Choosing fixed gas detectors by sensing principle — catalytic, infrared, electrochemical, ultrasonic leak detection — with the honest failure modes of each, mounting height by gas density, alarm setpoint conventions in %LEL and ppm, calibration against bump testing and cell life, the standards that govern performance and installation (IEC 60079-29-1/-2, EN 45544, EN 378 for refrigerants), and the Drager Polytron, Honeywell Sensepoint XCD and MSA Ultima ranges held against the selection table.
| Principle | Measures | Strengths | Honest weaknesses | Typical life |
|---|---|---|---|---|
| Catalytic bead | Flammables, %LEL | Cheap, proven, responds to almost any combustible | Needs >10% O2; poisoned by silicones/H2S/lead; fails to zero undetected; needs regular gas testing | 3–5 yr beads |
| Infrared (point) | Hydrocarbons, CO2, %LEL or %vol | Fail-safe optics, no poisoning, works in inert atmospheres, long intervals | Blind to hydrogen; mist/ice on optics; higher purchase price | 5–10 yr+ |
| Electrochemical | Toxics (CO, H2S, Cl2, NH3...), O2 | ppm sensitivity, selective by cell chemistry, low power | Cell is a consumable (2–3 yr); cross-sensitivities; temperature and humidity limits | 2–3 yr cells |
| Ultrasonic leak | Sound of pressurised gas escape | Instant, concentration-independent, outdoor-proof (wind cannot dilute sound) | Detects leaks, not concentration; acoustic background must be mapped | 10 yr class |
| Open-path IR | Line-of-sight hydrocarbon cloud, LEL·m | Covers fence lines and long bays with one pair | Fog/rain attenuation; alignment; reads integrated cloud, not point ppm | 5–10 yr |
Catalogue anchors across the principles: Drager Polytron 8100 EC (electrochemical, here O2, Ex d IIC), Polytron 8200 IR for CO2 in Zone 1, Polytron 5100 EC for H2S, Honeywell Sensepoint XCD catalytic CH4 and Sensepoint XCD IR hydrocarbon, MSA Ultima X5000 dual-gas, Drager Polytron 8900 UGLD ultrasonic and MSA Ultima XIR open-path (120 m).
| Gas | Relative density vs air | Sensor | Mounting |
|---|---|---|---|
| Methane / natural gas | Lighter (0.55) | Catalytic or IR, %LEL | High — ceiling or above leak sources |
| Propane / LPG / butane | Heavier (1.5–2) | Catalytic or IR, %LEL | Low — 300–600 mm above floor, pits and trenches |
| Hydrogen | Much lighter (0.07) | Catalytic or EC — not standard IR | Highest point, roof peaks, battery rooms |
| CO | Near air (0.97) | Electrochemical, ppm | Breathing height ≈ 1.5 m |
| H2S | Heavier (1.19) | Electrochemical, ppm | Low, near sources; sewage and mud systems |
| Ammonia (R717) | Lighter (0.59) | Electrochemical, ppm | High in machine rooms; EN 378 thresholds |
| CO2 (inert-gas, breweries, HVAC) | Heavier (1.53) | Infrared, %vol or ppm | Low; confined spaces and cellars |
| HFC/HFO refrigerants | Heavier | IR (selective) or semiconductor (cheap, cross-sensitive) | Low in machine rooms; EN 378 charge-based thresholds |
| Oxygen (deficiency/enrichment) | — | Electrochemical, %vol (alarm ≤ 19.5% / ≥ 23.5% common) | Breathing height in the protected space |
Siting beats specification: a perfect detector in the wrong corner protects the corner. The 60079-29-2 method is to map leak sources, gas density, ventilation paths and air movement, then place sensors where gas will actually pass — intake ducts, above flanges for light gases, in pits for heavy ones — and keep every sensor reachable for the technician with a bottle and a cup. Refrigerant machine-room practice (sensor per refrigerant, alarm tie-in to ventilation) follows EN 378 and is covered with the refrigerant side in our refrigerant leak detection guide.
