Danfoss MBS Pressure Transmitters — 3000 vs 5100, Ranges and the 4–20 mA Loop

Selection guide compiled by cBallast. 3-page PDF; the full content is on this page.
Brand
Danfoss
Subject
Pressure transmitters
Document type
Selection guide
Reference
2026 edition
Issued
2026-10-18
Pages
3
Format
Web page and PDF

Reading an MBS reference (range, process connection, plug, output), what separates the MBS 3000 workhorse from the marine-approved MBS 5100, why 4–20 mA survives every fieldbus fashion, and the installation details — pulsation snubbers, cable glands, loop checks — that keep transmitters honest for decades.

The reference carries the whole datasheet

An MBS line item reads like the stocked rows: MBS 3000, R1/4″, 4–20 mA, plug connection — family, process thread, output, electrical connection, plus the measuring range (selected per variant: the 1/2″ 0–125 bar IP65 build is one of many). Two families dominate the stocked 300-plus rows:

MBS 3000MBS 5100
PositionThe general-industry workhorse — compact, piezoresistive, all-stainless wetted partsThe classification-approved build for marine and harsh plant, with pulse-snubber variants
Stocked examplesR1/4″ and R1/2″ plug versions1/4″ 0–6 bar, 1/4″ 0–100 bar
Pick whenPumps, compressors, hydraulics, general monitoringClass-surveyed installations and engine-adjacent duty

Why 4–20 mA refuses to die

Installation notes that outlast commissioning

Quote the old unit's type code and range off the label — or the duty (medium, range, connection, output, approvals) — and the current MBS equivalent returns within 24 hours from Danfoss stock.

Frequently asked questions

What does 4–20 mA output actually mean?
The transmitter regulates loop current between 4 mA at range-zero and 20 mA at full scale — current, not voltage, so cable length barely matters, and anything below 4 mA flags a fault rather than masquerading as a low reading.
Which pressure range should I choose for a 7 bar system?
A 0–10 or 0–16 bar span, putting 7 bar comfortably mid-range — not a 0–100 bar unit where the whole system lives in the bottom tenth of the span and the percent-of-span error dwarfs the signal.
What is the difference between MBS 3000 and MBS 5100?
Build target: the 3000 is the compact industrial standard; the 5100 adds the marine classification approvals and harsh-duty details (snubbed variants for pulsation). Where surveys apply, the approval list decides.
Can a pressure transmitter replace my pressure switch?
For monitoring and soft alarms, yes and better; for hard-wired safety trips, a switch's dry contact often remains required by the approval chain. The common pattern is a transmitter for control plus a switch for the safety function.
Why does my transmitter drift after months on a piston pump line?
Pulsation fatigue — millions of pressure spikes work the diaphragm. Fit the snubbed variant or a restrictor fitting, and the same sensor lasts years; no amount of recalibration fixes the mechanical cause.
Open / Download PDF

Compiled by cBallast for identification and cross-reference. Part numbers, designations and trademarks belong to their respective manufacturers. Confirm ratings and dimensions against the manufacturer's current documentation and the nameplate of the installed equipment before ordering or installation.