Cam switch 3 steps +0 1-Pole bun (K1C003QCH)
Schneider Electric

Cam switch 3 steps +0 1-Pole bun

Part numberK1C003QCHEAN / GTIN3389110978728HS code8536.50
Switchgear & Protection
Disconnect Switches
MOQ:1

Pricing

Request a quote

We reply within 24 hours

Product Description

Schneider Electric K1C003QCH Cam Switch 3 steps +0 1-pole bottom.

Technical Specifications

Manufacturer part number (MPN)
K1C003QCH
EAN / GTIN
3389110978728
Sales unit
pcs
Package quantity
10 pcs
Number of poles
1P
Range of product
Harmony K
Product or component type
Complete cam switch
Component name
K1
[Ith] conventional free air thermal current
12 A
Mounting location
Front
fixing mode
Ø 22 mm hole
Cam switch head type
With front plate 45 x 45 mm
Type of operator
Black handle, length = 35 mm
Rotary handle padlocking
Without
Presentation of legend
With metallic legend, 0 - 1 - 2 - 3 black marking
Cam switch function
Stepping switch
Return
Without
Off position
With Off position
Poles description
1P
Switching positions
Right: 0° - 45° - 90° - 135°
IP degree of protection
IP65 conforming to IEC 60529
Number of steps
3
Switching angle
45 °
[Ui] rated insulation voltage
690 V (pollution degree 3) conforming to IEC 60947-1
[Ithe] conventional enclosed thermal current
10 A
Rated operational power in W
10500 W AC-21, 500...660 V 3 phases conforming to IEC 947-3; 1100 W AC-3, 230 V 3 phases conforming to IEC 947-3; 1500 W AC-23A, 230 V 3 phases conforming to IEC 947-3; 1500 W AC-3, 400 V 1 phase conforming to IEC 947-3; 1500 W AC-3, 400 V 3 phases conforming to IEC 947-3; 1500 W AC-3, 500 V 3 phases conforming to IEC 947-3; 1500 W AC-3, 690 V 3 phases conforming to IEC 947-3; 2200 W AC-23A, 400 V 3 phases conforming to IEC 947-3; 2200 W AC-23A, 500 V 3 phases conforming to IEC 947-3; 2200 W AC-23A, 690 V 3 phases conforming to IEC 947-3; 4800 W AC-21, 230 V 3 phases conforming to IEC 947-3; 600 W AC-3, 230 V 1 phase conforming to IEC 947-3; 8300 W AC-21, 400 V 3 phases conforming to IEC 947-3
[Ie] rated operational current AC
1.8 A at 690 V AC-3 3 phases conforming to IEC 947-3; 2.8 A at 500 V AC-3 3 phases conforming to IEC 947-3; 2.8 A at 690 V AC-23A 3 phases conforming to IEC 947-3; 3.3 A at 400 V AC-3 3 phases conforming to IEC 947-3; 3.8 A at 500 V AC-23A 3 phases conforming to IEC 947-3; 4.6 A at 230 V AC-3 3 phases conforming to IEC 947-3; 4.8 A at 400 V AC-23A 3 phases conforming to IEC 947-3; 5.6 A at 230 V AC-23A 3 phases conforming to IEC 947-3; 1 A at 500 V AC-15 conforming to IEC 947-5-1; 2 A at 400 V AC-15 conforming to IEC 947-5-1; 3 A at 230 V AC-15 conforming to IEC 947-5-1
Electrical durability
1000000 cycles AC-15; 1000000 cycles AC-21; 500000 cycles AC-23; 500000 cycles AC-3
Maximum operating rate
2.5 cyc/mn AC-21; 2.5 cyc/mn AC-23; 2.5 cyc/mn AC-3; 8.333 cyc/mn AC-15
Short-circuit current
10000 A
Short-circuit protection
16 A cartridge fuse, type gG
[Uimp] rated impulse withstand voltage
4 kV in isolating function; 6 kV conforming to IEC 947-1
Contact operation
Slow-break
positive opening
With
Electrical connection
Captive screw clamp terminals flexible, clamping capacity: 2 x 1.5 mm²; Captive screw clamp terminals solid, clamping capacity: 1 x 2.5 mm²
Mechanical durability
1000000 cycles
CAD overall width
45 mm
CAD overall height
50 mm
CAD overall depth
59 mm
Product weight
0.155 kg
Standards
IEC 60947-3 for power circuit; IEC 60947-5-1 for control circuit; CENELEC EN 50013
Product certifications
CSA 240 V 3 hp 3 phases 2 -pole(s); UL 240 V 0.33 hp 1 phase 2 -pole(s); CSA 240 V 1 hp 1 phase; UL 240 V 1 hp 3 phases
Protective treatment
TC
Ambient air temperature for operation
-25…55 °C
Ambient air temperature for storage
-40…70 °C
Shock resistance
30 gn conforming to IEC 68-2-27
Vibration resistance
5 gn conforming to IEC 68-2-6 (f = 10…150 Hz)
Overvoltage category
Class II conforming to IEC 536; Class II conforming to NF C 20-030
Number of Units in Package 1
1
Number of Units in Package 2
10
Country of origin
CZ
Warranty (in months)
18
Model
Level switch
Rated operation power at AC-3, 400 V
1.5 kW
Rated permanent current Iu
12 A
Rated operation current Ie at AC-3, 400 V
3.3 A
With zero (off) position
Yes
Housing material
Plastic
With retraction in 0-position
No
Degree of protection (IP), front side
IP65/IP67
Type of electrical connection of main circuit
Screw connection
Type of control element
Long rotary handle
Suitable for floor mounting
No
Suitable for front mounting
Yes
Suitable for distribution board installation
No
Suitable for intermediate mounting
Yes
Complete device in housing
Yes

Standards & Compliance

HS Code
8536.50

Cross References

  • EAN 3389110978728
  • SAP 1000253053
  • Code 81132579

Product Documentation

Document preview: Schneider Electric K1C003QCH — OEM Product Page

Catalogue entry last verified: 2026-09-30. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.

Frequently asked questions

Where can I buy K1C003QCH?
K1C003QCH can be ordered from cballast.com as a Schneider Electric catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
What is the manufacturer part number for this Schneider Electric product?
The manufacturer part number is K1C003QCH.
What is the HS code for K1C003QCH?
The customs tariff (HS) code for K1C003QCH is 8536.50.
Who manufactures K1C003QCH?
K1C003QCH is a Schneider Electric product in the Switchgear & Protection range.
Is a datasheet available for K1C003QCH?
Yes — the K1C003QCH datasheet can be viewed and downloaded on this page.
What is the minimum order quantity for K1C003QCH?
The minimum order quantity is 1.
Is K1C003QCH available?
Yes — K1C003QCH is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).