Suction Accumulators and Liquid Receivers — What They Do and How to Size Them

Application guide compiled by cBallast. 3-page PDF; the full content is on this page.
Compiled by
cBallast
Subject
Refrigerant vessels
Document type
Application guide
Reference
2026 edition
Issued
2026-10-03
Pages
3
Format
Web page and PDF

Why a suction-line accumulator protects the compressor on heat-pump, low-temperature and hot-gas-defrost plants, how receiver volume relates to system charge and pump-down, and the catalogue's vessel sizes from 1.5 to 22 litres (accumulators) and 10 to 50 litres (vertical receivers).

The accumulator's job

A suction-line accumulator is a vertical trap ahead of the compressor: refrigerant vapour enters at the top, any entrained liquid falls out, and the outlet dip tube draws vapour plus a controlled trickle of oil and liquid through a metering orifice back to the compressor. It exists because some systems periodically send liquid down the suction line by design — reversing heat pumps at the moment of cycle reversal, hot-gas defrost plants at defrost termination, low-temperature cabinets with floodback at pull-down, and any plant whose evaporator superheat control is marginal. The accumulator converts a slug that would break valve reeds into a few minutes of harmless boil-off.

Sizing an accumulator

Two numbers matter: holding volume — the industry rule is at least 50 % of the total system charge should fit in the vessel (because at the worst moment, most of the charge can arrive at once); and connection size — matched to the suction line so vapour velocity neither drops oil nor adds pressure loss. The catalogue sizes map to small and medium plants:

ConnectionVolumeListing
1/2"1.5 LBORSL1000215A
5/8"1.5 LSL2C16102210
3/4"3 LSL1C18130250
7/8"4.5 LBORSL1540265A
1 1/8"5 LSL2C28154270
2 1/8"22 LSL1C54285420

Install vertically, as close to the compressor as practical, insulated on low-temperature duty so the trapped liquid actually boils off from suction gas heat rather than ambient.

The receiver's job

A liquid receiver after the condenser stores the charge difference between operating modes: it feeds a solid liquid column to the expansion device while condenser inventory swings with load and ambient, and it must swallow the whole charge during pump-down for service. Size so that the full operating charge occupies at most ~80–90 % of receiver volume at 40 °C liquid (thermal expansion headroom — the EN 378 / PED documentation for the vessel states the limit that governs). The catalogue's vertical receivers: 10 L, 14 L, 18 L, 40 L and 50 L.

Protection and fittings

Receivers above the EN 378 thresholds carry a pressure-relief valve; the Henry relief range and the twin SDK changeover assemblies that allow valve replacement without pump-down are covered in the relief valve guide. Rotalock connections dominate on both vessel types: match adapters and service valves from the rotalock reference, and renew PTFE gaskets on every disturbance. A liquid-line sight glass downstream (SGP 6S) confirms a sealed liquid feed.

Symptoms worth knowing

Open / Download PDF

Compiled by cBallast for identification and cross-reference. Part numbers, designations and trademarks belong to their respective manufacturers. Confirm ratings and dimensions against the manufacturer's current documentation and the nameplate of the installed equipment before ordering or installation.