cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

4-Channel analog input; for PT100/RTD resistance sensors (750-460)

WAGO · Sensors & Instrumentation · Temperature Sensors
Part Number
750-460  ·  HS 8538.90
4-Channel analog input; for PT100/RTD resistance sensors (750-460)

WAGO 750-460 Manufacturer description: 4-channel analog input; For Pt100/RTD resistance sensors. 4-channel analog input;For Pt100/RTD motstandssensorer;light grey.

Technical Specifications

Manufacturer part number (MPN)750-460
EAN / GTIN4045454848927
Sales unitpcs
Number of analog inputs4
Total number of channels (module)4
Signal typeResistance measurement
Sensor connection4 x (2-wire)
Data width4 x 16-bit data; 4 x 8-bit control/status (optional)
Resolution (over entire range)0.1 °C
Conversion time (typ.)250 ms
Measurement error (reference temperature)25 °C
Measurement error, deviation (max.) from the upper-range value0.2 %
Temperature error (max.) of the upper-range value0.01 %/K
Measuring current (typ.)0.5 mA
Sensor typesPt100
Temperature range−200 … +850 °C
Supply voltage (system)5 VDC; via data contacts
Current consumption (system supply)65 mA
Isolation500 V system/field
IndicatorsLED (A-D) red: Error AI 1 … AI 4
Connection technologyI/O: 8 x CAGE CLAMP®
Connectable conductor materialsCopper
Connection typeInputs/Outputs
Solid conductor0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip length8 … 9 mm / 0.31 … 0.35 inches
Width12 mm / 0.472 inches
Height100 mm / 3.937 inches
Depth69.8 mm / 2.748 inches
Depth from upper-edge of DIN-rail62.6 mm / 2.465 inches
Mounting typeDIN-35 rail
Pluggable connectorfixed
Colorlight gray
Housing materialPolycarbonate; polyamide 6.6
Fire load0.085 MJ
Weight51.8 g
Conformity markingCE
Ambient temperature (operation)0 … +55 °C
Ambient temperature (storage)-40 … +85 °C
Protection typeIP20
Pollution degree2 per IEC 61131-2
Operating altitude0 … 2000 m / 0 … 6562 ft
Mounting positionHorizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)95 %
Vibration resistancePer IEC 60068-2-6
Shock resistance15g per IEC 60068-2-27
EMC immunity to interferenceper EN 61000-6-2
EMC emission of interferenceper EN 61000-6-4
Exposure to pollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %25 ppm
Product Group15 (I/O System)
PU (SPU)1 pcs
Packaging typebox
Country of originDE
Customs tariff number85437090990
UNSPSC32,151,706
eCl@ss 10.027-24-26-01
eCl@ss 9.027-24-26-01
ETIM 9.0EC001596
ETIM 10.0EC001596
ECCNNO US CLASSIFICATION
RoHS Compliance StatusCompliant,No Exemption
Power consumption1 W
Certified for UL hazardous location division 1Yes
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)Yes
Certified for UL hazardous location group B (hydrogen)Yes
Certified for UL hazardous location group C (ethylene)Yes
Certified for UL hazardous location group D (propane)Yes
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class IYes
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Supply voltage DC5 V
Voltage type (supply voltage)DC
Input, currentNo
Input, voltageNo
Input, resistorYes
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableNo
Resolution of the analogue inputs12 Bit
Output, currentNo
Output, voltageNo
Output signal configurableNo
Number of analogue inputs4
Analogue inputs configurableNo
Analogue outputs configurableNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsNo
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
Degree of protection (IP)IP20
Type of electric connectionSpring clamp connection
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleNo
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustATEX dust-ex-protection, Cat. 3D

Properties

MOQ1

Cross-References