay [s]
0 s
Sensor 1 type
Electrochemical
Supply voltage [V] DC [max]
28 V
Supply voltage [V] DC [min]
16 V
Temperature range [°C] [max]
50 °C
Temperature range [°C] [min]
-20 °C
Temperature range [°F] [max]
122 °F
Temperature range [°F] [min]
-4 °F

Standards & Compliance

Temperature Range
-20 to +50 °C
HS Code
9027.10

Compatibility & Fitment

Confirm the target gas (ammonia (R717)), detection range (0–5000 ppm) and supply voltage (16–28 V DC) match the installation before ordering; sensor element is gas-specific and factory-calibrated. Alarm set points 1000/4500 ppm are the Danfoss defaults; display-equipped GD versions allow the thresholds to be reconfigured.

Not sure if it fits? Email sales@cballast.com with your equipment serial number or photos — we confirm fit before you order.

Product Documentation

Document preview: Danfoss Gas Detection Unit (GD) — Specification Sheet

Catalogue entry last verified: 2026-08-13. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.

Frequently asked questions

Where can I buy 148H6031?
148H6031 can be ordered from cballast.com as a Danfoss catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
What is the manufacturer part number for this Danfoss product?
The manufacturer part number is 148H6031.
What is the HS code for 148H6031?
The customs tariff (HS) code for 148H6031 is 9027.10.
Who manufactures 148H6031?
148H6031 is a Danfoss product in the Hazardous Area Equipment range.
Is a datasheet available for 148H6031?
Yes — the 148H6031 datasheet can be viewed and downloaded on this page.
What is the minimum order quantity for 148H6031?
The minimum order quantity is 1.
Is 148H6031 available?
Yes — 148H6031 is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).