Eaton
Contactor 2,2kW 230-240VAC (DILEM-01(230V50HZ,240V60HZ))
Part numberDILEM-01(230V50HZ,240V60HZ)EAN / GTIN4015080517955HS code8536.90
Electrical Components
Contactors
MOQ:1
Pricing
Request a quote
We reply within 24 hours
Product Description
Eaton DILEM-01(230V50HZ,240V60HZ) DILEM - Contactor 230-240 VAC including 1NC.
Technical Specifications
- Manufacturer part number (MPN)
- DILEM-01(230V50HZ,240V60HZ)
- EAN / GTIN
- 4015080517955
- HS code
- 8536.90
- Sales unit
- pcs
- Package quantity
- 5 pcs
- Eaton catalogue number
- 051795
- Depth
- 52 mm
- Height
- 58 mm
- Width
- 45 mm
- Weight
- 0.17 kg
- Certifications
- CE; UL 508; CSA-C22.2 No. 14-05; UL Category Control No.: NLDX; IEC/EN 60947-4-1; CSA Class No.: 3211-04; VDE 0660; UL File No.: E29096; UL; CSA File No.: 012528; IEC/EN 60947; CSA
- Catalog Notes
- Also tested according to AC-3e.
- Ambient operating temperature - max
- 50 °C
- Ambient storage temperature - max
- 80 °C
- Ambient operating temperature - min
- -25 °C
- Ambient operating temperature (enclosed) - max
- 40 °C
- Ambient operating temperature (enclosed) - min
- -25 °C
- Ambient storage temperature - min
- -40 °C
- Climatic proofing
- Damp heat, cyclic, to IEC 60068-2-30; Damp heat, constant, to IEC 60068-2-78
- Control circuit reliability
- < 2 λ, < 1 failure at 100,000,000 Operations (at Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
- Number of auxiliary contacts (normally closed contacts)
- 1
- Number of auxiliary contacts (normally open contacts)
- 0
- Conventional thermal current Ith (1-pole, enclosed)
- 40 A
- Conventional thermal current Ith (3-pole, enclosed)
- 16 A
- Conventional thermal current Ith at 55°C (3-pole, open)
- 19 A
- Conventional thermal current Ith of auxiliary contacts (1-pole, open)
- 10 A
- Conventional thermal current Ith of main contacts (1-pole, open)
- 50 A
- Equipment heat dissipation, current-dependent Pvid
- 1.2 W
- Heat dissipation capacity Pdiss
- 0 W
- Heat dissipation per pole, current-dependent Pvid
- 0.4 W
- Rated operational current for specified heat dissipation (In)
- 9 A
- Static heat dissipation, non-current-dependent Pvs
- 1.8 W
- Rated breaking capacity at 220/230 V
- 90 A
- Rated breaking capacity at 380/400 V
- 90 A
- Rated breaking capacity at 500 V
- 64 A
- Rated breaking capacity at 660/690 V
- 42 A
- Rated insulation voltage (Ui)
- 690 V
- Rated making capacity up to 440 V (cos phi to IEC/EN 60947)
- 110 A
- Rated operational current (Ie)
- 2.5 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series); 2.5 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series); 0.5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series); 1.5 A at 100 V, DC L/R ≤ 15 ms (with 3 contacts in series)
- Rated operational current (Ie) at AC-1, 380 V, 400 V
- 415 V
- 22 A
- Rated operational current (Ie) at AC-15, 220 V, 230 V
- 240 V
- 6 A
- Rated operational current (Ie) at AC-15, 380 V, 400 V
- 415 V
- 3 A
- Rated operational current (Ie) at AC-15
- 500 V
- 1.5 A
- Rated operational current (Ie) at AC-3, 220 V, 230 V
- 240 V
- 9 A
- Rated operational current (Ie) at AC-3, 380 V, 400 V
- 415 V
- 9 A
- Rated operational current (Ie) at AC-3
- 440 V
- 9 A
- Rated operational current (Ie) at AC-3
- 500 V
- 6.4 A
- Rated operational current (Ie) at AC-3, 660 V
- 690 V
- 4.8 A
- Rated operational current (Ie) at AC-4, 220 V, 230 V
- 240 V
- 6.6 A
- Rated operational current (Ie) at AC-4
- 440 V
- 6.6 A
- Rated operational current (Ie) at AC-4
- 500 V
- 5 A
- Rated operational current (Ie) at AC-4, 660 V
- 690 V
- 3.4 A
- Rated operational current (Ie) at DC-1
- 110 V
- 20 A
- Rated operational current (Ie) at DC-1
- 12 V
- 20 A
- Rated operational current (Ie) at DC-1
- 220 V
- 20 A
- Rated operational current (Ie) at DC-1
- 24 V
- 20 A
- Rated operational current (Ie) at DC-1
- 60 V
- 20 A
- Rated operational power at AC-3, 240 V
- 50 Hz
- 2.5 kW
- Rated operational power at AC-3, 380/400 V
- 50 Hz
- 4 kW
- Rated operational power at AC-3, 415 V
- 50 Hz
- 4.3 kW
- Rated operational power at AC-4, 220/230 V
- 50 Hz
- 1.5 kW
- Rated operational power at AC-4, 240 V
- 50 Hz
- 1.8 kW
- Rated operational power at AC-4, 415 V
- 50 Hz
- 3.1 kW
- Rated operational power at AC-4, 440 V
- 50 Hz
- 3.3 kW
- Rated operational power at AC-4, 500 V
- 50 Hz
- 3 kW
- Rated operational power at AC-4, 660/690 V
- Rated operational voltage (Ue) at AC - max
- 690 V
- Safe isolation
- 300 V AC, Between coil and auxiliary contacts, According to EN 61140; 300 V AC, Between the contacts, According to EN 61140; 300 V AC, Between auxiliary contacts, According to EN 61140; 300 V AC, Between coil and contacts, According to EN 61140
- Features
- Positive operating contacts to EN 60947-5-1 appendix L, including auxiliary contact module
- Fitted with
- Auxiliary contact
- Number of poles
- Three-pole
- Application
- Mini Contactors for Motors and Resistive Loads
- Degree of protection
- IP20
- Lifespan, mechanical
- 150,000 Operations (at 240 V, DC
- L/R = 50 ms
- 2 contacts in series 0.5 A); 10,000,000 Operations; 7,000,000 Operations (Coil 50/60 Hz); 200,000 Operations (at 240 V, AC-15)
- Mounting position
- As required (except vertical with terminals A1/A2 at the bottom)
- Operating frequency
- 9000 mechanical Operations/h
- Overvoltage category
- III
- Pollution degree
- 3
- Product category
- Contactors
- Protection
- Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
- Rated impulse withstand voltage (Uimp)
- 6000 V AC
- Suitable for
- Also motors with efficiency class IE3
- Utilization category
- AC-1: Non-inductive or slightly inductive loads, resistance furnaces; AC-3: Normal AC induction motors: starting, switch off during running; AC-4: Normal AC induction motors: starting, plugging, reversing, inching
- Voltage type
- AC
- Arcing time
- 12 ms at 690 V AC
- Changeover time
- 16 - 21 ms
- Duty factor
- 100 %
- Pick-up voltage
- 1.1 V AC x Uc (voltage tolerance - dual frequency coil 50/60 Hz); 0.8 - 1.1 V AC x Uc (voltage tolerance - single-voltage coil 50 Hz and dual-voltage coil 50 Hz, 60 Hz)
- Power consumption, pick-up
- 50 Hz
- 25 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz; 22 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
- Power consumption, pick-up
- 60 Hz
- 22 W, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz; 25 VA, AC, Single-frequency coil 50 Hz and Dual-frequency coil 50/60 Hz
- Power consumption, sealing
Standards & Compliance
- HS Code
- 8536.90
Cross References
- EAN 4015080517955
- SAP 1000009094
- Code 868709
Product Documentation
Document preview: CONTACTOR 2,2KW 230-240VAC (DILEM-01(230V50HZ,240V60HZ)) — Specification Data Sheet (OEM)
More from Eaton

