AWG to mm² Conversion Chart — Wire Sizes, Cross Sections and Current Ratings

Dimensional reference compiled by cBallast. 3-page PDF; the full content is on this page.
Compiled by
cBallast
Subject
Cables and conductors
Document type
Dimensional reference
Reference
2026 edition
Issued
2026-10-04
Pages
3
Format
Web page and PDF

Conversion table from American Wire Gauge (AWG 24 to 4/0) and kcmil to metric mm² cross sections, with conductor diameters and indicative copper current ratings, plus the standard IEC cable sizes and how to substitute between the systems.

Conversion table

AWGØ (mm)mm² (exact)Nearest IEC sizeCu rating* (A)
240.5110.2050.252
220.6440.3260.343
200.8120.5180.55
181.0240.8230.757
161.2911.311.510
141.6282.082.515
122.0533.31420
102.5885.26630
83.2648.371040
64.11513.31655
45.18921.12570
26.54433.63595
17.34842.450110
1/08.25153.550125
2/09.26667.470145
3/010.4085.095165
4/011.68107120195
250 kcmil12.70127120215
350 kcmil15.03177185260
500 kcmil17.96253240320

*Indicative 75 °C copper ratings for a single circuit in free air/conduit per NEC-style tables — the installation standard (NEC, IEC 60364-5-52) and derating factors govern any real circuit.

Substituting between systems

AWG steps are geometric: three gauge numbers double the cross section, six double the diameter. When replacing an AWG conductor with metric cable, round up to the next IEC size (10 AWG = 5.26 mm² → 6 mm²) so ampacity and voltage drop are never worse. Terminal and lug sizes follow the metric cross section — e.g. 35 mm² cable lugs crimp 2 AWG conductors. Fixed-installation cables by cross section are listed under Cables & Wiring, and box-terminal ranges for breakers state both systems, as on the Siemens 3VA box terminal (25–185 mm² / 4 AWG–350 kcmil).

Stranding note

An AWG number names the cross section regardless of stranding: 10 AWG solid and 10 AWG 19-strand have the same 5.26 mm². Class 5/6 flexible metric conductors need ferrules or the correct clamp-type terminals — solid-conductor torque values do not transfer to fine-strand wire.

Frequently asked questions

What is 10 AWG in mm²?
10 AWG is 5.26 mm²; the standard metric substitute is 6 mm².
What is 4/0 AWG in mm²?
4/0 AWG (0000) is 107 mm²; the usual metric equivalent is 120 mm².
Is 2.5 mm² the same as 14 AWG?
Close: 14 AWG is 2.08 mm², so 2.5 mm² is the correct metric replacement (never substitute downwards to 1.5 mm²).
How much current can 6 AWG carry?
About 55 A at 75 °C in a typical single-circuit installation; the applicable installation code and derating factors decide the real limit.
How do AWG sizes scale?
Geometrically: minus three gauge numbers doubles the copper area, minus six doubles the diameter; sizes above 4/0 switch to kcmil (thousand circular mils).
Open / Download PDF

Reference compiled for identification and cross-reference. Dimensions are nominal; confirm against the controlling Multiple 2026 edition revision and the specific component data sheets before manufacture or procurement. All trademarks are the property of their respective owners.