cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

2-Channel analog input; 4 … 20 mA; Single-ended (750-466)

WAGO · Electrical Components · Terminal Blocks
Part Number
750-466  ·  HS 8538.90
2-Channel analog input; 4 … 20 mA; Single-ended (750-466)

WAGO 750-466 Manufacturer description: 2-channel analog input; 4 … 20 mA; Single-ended. 2AI;4-20 mA;Single-sided;light grey.

Technical Specifications

Manufacturer part number (MPN)750-466
EAN / GTIN4045454392949
Sales unitpcs
Number of analog inputs2
Total number of channels (module)2
Signal typeCurrent
Signal type (current)4 … 20 mADC
Sensor connection2 x (2-wire, 3-wire)
Input voltage (max.)10 V
Signal characteristicsSingle-ended
Resolution [bit]12 Bit
Input resistance (max.)220 Ω
Data width2 x 16-bit data; 2 x 8-bit control/status (optional)
Conversion time (typ.)2 ms
Measurement error (reference temperature)25 °C
Measurement error, deviation (max.) from the upper-range value0.2 %
Temperature error (max.) of the upper-range value0.01 %/K
Supply voltage (system)5 VDC; via data contacts
Current consumption (system supply)75 mA
Supply voltage (field)24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
Isolation500 V system/field
IndicatorsLED (A
C) greenFunction AI 1, AI 2; LED (B
D) redError AI 1, AI 2
Number of incoming power jumper contacts2
Number of outgoing power jumper contacts2
Connection technologyI/O: 8 x CAGE CLAMP®
Connectable conductor materialsCopper
Connection typeInputs/Outputs
Solid conductor0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor0.08 … 2.5 mm² / 28 … 14 AWG
Strip length8 … 9 mm / 0.31 … 0.35 inches
Width12 mm / 0.472 inches
Height100 mm / 3.937 inches
Depth69.8 mm / 2.748 inches
Depth from upper-edge of DIN-rail62.6 mm / 2.465 inches
Mounting typeDIN-35 rail
Pluggable connectorfixed
Colorlight gray
Housing materialPolycarbonate; polyamide 6.6
Fire load0.945 MJ
Weight49.9 g
Conformity markingCE
Ambient temperature (operation)0 … +55 °C
Ambient temperature (storage)-40 … +85 °C
Protection typeIP20
Pollution degree2 per IEC 61131-2
Operating altitude0 … 2000 m / 0 … 6562 ft
Mounting positionHorizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
Relative humidity (without condensation)95 %
Vibration resistancePer IEC 60068-2-6
Shock resistance15g per IEC 60068-2-27
EMC immunity to interferenceper EN 61000-6-2
EMC emission of interferenceper EN 61000-6-4
Exposure to pollutantsPer IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %25 ppm
Product Group15 (I/O System)
PU (SPU)1 pcs
Packaging typebox
Country of originDE
Customs tariff number85437090990
UNSPSC32,101,502
eCl@ss 10.027-24-26-01
eCl@ss 9.027-24-26-01
ETIM 9.0EC001596
ETIM 10.0EC001596
ECCNNO US CLASSIFICATION
CAS-No.1303-86-2 | 1317-36-8 | 7439-92-1
REACH Candidate Strip SubstanceDiboron trioxide | Lead | Lead monoxide
RoHS Compliance StatusCompliant,With Exemption
RoHS Exemption7(c)-I | 6(c) | 7(a) | 7(c)-I | 7(c)-II
SCIP notification number (Austria)448233da-0cfd-4410-844a-035cbd6bd610
SCIP notification number (Belgium)52e127be-5791-47a6-8020-c23f994ec05c
SCIP notification number (Bulgaria)dba44114-8852-4acc-986d-1d9ac0b8cba0
SCIP notification number (Czech Republic)2d537bdf-5163-4618-b110-c240649fc2a9
SCIP notification number (Denmark)34958418-b19d-459c-b740-b0a24747702d
SCIP notification number (Finland)50d90c88-4ea7-45f1-8e18-dd32e9f430e3
SCIP notification number (France)a6fffb0c-ab8c-46bf-b023-6cdd572abf5c
SCIP notification number (Germany)c7035a35-bcf1-4c22-9e63-e11c122a59c5
SCIP notification number (Hungary)ce286eb7-13c0-4297-96bf-a559348e7617
SCIP notification number (Italy)aa9f9b98-e9b1-4a80-bd4e-e3ca07d666e8
SCIP notification number (Netherlands)b981cfa1-6233-4bb9-bc02-5b1e09349429
SCIP notification number (Poland)f7a0a260-a9a0-4a39-9b79-076da4f45a37
SCIP notification number (Romania)d2a44cb0-eb95-44ae-a241-b4fe991432cc
SCIP notification number (Sweden)92b73b78-80cf-4254-91ee-348468001171
Power consumption1 W
Certified for UL hazardous location division 1Yes
Certified for UL hazardous location division 2No
Certified for UL hazardous location group A (acetylene)Yes
Certified for UL hazardous location group B (hydrogen)Yes
Certified for UL hazardous location group C (ethylene)Yes
Certified for UL hazardous location group D (propane)Yes
Certified for UL hazardous location group E (metal dusts)No
Certified for UL hazardous location class IYes
Certified for UL hazardous location class IINo
Certified for UL hazardous location class IIINo
Supporting protocol for EtherCATNo
Supply voltage DC24 V
Voltage type (supply voltage)DC
Input, currentYes
Input, resistorNo
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableNo
Resolution of the analogue inputs12 Bit
Output, currentNo
Output, voltageNo
Output signal configurableNo
Number of analogue inputs2
Analogue inputs configurableNo
Analogue outputs configurableNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsNo
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
Degree of protection (IP)IP20
Type of electric connectionSpring clamp connection
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleNo
Rack-assembly possibleNo
Suitable for safety functionsNo
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Appendant operation agent (Ex ia)No
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustATEX dust-ex-protection, Cat. 3D

Properties

MOQ1

Cross-References

Attached Documents