Eaton NZMN3-PMX350-AVE Circuit breaker
Eaton

Eaton NZMN3-PMX350-AVE Circuit breaker

Part numberNZMN3-PMX350-AVEEAN / GTIN4015081928866HS code8536.90
Electrical Components
Motor Protection Circuit Breakers
MOQ:1

Pricing

Request a quote

We reply within 24 hours

Overview

Eaton NZMN3-PMX350-AVE Circuit breaker is listed under Electrical Components / Motor Protection Circuit Breakers. HS code: 8536.90; Sales unit: pcs; Eaton catalogue number: 192335; Depth: 346 mm; Height: 260 mm; Width: 185 mm.

Technical Specifications

Manufacturer part number (MPN)
NZMN3-PMX350-AVE
EAN / GTIN
4015081928866
HS code
8536.90
Sales unit
pcs
Eaton catalogue number
192335
Depth
346 mm
Height
260 mm
Width
185 mm
Weight
16.54 kg
Compliances
RoHS conform
Certifications
IEC; IEC/EN 60947
Functions
Motor protection with class 1 energy metering; Phase failure sensitive
Accessories required
NZM3-XAVS
Amperage Rating
350 A
Application
Use in unearthed supply systems at 690 V
Circuit breaker frame type
NZM3
Fitted with
Thermal protection
Number of poles
Three-pole
Release system
Electronic release
Type
Circuit breaker
Ambient operating temperature - max
70 °C
Ambient storage temperature - max
70 °C
Ambient operating temperature - min
-25 °C
Equipment heat dissipation, current-dependent
36.75 W
Rated operational current for specified heat dissipation (In)
350 A
Direction of incoming supply
As required
Electrical connection type of main circuit
Other
Handle type
Rocker lever
Instantaneous current setting (Ii) - max
15 A
Instantaneous current setting (Ii) - min
2 A
Isolation
300 V AC (between the auxiliary contacts); 500 V AC (between auxiliary contacts and main contacts)
Lifespan, electrical
2000 operations at 415 V AC-3; 5000 operations at 415 V AC-1; 3000 operations at 690 V AC-1; 2000 operations at 400 V AC-3; 2000 operations at 690 V AC-3; 5000 operations at 400 V AC-1
Number of operations per hour - max
60
Overload current setting (Ir) - max
350 A
Overload current setting (Ir) - min
140 A
Overvoltage category
III
Pollution degree
3
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated insulation voltage (Ui)
690 V
Rated operating power at AC-3
230 V
110 kW
Rated operating power at AC-3
400 V
200 kW
Rated short-circuit making capacity Icm at 240 V
50/60 Hz
187 kA
Rated short-circuit making capacity Icm at 400/415 V
50/60 Hz
105 kA
Rated short-circuit making capacity Icm at 440 V
50/60 Hz
74 kA
Rated short-circuit making capacity Icm at 525 V
50/60 Hz
53 kA
Rated short-circuit making capacity Icm at 690 V
50/60 Hz
40 kA
Rated short-time withstand current (t = 0.3 s)
3.3 kA
Rated short-time withstand current (t = 1 s)
3.3 kA
Short-circuit release non-delayed setting - max
5250 A
Short-circuit release non-delayed setting - min
700 A
Short-circuit total breaktime
< 10 ms
Utilization category
A (IEC/EN 60947-2)
Voltage rating
690 V - 690 V
Climatic proofing
Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
Degree of protection
IP20 (basic degree of protection, in the operating controls area); IP20
Degree of protection (IP), front side
IP40 (with insulating surround); IP66 (with door coupling rotary handle)
Degree of protection (terminations)
IP00 (terminations, phase insulator and strip terminal); IP10 (tunnel terminal)
Lifespan, mechanical
15000 operations
Mounting Method
Built-in device slide-in technique (withdrawable); Withdrawable
Protection against direct contact
Finger and back-of-hand proof to VDE 0106 part 100
Shock resistance
20 g (half-sinusoidal shock 20 ms)
Switch off technique
Electronic
Optional terminals
Box terminal. Connection on rear. Tunnel terminal
Standard terminals
Screw terminal
Terminal capacity (aluminum solid conductor/cable)
16 mm² (1x) at tunnel terminal
Terminal capacity (aluminum stranded conductor/cable)
50 mm² - 240 mm² (2x) at 2-hole tunnel terminal; 50 mm² - 240 mm² (1x) at 2-hole tunnel terminal; 25 mm² - 185 mm² (1x) at tunnel terminal
Terminal capacity (control cable)
0.75 mm² - 1.5 mm² (2x); 0.75 mm² - 2.5 mm² (1x)
Terminal capacity (copper busbar)
Max. 10 mm x 50 mm (2x) at rear-side width extension; M10 at rear-side screw connection; Max. 30 mm x 10 mm + 30 mm x 5 mm direct at switch rear-side connection; Min. 20 mm x 5 mm direct at switch rear-side connection
Terminal capacity (copper solid conductor/cable)
300 mm² (2x) at rear-side width extension; 16 mm² (2x) at box terminal; 16 mm² (1x) at tunnel terminal; 16 mm² (1x) direct at switch rear-side connection; 16 mm² (2x) direct at switch rear-side connection
Terminal capacity (copper stranded conductor/cable)
35 mm² - 240 mm² (1x) at box terminal; 25 mm² - 240 mm² (2x) direct at switch rear-side connection; 25 mm² - 240 mm² (1x) direct at switch rear-side connection; 16 mm² - 185 mm² (1x) at 1-hole tunnel terminal; 25 mm² - 120 mm² (2x) at box terminal

Standards & Compliance

HS Code
8536.90

Cross References

  • EAN 4015081928866
  • SAP 1200600461
  • Code 82989071

Product Documentation

Document preview: Eaton Circuit breaker NZMN3-PMX350-AVE Supplied for general industrial and marine service under the applicable OEM specification — Specification Data Sheet (OEM)

Catalogue entry last verified: 2026-09-30. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.

Frequently asked questions

Where can I buy NZMN3-PMX350-AVE?
NZMN3-PMX350-AVE can be ordered from cballast.com as a Eaton catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
What is the manufacturer part number for this Eaton product?
The manufacturer part number is NZMN3-PMX350-AVE.
What is the HS code for NZMN3-PMX350-AVE?
The customs tariff (HS) code for NZMN3-PMX350-AVE is 8536.90.
Who manufactures NZMN3-PMX350-AVE?
NZMN3-PMX350-AVE is a Eaton product in the Electrical Components range.
Is a datasheet available for NZMN3-PMX350-AVE?
Yes — the NZMN3-PMX350-AVE datasheet can be viewed and downloaded on this page.
What is the minimum order quantity for NZMN3-PMX350-AVE?
The minimum order quantity is 1.
Is NZMN3-PMX350-AVE available?
Yes — NZMN3-PMX350-AVE is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).