Schneider Electric Circuit breaker, ComPacT NSX100R, 200KA/415VAC, 3 poles, MicroLogic 6.2E-M trip unit 80A C10R36M080
Pricing
Request a quote
We reply within 24 hours
Product Description
Schneider Electric C10R36M080 Circuit breaker NSX100R with motor protection and energy metering 6.2E-M 100A 3P 200kA/440VAC - 45kA/690VAC.
Technical Specifications
- Manufacturer part number (MPN)
- C10R36M080
- EAN / GTIN
- 3606482001459
- HS code
- 8536.90
- Sales unit
- pcs
- Rated current
- 100 A
- Number of poles
- 3P
- Range
- ComPacT
- Product name
- ComPacT NSX
- Device short name
- NSX100R
- Product or component type
- Circuit breaker
- Device application
- Motor protection
- Poles description
- 3P
- Protected poles description
- 3D
- [In] rated current
- 80 A at 65 °C
- [Ue] rated operational voltage
- 690 V AC 50/60 Hz
- Network type
- AC
- Network frequency
- 50/60 Hz
- Suitability for isolation
- Yes conforming to EN/IEC 60947-2
- Utilisation category
- Category A
- Breaking capacity
- 200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
- Breaking capacity code
- R 200 kA 415 V AC
- Trip unit name
- MicroLogic 6.2 E-M
- Trip unit technology
- Electronic
- Trip unit protection functions
- LSIG
- Control type
- Toggle
- Circuit breaker mounting mode
- Fixed
- [Ui] rated insulation voltage
- 800 V AC 50/60 Hz
- [Uimp] rated impulse withstand voltage
- 8 kV
- [Ics] rated service breaking capacity
- 200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
- Mechanical durability
- 20000 cycles
- Electrical durability
- 20000 cycles at 440 V In/2; 10000 cycles at 440 V In; 10000 cycles at 690 V In/2; 5000 cycles at 690 V In
- Power dissipation per pole
- 4.7 W
- Mounting support
- Backplate
- Mounting position
- Horizontal and vertical; Flat on the back
- Upside connection
- Front
- Downside connection
- Front
- Connection pitch
- 35 mm
- Protection type
- L : for overload protection (long time); So : for short time short-circuit protection; I : for instantaneous short-circuit protection; G : for ground fault protection
- Trip unit rating
- 80 A at 65 °C
- Motor tripping class
- 5; 30; 20; 10
- Complementary motor protection
- Stalled rotor; Phase unbalance; Protracted starting time; Underload
- Long-time pick-up adjustment type Ir (thermal protection)
- Adjustable 9 settings
- [Ir] long-time protection pick-up adjustment range
- 35...80 A
- Long-time protection delay adjustment type tr
- Adjustable
- [tr] long-time delay adjustment range
- 120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20; 720 s at 1.5 x Ir for trip class 30; 38 s at 6 x Ir for trip class 30; 30 s at 7.2 x Ir for trip class 30
- Thermal memory
- 20 minutes before and after tripping
- Short-time protection pick-up adjustment type Isd
- Adjustable
- [Isd] Short-time protection pick-up adjustment range
- 5...13 x Ir
- Short-time protection delay adjustment type tsd
- Fixed
- Instantaneous protection pick-up adjustment type Ii
- Fixed
- [Ii] instantaneous protection pick-up adjustment range
- 1200 A
- Ground-fault protection pick-up adjustment type Ig
- Adjustable 9 settings
- [Ig] ground-fault pick-up adjustment range
- 0.6...1 x In for In = 25 A; 0.3...1 x In for In = 50 A; 0.2...1 x In for In > 50 A; Ig enable on/off
- Ground-fault protection time delay adjustment type tg
- Adjustable 5 settings
- [tg] Ground-fault time delay adjustment range
- 0…0.4 s
- Earth-leakage protection
- Without
- Zone selective interlocking ZSI
- With
- Number of slots
- 5 slot(s)
- Local signalling
- Flashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point
- Display type
- LCD display
- Type of measurement
- Energy meter
- Communication of data
- Power quality; Demand current and power; Time-stamped histories and event tables; Protection and alarm settings; Instantaneous and demand values; Thermal image function; Maximeters/minimeters; Phase sequence; Maintenance indicators; Energy metering
- Width (W)
- 105 mm
- Height (H)
- 161 mm
- Depth (D)
- 86 mm
- Product weight
- 2.05 kg
- Standards
- EN/IEC 60947-2
- Overvoltage category
- III
- Electrical shock protection class
- Class II on front face
- Pollution degree
- 3 conforming to IEC 60664-1
- IP degree of protection
- IP40 conforming to IEC 60529
- IK degree of protection
- IK07 conforming to IEC 62262
- Ambient air temperature for operation
- -25…70 °C
- Ambient air temperature for storage
- -40…85 °C
- Relative humidity
- 0…95 %
- Operating altitude
- 0...2000 m without derating; 2000 m...5000 m with derating
- Warranty (in months)
- 18
Standards & Compliance
- HS Code
- 8536.90
Cross References
- EAN 3606482001459
- SAP 1200533276
- Code 82687713
Product Documentation
More from Schneider Electric

Schneider Electric
Rev.coupling.rod 3P Kit G115-225
LA9G3760

Schneider Electric
Sign Frame flush with sign (ZBYF2303)

Schneider Electric
Transparent door PrismaSeT G wall 9MOD
LVS08133

Schneider Electric
Schneider Electric Control unit MicroLogic 5.0E, ComPacT NS630B to NS1600 withdrawable and manually operated, selective protections C5EWM

Schneider Electric
Metal plate 54X72 PLS
NSYPMM5472

Schneider Electric
Schneider Electric TeSys K control relay - 4 NO - <= 690 V - 220...230 V AC coil CA2KN40M7

Schneider Electric
Schneider Electric Inner Corner Tir+ IH 120/60 White
5427085

Schneider Electric
S3D 300X400X200 with Glassdoor
NSYS3D3420T
Technical guides
Catalogue entry last verified: 2026-09-29. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.
Frequently asked questions
- Where can I buy C10R36M080?
- C10R36M080 can be ordered from cballast.com as a Schneider Electric catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
- What is the manufacturer part number for this Schneider Electric product?
- The manufacturer part number is C10R36M080.
- What is the HS code for C10R36M080?
- The customs tariff (HS) code for C10R36M080 is 8536.90.
- Who manufactures C10R36M080?
- C10R36M080 is a Schneider Electric product in the Electrical Components range.
- Is a datasheet available for C10R36M080?
- Yes — the C10R36M080 datasheet can be viewed and downloaded on this page.
- What is the minimum order quantity for C10R36M080?
- The minimum order quantity is 1.
- Is C10R36M080 available?
- Yes — C10R36M080 is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).