Danfoss KP and RT Switches — Ranges, Reset Logic and Replacement Reading

Selection guide compiled by cBallast. 3-page PDF; the full content is on this page.
Brand
Danfoss
Subject
Pressure and temperature switches
Document type
Selection guide
Reference
2026 edition
Issued
2026-10-18
Pages
3
Format
Web page and PDF

The compact KP family versus the industrial RT line: reading range and differential, auto versus manual reset (and why the law of the machine decides it), LP/HP duty splits, connection styles from flare to solder, and the accessories that keep decades-old switches in approved service.

Two families, one job, different build points

KP (compact)RT (industrial)
BuildCompact bellows switch for refrigeration and light industryLarger industrial housing, wider ranges, finer adjustability
Stocked examplesKP1 LP 0.2–7.5 bar auto, KP1E solder/flare, KP5 HP 8–32 bar manual, KPR5 6–18 barRT 200, 0.2–6 bar; temperature versions like the RT124, 200–300 range in auto and manual reset
Typical dutyLP cut-out, HP safety, fan cyclingPlant monitoring, marine and process panels, class-approved duties

The four facts on every nameplate

Accessories keep the installed base alive: RT hand knobs, seal screws for tamper-evident settings, and brackets ship as line items. Around 160 KP and 180 RT rows are stocked under Danfoss — quote the type code and range off the old switch's plate and the current equivalent returns within 24 hours (type codes have survived decades, which is why RT switches from the 1980s still replace one-for-one).

Frequently asked questions

Should a high-pressure cut-out be auto or manual reset?
Manual, almost always — an HP trip means something is wrong (condenser fan, airflow, overcharge), and auto-reset would cycle the compressor against the fault. Many approvals mandate manual reset on the safety HP switch outright.
What does the differential on a pressure switch do?
It is the distance between switching points: cut-out at the set point, cut-in differential-lower (or higher, by duty). Wide differential = fewer, longer cycles; too narrow and compressors short-cycle to death.
Can an RT switch replace a KP in the same duty?
Functionally where range, differential and approvals line up — the RT is the larger, finer-adjustment industrial build. Panel cut-outs, connection and bracket differ, so it is a planned substitution, not a drop-in.
Why does my pressure switch chatter near the set point?
Set point at the extreme end of the range, vibration at the bellows, or pulsation from the machine — a damping loop or a mid-range switch model fixes what contact cleaning cannot.
Are these switches still acceptable where a transmitter is specified?
Different instruments: a switch gives a hard contact at a point — ideal for safety chains; a transmitter gives the continuous signal control systems want. Modern panels commonly run both, and the dedicated guide maps the split.
Open / Download PDF

Compiled by cBallast for identification and cross-reference. Part numbers, designations and trademarks belong to their respective manufacturers. Confirm ratings and dimensions against the manufacturer's current documentation and the nameplate of the installed equipment before ordering or installation.