| Manufacturer part number (MPN) | 750-626 |
| EAN / GTIN | 4045454393977 |
| Sales unit | pcs |
| Signal type | Voltage |
| Signal type (voltage) | 24 VDC |
| Supply voltage (system) | 24 VDC (-25 … +30 %); via wiring interface (CAGE CLAMP® connection); External fuse required: 2 A slow-blow |
| Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts (supply via CAGE CLAMP® connection; distribution via spring contact); External fuse required: 10 A slow-blow |
| Current via system voltage (max.) | 1.5 A (1 A up to hardware version 03) |
| Current carrying capacity (power jumper contacts) | 10 A |
| Number of outgoing power jumper contacts | 2 |
| Use | Marine-certified operation in conjunction with the Ex i supply module and the use of 750 Series PROFIsafe Modules |
| Indicators | LED (A |
| B) green | operating voltage status: system, power jumper contacts |
| Connectable conductor materials | Copper |
| Connection type | System/field supply |
| Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
| Connection technology | field supply: 4 x CAGE CLAMP® |
| Connection technology | system supply: 4 x CAGE CLAMP® |
| Width | 12 mm / 0.472 inches |
| Height | 100 mm / 3.937 inches |
| Depth | 69.8 mm / 2.748 inches |
| Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
| Mounting type | DIN-35 rail |
| Pluggable connector | fixed |
| Color | light gray |
| Housing material | Polycarbonate; polyamide 6.6 |
| Fire load | 1.261 MJ |
| Weight | 49.6 g |
| Conformity marking | CE |
| Ambient temperature (operation) | 0 … +55 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Protection type | IP20 |
| Pollution degree | 2 per IEC 61131-2 |
| Operating altitude | 0 … 2000 m / 0 … 6562 ft |
| Mounting position | Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom |
| Relative humidity (without condensation) | 95 % |
| Vibration resistance | 4g per IEC 60068-2-6 |
| Shock resistance | 15g per IEC 60068-2-27 |
| EMC immunity to interference | per EN 61000-6-2, marine applications |
| EMC emission of interference | per EN 61000-6-4, marine applications |
| Exposure to pollutants | per IEC 60068-2-42 and IEC 60068-2-43 |
| Permissible H2S contaminant concentration at a relative humidity 75 % | 10 ppm |
| Permissible SO2 contaminant concentration at a relative humidity 75 % | 25 ppm |
| Product Group | 15 (I/O System) |
| PU (SPU) | 1 pcs |
| Packaging type | Box |
| Country of origin | DE |
| Customs tariff number | 85389091890 |
| UNSPSC | 39,121,610 |
| eCl@ss 10.0 | 27-24-26-10 |
| eCl@ss 9.0 | 27-24-26-10 |
| ETIM 9.0 | EC001600 |
| ETIM 10.0 | EC001600 |
| ECCN | NO US CLASSIFICATION |
| CAS-No. | 1303-86-2 | 1317-36-8 | 7439-92-1 |
| REACH Candidate Strip Substance | Diboron trioxide | Lead | Lead monoxide |
| RoHS Compliance Status | Compliant,With Exemption |
| RoHS Exemption | 7(a) | 7(c)-I |
| SCIP notification number (Austria) | 67c0c0b1-7384-4b47-a2e5-4c27138899d5 |
| SCIP notification number (Belgium) | df0f77b2-d61d-4ad6-a3b3-f7711ef98d42 |
| SCIP notification number (Bulgaria) | 2d06e6ca-d722-4510-b42c-65e6403fa9d5 |
| SCIP notification number (Czech Republic) | a68e4cdd-5f5a-418b-8e5e-e803e77fca65 |
| SCIP notification number (Denmark) | 64efa0c4-e047-4e42-be2c-7ac2c5682a5f |
| SCIP notification number (Finland) | 1d58eed1-1e70-4a5c-b275-94ef51c4b0e6 |
| SCIP notification number (France) | 4e0a8b03-54ed-4246-ae5c-7b0f6059a324 |
| SCIP notification number (Germany) | 44af5fb9-ca85-4975-b391-63f66ebec7da |
| SCIP notification number (Hungary) | 96033c53-5b69-4a96-822d-d0cd90af0ac2 |
| SCIP notification number (Italy) | cf47825e-5dc0-4974-bde0-53ea3b2effe4 |
| SCIP notification number (Netherlands) | aae1ec69-6acb-4163-9a02-4744f8d8f656 |
| SCIP notification number (Poland) | 2e19eca4-0e0c-4291-a245-0b850a9e3ac2 |
| SCIP notification number (Romania) | 4edd15ad-8a94-49aa-bbc0-cf5351cee8b9 |
| SCIP notification number (Sweden) | caf61d73-0270-4183-8472-a7cf01e7c216 |
| Certified for UL hazardous location division 1 | Yes |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | Yes |
| Certified for UL hazardous location group B (hydrogen) | Yes |
| Certified for UL hazardous location group C (ethylene) | Yes |
| Certified for UL hazardous location group D (propane) | Yes |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | Yes |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 24 V |
| Voltage type (supply voltage) | DC |
| With optical interface | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| System accessory | Yes |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Spring clamp connection |
| With potential separation | No |
| With power supply module | No |
| Suitable as segment module | Yes |
| Remote module | No |
| Fieldbus connection over separate bus coupler possible | Yes |
| Bus diagnosis possible | No |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | No |
| Front built-in possible | No |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | ATEX dust-ex-protection, Cat. 3D |