Danfoss AVQT flow and temperature controller, PN 25, DN 15, flow range 0.03–0.9 m³/h, Kvs 1.6 m³/h, External thread G 3/4 A (ISO 228/1), via tailpieces
Pricing
Request a quote
We reply within 24 hours
Product Description
Danfoss AVQT (003H6759) — self-acting flow and temperature controller, PN 25, DN 15, for district heating and cooling systems. The AVQT holds the flow constant and limits it to the set maximum and closes on rising temperature. It accepts an AVT thermostatic actuator, or an STM safety temperature monitor where over-temperature protection is required. It comprises a control valve with adjustable flow restrictor, a connection neck for the thermostatic actuator, and a pressure actuator with one control diaphragm. Flow range 0.03 - 0.9 m³/h; flow-restrictor differential pressure 0.2 bar; Kvs 1.6 m³/h. Maximum differential-pressure range 20 bar; media temperature 2–150 °C; cavitation factor z ≥ 0.6; seat leakage 0.02 % Kvs (IEC 60534). Temperature is set by the separately ordered AVT thermostatic actuator, setting ranges 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately); the controller is delivered assembled with the impulse tube between valve and actuator, the actuator ordered separately. Combined with AMV(E), AVT or STM actuators the controller is type-tested to EN 14597. Valve body Red bronze CuSn5ZnPb (Rg5); valve cone Dezincing free brass CuZn36Pb2As; seat Stainless steel, mat. 1.4571; control diaphragm EPDM. Connection External thread G 3/4 A (ISO 228/1), via tailpieces. Mounting version Free. Permissible media: District heating/cooling circulation water (Glycolic water up to 30%), pH 7–10. OEM P/N 003H6759. Technical data quoted verbatim from store.danfoss.com (code 003H6759) and the Danfoss AVQT / AVQMT (PN 25) data sheet. 1.4571; control diaphragm EPDM; Pressure rating: PN 25 (max. differential-pressure range 20 bar); Temperature range: 2 to 150 °C (district heating/cooling water); HS code: 8481.80. Used in commercial refrigeration, provision-room cooling and reefer plant rooms across HFC, HFO and CO2 (R744) refrigerants. No.
Technical Specifications
- Code number
- 003H6759
- Type
- AVQT
- Product group
- Pressure and flow controllers
- Function
- Self-acting flow and temperature controller (limits max. flow; closes on rising temperature; accepts AVT/STM thermostatic actuator)
- Valve size
- DN 15
- Pressure class
- PN 25
- Connection
- External thread G 3/4 A (ISO 228/1), via tailpieces
- Kvs value
- 1.6 m³/h
- Flow rate range
- 0.03 - 0.9 m³/h
- Flow restrictor differential pressure (Δpb)
- 0.2 bar
- Max. differential pressure range
- 20 bar
- Media temperature
- 2 - 150 °C
- Temperature setting ranges (AVT actuator, ordered separately)
- 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately)
- Media pH
- 7 - 10
- Cavitation factor z
- ≥ 0.6
- Seat leakage rate
- 0.02 % Kvs (IEC 60534)
- Mounting version
- Free
- Stem position
- Normally open
- Stroke
- 5 mm
- Type test
- EN 14597 (controller combined with AMV(E) / AVT / STM actuator)
- Permissible media
- District heating/cooling circulation water (Glycolic water up to 30%)
- Valve body material
- Red bronze CuSn5ZnPb (Rg5)
- Valve cone material
- Dezincing free brass CuZn36Pb2As
- Valve seat material
- Stainless steel, mat. No. 1.4571
- Actuator diaphragm
- EPDM
- EU RoHS compliance
- Yes with exemptions (6(c))
- REACH Candidate List substance
- Lead (CAS no. 7439-92-1)
- China RoHS
- Out of scope
- Net weight
- 3.048 kg
- Gross weight
- 3.048 kg
- EAN
- 5702421542804
Standards & Compliance
- Material
- Valve body Red bronze CuSn5ZnPb (Rg5); valve cone Dezincing free brass CuZn36Pb2As; valve seat Stainless steel, mat. No. 1.4571; control diaphragm EPDM
- Pressure Rating
- PN 25 (max. differential-pressure range 20 bar)
- Temperature Range
- 2 to 150 °C (district heating/cooling water)
- HS Code
- 8481.80
Compatibility & Fitment
Danfoss AVQT for DN 15 district-heating/cooling combined flow limiting and temperature control at PN 25. Set the maximum flow within 0.03 - 0.9 m³/h using the adjustable flow restrictor (Kvs 1.6 m³/h). Fit a Danfoss AVT thermostatic actuator to set the temperature, or an STM safety temperature monitor for over-temperature protection (ordered separately). Temperature setting ranges 10–40 / 20–70 / 40–90 / 60–110 °C and 10–45 / 35–70 / 60–100 / 85–125 °C (AVT actuator, ordered separately). Confirm the connection (External thread G 3/4 A (ISO 228/1), via tailpieces) and pressure class (PN 25) match the pipework; order the matching tailpiece/union-nut or flange set separately. Maximum differential-pressure range 20 bar, media temperature up to 150 °C.
Product Documentation
More from Danfoss

