The electronic layer of commercial and marine refrigeration decoded for buyers and service engineers: what EKC case/evaporator controllers and AK-CC controllers for AKV pulse valves actually do, how variants differ (relay outputs, defrost schemes, comms like Modbus and LON), the sensor question that decides every replacement (PT1000 against NTC and probe placement), the AKV pulse-valve partnership that separates AK-CC duty from thermostatic systems, accessories from terminals to real-time-clock modules, replacement rules when a controller dies mid-season, and the cross-class map to Eliwell and Carel territory.
| Family / class | Duty | Expansion device it assumes | Notes |
|---|---|---|---|
| EKC 100-class (e.g. EKC 102) | Basic case/room temperature + defrost | Thermostatic (TEV) or solenoid-controlled systems | The economical panel controller; terminals per the 084B connector sets |
| EKC 200-class (EKC 202 A/B/C/D) | Full case/evaporator control: temperature, defrost (natural/electric), fans, alarms | TEV/solenoid systems | D-variants add fieldbus — the 202D1 (LON/Modbus) is the networked workhorse |
| AK-CC 550 (A/B) | Evaporator control with electronic injection | AKV pulse valves | 550A standard; 550B with second defrost output for twin-section cases |
| AK-CC 55-class compacts | Case-mounted electronic injection | AKV | Per case format |
| AK-PC class (context) | Pack/compressor capacity control | — | The suction-side sibling; shares accessories like the AK-OB 101A RTC |
System architecture in one sentence: EKC-class controllers manage the cold space around conventional expansion; AK-CC + AKV replace the thermostatic valve with pulse-controlled electronic injection — tighter temperatures, better part-load behaviour, and a different parts list. Identify which world a dead controller lived in before quoting its successor; the valve on the coil answers it instantly.
| Check | Why it decides the swap |
|---|---|
| Exact type + variant from the label (084B/080Z code number) | The code number carries relay set, defrost scheme and comms — "EKC 202" alone under-specifies; the 084B number does not |
| Supply voltage | 230 V and low-voltage versions exist across the families — read the label, not the habit |
| Probe type and count | PT1000-class probes in this architecture; verify each input's probe and placement (air-on, air-off/defrost-stop, product) — mismatched probe type reads tens of degrees wrong |
| Defrost method | Natural, electric, hot gas — the variant must carry the outputs the case wires (the 550B's second defrost output exists for a reason) |
| Comms | If the plant monitors via Modbus/LON/system manager, the replacement must speak it (D-variants, gateway hardware) or the alarm chain silently dies |
| Parameter set | Photograph or export the old settings if the unit still boots; otherwise commission from the case schedule — setpoint, differential, defrost times, fan logic, alarm limits |
| Hardware completion | Terminal sets (7-pole/2-pole), panel cut-out match, RTC module where schedules run offline (AK-OB 101A) |
The honest mid-season playbook: a same-code replacement plus fresh terminals plus the parameter sheet is a one-hour job; a "similar" controller from another class is a redesign performed at 22:00 in a provision room. We quote same-code first, successor-code (with the parameter mapping flagged) second, cross-class only when asked.
Probe discipline, because most "controller problems" are probe findings: air-on (return air) is the control probe for case temperature; air-off (supply) tightens display-case control in the schemes that use both; the defrost-stop probe sits on the coil, in the fins where ice lingers longest — a defrost that "runs too long" usually has this probe in the wrong place, not a wrong parameter; product/simulant probes drive alarms that reflect food temperature rather than air swings. Replace probes with the matching type (PT1000-class for this family), verify with an ice-bath or calibrator (calibrator guide), and route probe cables away from mains — induced noise reads as wandering temperatures. Probe stock per voltage/type belongs in the same drawer as the EVR coils: the consumables that keep refrigeration RFQs small and fast instead of large and desperate.
| Ecosystem | Controllers | Cross-class reality |
|---|---|---|
| Danfoss (this guide) | EKC panel classes, AK-CC/AK-PC with AKV injection, system managers above them | Within-family: clean same-code/successor logic by 084B/080Z number |
| Eliwell | IDNext/ICPlus classes — see our Eliwell & Penn guide and stocked IDNext 902 P6D, ICPlus 11I | Function-level crosses for basic case control (thermostat+defrost+fan) are routine; probe types (NTC vs PT1000) and relay ratings must be re-checked line by line |
| Carel, Penn/Johnson classes | Parallel programmes | Same function-level logic; electronic-injection systems do NOT cross between ecosystems — controller + valve + algorithm are one system |
The rule that keeps crosses honest: basic case controllers cross on function; injection systems do not cross at all. An EKC 202-class duty can be served by an Eliwell IDNext-class unit with probes and relays re-verified; an AK-CC + AKV case stays Danfoss (or gets re-engineered deliberately). Every crossed line we quote names its basis and its probe consequence — the same honesty rule as the refrigeration cross-reference guide applies to the electronics.
How buying works at cballast. We stock EKC and AK-CC controllers, probes, terminal sets and RTC/display accessories, quote same-code and successor paths with the parameter consequences stated, and cross to Eliwell-class hardware only at the function level with probes re-specified. Accounts are vetted at onboarding; first order prepaid; established accounts on credit terms with repeat discounts; public bodies and utilities invoiced against purchase order from the first order. RFQs to sales@cballast.com.
Standards and sources referenced: Danfoss EKC and AK-CC/AK-PC product documentation and parameter guides, AKV electronic-injection system documentation; Eliwell programme data for the cross-class map; EN 60730-class controller practice.
Questions on a controller you cannot identify or a cross you are unsure of: write to sales@cballast.com. We answer whether or not you buy from us.