| Manufacturer part number (MPN) | 750-460 |
| EAN / GTIN | 4045454848927 |
| Sales unit | pcs |
| Number of analog inputs | 4 |
| Total number of channels (module) | 4 |
| Signal type | Resistance measurement |
| Sensor connection | 4 x (2-wire) |
| Data width | 4 x 16-bit data; 4 x 8-bit control/status (optional) |
| Resolution (over entire range) | 0.1 °C |
| Conversion time (typ.) | 250 ms |
| Measurement error (reference temperature) | 25 °C |
| Measurement error, deviation (max.) from the upper-range value | 0.2 % |
| Temperature error (max.) of the upper-range value | 0.01 %/K |
| Measuring current (typ.) | 0.5 mA |
| Sensor types | Pt100 |
| Temperature range | −200 … +850 °C |
| Supply voltage (system) | 5 VDC; via data contacts |
| Current consumption (system supply) | 65 mA |
| Isolation | 500 V system/field |
| Indicators | LED (A-D) red: Error AI 1 … AI 4 |
| Connection technology | I/O: 8 x CAGE CLAMP® |
| Connectable conductor materials | Copper |
| Connection type | Inputs/Outputs |
| Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
| Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
| Width | 12 mm / 0.472 inches |
| Height | 100 mm / 3.937 inches |
| Depth | 69.8 mm / 2.748 inches |
| Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
| Mounting type | DIN-35 rail |
| Pluggable connector | fixed |
| Color | light gray |
| Housing material | Polycarbonate; polyamide 6.6 |
| Fire load | 0.085 MJ |
| Weight | 51.8 g |
| Conformity marking | CE |
| Ambient temperature (operation) | 0 … +55 °C |
| Ambient temperature (storage) | -40 … +85 °C |
| Protection type | IP20 |
| Pollution degree | 2 per IEC 61131-2 |
| Operating altitude | 0 … 2000 m / 0 … 6562 ft |
| Mounting position | Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom |
| Relative humidity (without condensation) | 95 % |
| Vibration resistance | Per IEC 60068-2-6 |
| Shock resistance | 15g per IEC 60068-2-27 |
| EMC immunity to interference | per EN 61000-6-2 |
| EMC emission of interference | per EN 61000-6-4 |
| Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
| Permissible H2S contaminant concentration at a relative humidity 75 % | 10 ppm |
| Permissible SO2 contaminant concentration at a relative humidity 75 % | 25 ppm |
| Product Group | 15 (I/O System) |
| PU (SPU) | 1 pcs |
| Packaging type | box |
| Country of origin | DE |
| Customs tariff number | 85437090990 |
| UNSPSC | 32,151,706 |
| eCl@ss 10.0 | 27-24-26-01 |
| eCl@ss 9.0 | 27-24-26-01 |
| ETIM 9.0 | EC001596 |
| ETIM 10.0 | EC001596 |
| ECCN | NO US CLASSIFICATION |
| RoHS Compliance Status | Compliant,No Exemption |
| Power consumption | 1 W |
| Certified for UL hazardous location division 1 | Yes |
| Certified for UL hazardous location division 2 | No |
| Certified for UL hazardous location group A (acetylene) | Yes |
| Certified for UL hazardous location group B (hydrogen) | Yes |
| Certified for UL hazardous location group C (ethylene) | Yes |
| Certified for UL hazardous location group D (propane) | Yes |
| Certified for UL hazardous location group E (metal dusts) | No |
| Certified for UL hazardous location class I | Yes |
| Certified for UL hazardous location class II | No |
| Certified for UL hazardous location class III | No |
| Supporting protocol for EtherCAT | No |
| Supply voltage DC | 5 V |
| Voltage type (supply voltage) | DC |
| Input, current | No |
| Input, voltage | No |
| Input, resistor | Yes |
| Input, resistance thermometer | No |
| Input, thermocouple | No |
| Input signal, configurable | No |
| Resolution of the analogue inputs | 12 Bit |
| Output, current | No |
| Output, voltage | No |
| Output signal configurable | No |
| Number of analogue inputs | 4 |
| Analogue inputs configurable | No |
| Analogue outputs configurable | No |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for CAN | No |
| Supporting protocol for INTERBUS | No |
| Supporting protocol for ASI | No |
| Supporting protocol for KNX | No |
| Supporting protocol for Modbus | No |
| Supporting protocol for Data-Highway | No |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for SUCONET | No |
| Supporting protocol for LON | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFINET CBA | No |
| Supporting protocol for SERCOS | No |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | No |
| Supporting protocol for AS-Interface Safety at Work | No |
| Supporting protocol for DeviceNet Safety | No |
| Supporting protocol for INTERBUS-Safety | No |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for SafetyBUS p | No |
| Supporting protocol for other bus systems | No |
| Radio standard Bluetooth | No |
| Radio standard WLAN 802.11 | No |
| Radio standard GPRS | No |
| Radio standard GSM | No |
| Mobile communications standard 3G (UMTS) | No |
| IO link master | No |
| System accessory | Yes |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Spring clamp connection |
| Fieldbus connection over separate bus coupler possible | Yes |
| Suitable for rail mounting | Yes |
| Wall mounting/direct mounting | No |
| Front built-in possible | No |
| Rack-assembly possible | No |
| Suitable for safety functions | No |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | ATEX dust-ex-protection, Cat. 3D |