Fixed transmitters output 4–20 mA (with HART on the current generations), relays, and increasingly Modbus or Foundation Fieldbus; controllers or the vessel's/plant's safety system evaluate setpoints. Conventions that keep surveyors content: flammables at 20% LEL warning and 40% LEL action (shutdown/ESD where the safety case says so); toxic alarms at the national exposure limits (for H2S commonly 5/10 ppm two-stage); oxygen at 19.5%/23.5%; latching executive actions with manual reset. Fault (≤ 3 mA) must be wired as a distinct state, never as "no alarm" — a dead detector reading as healthy is the industry's recurring accident report. Display and interface modules are maintainable spares on most families (the Sensepoint XCD display module is a stocked example); portable multigas units — the MSA Altair 4XR (LEL/O2/H2S/CO) class — complement the fixed system for entries and maintenance, they do not replace it.
| Activity | What it proves | Typical interval |
|---|---|---|
| Bump (function) test | Gas path open, cell responds, alarms operate | Monthly to quarterly fixed; before each use portable |
| Full calibration | Accuracy re-established against certified span gas | 3–6 months catalytic/EC; 6–12 months IR (maker's table governs) |
| Cell / bead replacement | End of chemical life | EC cells 2–3 yr; O2 cells often 1–2 yr; catalytic beads on failure to calibrate |
Calibration gas is a dated consumable with its own certificate — order it with a lead time against the ship's or plant's schedule, in the regulator-and-cup kit the detector maker specifies. The economics favour planning: a cell changed at calibration visit costs the cell; the same cell failed at survey costs a re-visit, a deviation and sometimes a detained schedule. Our team quotes detectors, spare cells, sensing heads, calibration kits and span gas as one standing list per vessel or site — the same certificate-bound consumable logic as UV lamps.
The transmitter must carry the Ex certification for its zone and gas group (typically Ex d flameproof heads, IIC T4/T6; see the ATEX/IECEx marking guide), the measurement function its 60079-29-1 (flammable) or EN 45544 (toxic) performance certificate, and shipboard installations the class society type approval — all three are different documents, and the requisition should name each. SIL-rated loops (common for ESD on gas carriers and platforms) additionally need the SIL capability declaration under IEC 61508. IS-powered detection heads run behind barriers — entity rules in our IS barrier guide.
A quotable line carries: target gas and range (CH4 0–100% LEL; H2S 0–50 ppm; CO2 0–5% vol; O2 0–25% vol), sensing principle if constrained (IR for inert atmospheres), zone and Ex marking, performance certificate (60079-29-1 / EN 45544), output (4–20 mA HART, relays, Modbus), ambient (temperature, IP, marine), mounting accessories (duct kits, collecting cones, sunshades, remote heads), class society where shipboard, and the commissioning span-gas kit. For replacements, the installed head's part number and the controller it reports to — cross-maker replacement is routine (Polytron, Sensepoint, Ultima cover the same duties) but ranges, cell chemistry and output scaling must be matched line by line.
How buying works at cballast. We quote fixed and portable gas detection with the certificates attached (Ex, performance, class where required), spare cells and calibration gas against the maintenance calendar, and successors for obsolete heads declared next to like-for-like. Accounts are vetted at onboarding; first order prepaid; established accounts on credit terms with repeat discounts; public bodies and utilities invoiced against purchase order from the first order. RFQs to sales@cballast.com.
Standards referenced: IEC/EN 60079-29-1 (performance, flammable); IEC/EN 60079-29-2 (selection, installation, use, maintenance); EN 45544 (toxic gas detection); EN 50104 (oxygen); EN 378 (refrigeration machine rooms); IEC 61508 (SIL); IEC 60079 series (Ex); class society rules for gas detection on tankers and gas carriers; Drager, Honeywell and MSA technical manuals.