Danfoss
Danfoss AVQT flow and temperature controller, PN 25, DN 15, flow range 0.07–1.6 m³/h, Kvs 2.5 m³/h, External thread G 3/4 A (ISO 228/1), via tailpieces
003H6760

Danfoss
Danfoss AVQT flow and temperature controller, PN 25, DN 15, flow range 0.07–2.4 m³/h, Kvs 4 m³/h, External thread G 3/4 A (ISO 228/1), via tailpieces
003H6761

Danfoss
Danfoss AVQT flow and temperature controller, PN 25, DN 20, flow range 0.16–3.5 m³/h, Kvs 6.3 m³/h, External thread G 1 A (ISO 228/1), via tailpieces
003H6762

Danfoss
Danfoss AVQT flow and temperature controller, PN 25, DN 25, flow range 0.2–4.5 m³/h, Kvs 8 m³/h, External thread G 1 1/4 A (ISO 228/1), via tailpieces
003H6763

Danfoss
Danfoss AVQT flow and temperature controller, PN 25, DN 32, flow range 0.4–10 m³/h, Kvs 12.5 m³/h, Flange DN 32 (EN 1092-2)
003H6767

Danfoss
Danfoss AVQT flow and temperature controller, PN 25, DN 40, flow range 0.8–12 m³/h, Kvs 20 m³/h, Flange DN 40 (EN 1092-2)
003H6768

Danfoss
Danfoss AVQT flow and temperature controller, PN 25, DN 50, flow range 0.8–15 m³/h, Kvs 25 m³/h, Flange DN 50 (EN 1092-2)
003H6769

Danfoss
Danfoss AVQMT flow and temperature controller with integrated control valve (PICV), PN 25, DN 15, flow range 0.01–0.18 m³/h, Kvs 0.4 m³/h, External thread G 3/4 A (ISO 228/1), via tailpieces
003H6770
Technical guides
- Cross-Referencing Danfoss Refrigeration Components by IMPA and OEM Code
- Danfoss Product Code Decoder — 003Z, 013G, 017B, 023U, 027L, 032F, 060G, 060H, 065B, 065Z, 068Z, 084H, 132F, 148B Series (Complete Reference)
- Danfoss Maneurop MTZ Reciprocating Compressors — Model Range, Voltage Codes and Replacement Guide
Catalogue entry last verified: 2026-08-29. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.
Frequently asked questions
- Where can I buy 003H6759?
- 003H6759 can be ordered from cballast.com as a Danfoss catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
- What is the manufacturer part number for this Danfoss product?
- The manufacturer part number is 003H6759.
- What is the HS code for 003H6759?
- The customs tariff (HS) code for 003H6759 is 8481.80.
- Who manufactures 003H6759?
- 003H6759 is a Danfoss product in the HVAC & Refrigeration range.
- Is a datasheet available for 003H6759?
- Yes — the 003H6759 datasheet can be viewed and downloaded on this page.
- What is the minimum order quantity for 003H6759?
- The minimum order quantity is 1.
- Is 003H6759 available?
- Yes — 003H6759 is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).