Eaton
Contactor DILMP32-10(RDC24)

Eaton
NH-02 500V gG/gL 250A
250NHG02B

Eaton
Eaton NZMH2-PX100-BT Molded-Case Circuit Breaker 3-Pole 100A 150KA

Eaton
Motor Protectionbr IKMAX50KA (PKZM0-12)

Eaton
Eaton NZMN3-AE400 Molded-Case Circuit Breaker 3-Pole 400A 50KA

Eaton
WALL-Mount Cabinet H300 B400 D200
CS-34/200

Eaton
Auxiliary contact DILM150-XHIA22

Eaton
Cablefestejern xE Main B800
XAR08
Technical guides
Catalogue entry last verified: 2026-09-30. A manufacturer datasheet is attached to this entry — confirm application-critical values against it.
Frequently asked questions
- Where can I buy DILEM-01(230V50HZ,240V60HZ)?
- DILEM-01(230V50HZ,240V60HZ) can be ordered from cballast.com as a Eaton catalogue item: request a quotation on this page or email sales@cballast.com, and the order ships worldwide.
- What is the manufacturer part number for this Eaton product?
- The manufacturer part number is DILEM-01(230V50HZ,240V60HZ).
- What is the HS code for DILEM-01(230V50HZ,240V60HZ)?
- The customs tariff (HS) code for DILEM-01(230V50HZ,240V60HZ) is 8536.90.
- Who manufactures DILEM-01(230V50HZ,240V60HZ)?
- DILEM-01(230V50HZ,240V60HZ) is a Eaton product in the Electrical Components range.
- Is a datasheet available for DILEM-01(230V50HZ,240V60HZ)?
- Yes — the DILEM-01(230V50HZ,240V60HZ) datasheet can be viewed and downloaded on this page.
- What is the minimum order quantity for DILEM-01(230V50HZ,240V60HZ)?
- The minimum order quantity is 1.
- Is DILEM-01(230V50HZ,240V60HZ) available?
- Yes — DILEM-01(230V50HZ,240V60HZ) is available to order: fulfilment is from supplier stock in cBallast's European network, dispatched directly from the warehouse to the customer, with the exact lead time stated in the quotation (reply within 24 hours).