PN10 Flange Dimensions (EN 1092-1 Type 11, DN10 to DN350)

Dimensional reference compiled by cBallast. 1-page PDF; the full content is on this page.
Compiled by
cBallast
Subject
Type 11 raised-face weld-neck flange
Document type
Dimensional reference
Reference
EN 1092-1
Issued
2026-06-19
Pages
1
Format
Web page and PDF

PN10 flange dimensions to EN 1092-1: flange outside diameter D, bolt-circle diameter K, bolt-hole size, number of bolts, bolt size and flange thickness C for Type 11 weld-neck flanges from DN10 through DN350. Includes DN50 (165 mm OD, 4 x M16), DN100 (180 mm bolt circle, 8 x M16) and DN150 (8 x M20). The common low-pressure (10 bar) rating; dimensionally identical to PN16 up to DN150. Values cross-checked across two independent reference tables.

PN10 flange dimensions (EN 1092-1 Type 11, DN10 to DN350)

PN10 is the EN 1092-1 pressure rating for a nominal 10 bar flange and the common rating for low-pressure water, HVAC, pump and general process service. The PN number fixes the bolt pattern, so a PN10 DN100 flange from any maker shares the same 220 mm outside diameter, 180 mm bolt circle and eight M16 bolts. The values below are the EN 1092-1 nominal dimensions for the Type 11 raised-face weld-neck flange across the common DN10 to DN350 range, cross-checked across two independent reference tables.

DNFlange OD D (mm)Bolt circle K (mm)Bolt hole (mm)No. of boltsBolt sizeFlange thick C (mm)
DN109060144M1216
DN159565144M1216
DN2010575144M1218
DN2511585144M1218
DN32140100184M1618
DN40150110184M1618
DN50165125184M1618
DN65185145188M1618
DN80200160188M1620
DN100220180188M1620
DN125250210188M1622
DN150285240228M2022
DN200340295228M2024
DN2503953502212M2026
DN3004454002212M2026
DN3505054602216M2026

Bolt holes are drilled on the bolt circle K, straddling the centreline and equally spaced. The bolt size is the largest that passes the listed hole: 14 mm holes take M12, 18 mm M16 and 22 mm M20. PN10 keeps the same M16 bolt from DN32 to DN125, stepping up to M20 from DN150 to DN350.

Reading the dimensions

Selecting and matching

Two flanges bolt together only when the pressure rating, DN, bolt circle K and bolt pattern all agree, so confirm all four before ordering. A PN10 flange will not mate to a PN25 or an ASME Class flange of the same DN even though the bore is the same — the bolt circle and hole count differ. PN10 and PN16 to EN 1092-1 are dimensionally identical from DN10 through DN150, so DN15 to DN150 flanges interchange freely between the two ratings; at DN200 they share the same outside diameter, bolt circle, hole and bolt size but PN10 uses eight bolts where PN16 uses twelve, and above DN200 the two ratings diverge in diameter as well. EN 1092-1 also defines the facing (Type B1 raised face is the common PN10 facing) and the flange material group, which set the gasket and bolt grade for the temperature and pressure. The dimensions above are for the Type 11 weld-neck flange; blind, plate and slip-on PN10 flanges to EN 1092-1 share the same D, K, bolt hole, bolt count and bolt size.

Dimensions are nominal EN 1092-1 values and provided for identification and cross-reference. Confirm against the controlling standard and the specific flange maker’s current data sheet before manufacture or procurement.

Frequently asked questions

What are the dimensions of a DN50 PN10 flange?
A DN50 PN10 flange to EN 1092-1 is 165 mm outside diameter with four 18 mm holes (M16 bolts) on a 125 mm bolt circle — identical drilling to DN50 PN16.
What are the dimensions of a DN100 PN10 flange?
DN100 PN10: 220 mm outside diameter, 180 mm bolt circle, eight M16 bolts — the same pattern as PN16 at this size.
Up to which size do PN10 and PN16 share dimensions?
Through DN150 the EN 1092-1 drilling is the same; from DN200 the two ratings use different bolt circles and bolt counts.
Is a PN10 flange strong enough for 10 bar?
PN10 denotes a 10 bar nominal rating at reference temperature; the allowable pressure falls with temperature per the material group tables in EN 1092-1, so check the pressure–temperature rating, not just the PN number.
Open / Download PDF

Reference compiled for identification and cross-reference. Dimensions are nominal; confirm against the controlling EN 1092-1 PN10 EN 1092-1 revision and the specific component data sheets before manufacture or procurement. All trademarks are the property of their respective owners.