Timer Relay Functions — On-Delay, Off-Delay, Single-Shot, Flasher and Star-Delta Explained

Standards explainer compiled by cBallast. 3-page PDF; the full content is on this page.
Compiled by
cBallast
Subject
Timing relays
Document type
Standards explainer
Reference
2026 edition
Issued
2026-10-06
Pages
3
Format
Web page and PDF

What each timing function actually does to the output contact, how multifunction units like Zelio RE22 and SIRIUS 3RP25 replace a drawer of single-function spares, the true-off-delay trap (timing without auxiliary supply), and the dedicated star-delta timer's transfer gap — with stocked examples.

Five functions cover almost every panel

FunctionBehaviourClassic use
On-delay (A)Supply on → output waits the set time, then closesStaggered starts, alarm suppression during start-up
Off-delayTrigger removed → output holds for the set time, then opensFan run-on, lubrication after-run
Single-shot / intervalOne fixed-length pulse per triggerEjectors, stamping, horn pulses
Flasher (symmetric)Output cycles on/off at the set periodBeacon and indicator flashing
Star-deltaStar time, then a fixed ~50 ms dead gap, then deltaReduced-inrush motor starting

The star-delta version is its own species: the dead gap between the star contactor dropping and the delta contactor pulling in is built into the device — the Zelio Time RE7TP11BU carries both timed outputs in one 22.5 mm housing. Get the gap wrong with two generic timers and the supply sees a phase-to-phase short through the motor windings; the contactor trio itself is sized in the contactor guide.

Multifunction units ended the spares drawer

A modern multifunction timer selects its function and range by dials: a Zelio RE22R2AMR (2 C/O) or RE22R1AMR covers ten-plus functions across 24–240 V AC/DC supply — one spare on the shelf stands in for nearly any failed single-function unit. Siemens' equivalent is the SIRIUS 3RP25 family (3RP2505-1AB30, 3RP2505-2AW30), and wide-supply multifunction units exist across brands (a 24 V DC / 24–240 V AC 2 C/O example). Two checks before substituting:

Close to 1,900 timing-relay line items are in the catalogue — about a hundred Zelio Time units alone, plus the SIRIUS 3RP range and panel-builder staples. The plug-in relays these timers often drive, and their bases, are covered in the relay and socket pairing chart; quote the failed unit's full reference and function letter and a current equivalent is confirmed within 24 hours.

Frequently asked questions

What is the difference between on-delay and off-delay timing?
On-delay waits after power arrives before closing the output; off-delay closes immediately and holds the output for the set time after the trigger or supply disappears — fan run-on being the textbook case.
Why does a star-delta starter need its own timer type?
Because the changeover needs a guaranteed dead gap (around 50 ms) between star dropping out and delta pulling in — a dedicated star-delta timer provides both outputs with that interlock built in.
Can one multifunction timer replace any old timing relay?
Nearly — if the supply voltage band covers the panel's control voltage, the function list includes the old unit's letter, and the off-delay variant matches the wiring (true off-delay versus triggered off-delay are wired differently).
What does 2 C/O mean on a timer relay?
Two changeover output contacts — each with common, NO and NC — switching together; it is the contact count, the same convention plug-in relays use.
How long should the star time be set?
Long enough for the motor to approach rated speed in star — typically a few seconds, set by watching the current fall — because switching to delta while current is still high defeats the purpose of the reduced-inrush start.
Open / Download PDF

Compiled by cBallast for identification and cross-reference. Part numbers, designations and trademarks belong to their respective manufacturers. Confirm ratings and dimensions against the manufacturer's current documentation and the nameplate of the installed equipment before ordering or installation.