The refrigeration solenoid workhorse decoded: EVR sizes 2 to 40 and what the number means, direct against servo operation and the minimum pressure differential that explains most "valve will not open" calls, NC against NO versions, EVRH for high-pressure duty, the clip-on coil system (coil families, voltage codes, AC against DC, cable plugs) that lets a dead coil be changed without opening the line, seal and service kits by size group, the cross-reference logic to Castel and Emerson-Alco solenoids, and the RFQ lines that identify a valve exactly from what is stamped on it.
| Marking element | Example | Meaning |
|---|---|---|
| Family + size | EVR 6 | Capacity/connection class — e.g. the EVR 6 3/8" solder valve (032F1212) |
| Code number | 032F1212 | The exact orderable variant: size + connection type/size + NC/NO + options. The 032F prefix is the solenoid-valve program; quote this number and the identification is finished |
| Connection | 3/8" ODF solder, or SAE flare | Solder (LD suffix habits in wholesale listings) dominates fixed installs; flare survives in service work |
| NC / NO | NC default; NO marked | NC opens when energised (liquid-line standard); NO closes when energised (hot gas, defrost schemes) |
| EVRH | EVRH 6 | High-pressure variant for modern refrigerant duties — kits differ (032F8165), do not mix with standard EVR kits |
| Manual stem | Spindle under a cap | Lets the plant run with a dead coil — and tells you at service why a "closed" valve is passing: the stem was left open |
If the plate is unreadable: measure the connection (type and size), note NC/NO from the schematic, read the coil's own label for voltage, and send photos of body and stamping — that identifies the 032F code in one pass. The Danfoss code decoder guide covers the neighbouring number families (060, 018F, 032F, 084).
| Construction | Sizes (typical) | Opens at | Consequence |
|---|---|---|---|
| Direct-operated | The small end of the family (EVR 2/3 class) | Zero pressure differential — the coil lifts the plunger directly | Works on equalised lines, bypasses, small capacities |
| Servo-operated (pilot + diaphragm/piston) | EVR 6 and up | Needs a minimum differential (of the order of a few hundredths of a bar) to use line pressure as the muscle | On an equalised or dead line it opens a pilot path only — the classic "energised but not flowing" call |
Three field consequences worth a technician's tattoo: a servo EVR cannot be used as a vacuum-breaking or zero-Δp bypass valve — select a direct-operated size or a different family; an oversized solenoid on a lightly loaded liquid line may never see its minimum differential and will chatter or hunt — size by capacity, not by pipe; and MOPD (maximum opening pressure differential) is a coil-power property — a 10 W coil opens against less differential than a 20 W DC coil, so coil substitutions change the valve's capability, not just its voltage.
| Coil family (letters) | Character | Typical codes | Catalogue anchors |
|---|---|---|---|
| BB class — AC clip-on, 10 W | The standard AC coil for EVR bodies | BB230AS (230 V), BB024AS-class (24 V 50 Hz) | BB230AS DIN-spade; 018F7358 24 V 10 W |
| BN class — DC, 20 W | DC supply duty (marine, mobile, control systems) | BN024DS (24 V DC) | BN024DS; see also the BN024AS 24 V AC 24 W step-up |
| BE class and siblings | Variants by terminal style and power | BE230AS class | Quoted by code |
| Code logic | Letters = family/power class; digits = voltage; A/D = AC/DC; final S-class letters = terminal type (DIN spade, cable, terminal box). The 018F prefix on the code number is the coil programme itself | ||
| Cable plugs | DIN-spade plugs with or without indicator lamp | By coil voltage | 230 V plug, 24 V plug — fits 018F/018Z/042N type-B coils |
Replacement rules that prevent returns: match voltage AND frequency AND AC/DC exactly (a 230 V AC coil on 24 V does nothing; a 24 V AC coil on 24 V DC burns); never energise a clip-on coil off the valve (it overheats within minutes without the core); and when a coil has burned once, check why — overvoltage, moisture in the plug, or a stuck armature — before fitting its twin. A spare coil per voltage class belongs in every plant's drawer: it is the single highest-frequency refrigeration RFQ line we see, precisely because the body stays in the line.
| Duty | Selection logic | Partner components |
|---|---|---|
| Liquid line (pump-down control, tight shut-off at stop) | NC, sized to liquid capacity at the design Δp — the standard case | Filter drier upstream, sight glass downstream, TEV per the expansion valve finder |
| Suction line | Larger body for the vapour volume at low Δp — size from capacity tables, never by pipe diameter | Check valve logic per system design |
| Hot gas (defrost, bypass) | NO versions and high-temperature coils by scheme; EVRH territory at higher pressures | Defrost control per the EKC / AK-CC controller guide |
| Zero-Δp or equalised lines | Direct-operated small sizes only | — |
Installation discipline the datasheet assumes: flow arrow respected, coil removable upward with service clearance, body protected from solder heat (wrap it wet or disassemble per instructions — overheated PTFE seats are the hidden cause of "new valve leaks"), and a strainer or drier upstream because servo pilots and scale do not coexist. Industrial-refrigeration positions (ammonia, large CO2) belong to the ICF/SVA programme instead — see the SVA/ICF guide; water and neutral-fluid duty belongs to the EV2xx family in the solenoid valve finder.
Cross-brand method (full tables in the cross-reference guide): match (1) duty and NC/NO function, (2) capacity at the actual refrigerant and Δp — not nominal size names across brands, (3) connection type and size, (4) refrigerant/pressure approval (standard vs high-pressure variants), (5) coil voltage and power separately, because every maker sells coil and body apart. Castel's 10x8-series and Emerson/Alco's 200RB class map onto EVR duties cleanly at the class level; the exact pairing is by capacity table, which we run per line. A complete RFQ line reads: code number if known (032F…), else family+size, connection, NC/NO, refrigerant, and the coil as its own line (voltage/frequency/AC-DC, plug wanted or not). ASCO-pattern general solenoids on air/water live in their own world — the 8210 cross-reference — do not cross refrigerant valves against them.
How buying works at cballast. We stock and quote EVR bodies, the full coil programme, plugs and service kits, cross Castel and Alco positions by capacity table with the basis stated per line, and flag the servo/minimum-Δp trap when an inquiry smells like a zero-differential application. Accounts are vetted at onboarding; first order prepaid; established accounts on credit terms with repeat discounts; public bodies and utilities invoiced against purchase order from the first order. RFQs to sales@cballast.com.