| Manufacturer part number (MPN) | ZB6E1A |
| EAN / GTIN | 3389110775259 |
| Sales unit | pcs |
| Package quantity | 10 pcs |
| Contact configuration | 1 NO |
| Range of product | Harmony XB6 |
| Product or component type | Contact block |
| Device short name | ZB6 |
| Sale per indivisible quantity | 10 |
| Contacts type and composition | 1 NO |
| Contact operation | Slow-break |
| Contact block type | Single |
| Connections - terminals | Pins for printed circuit board |
| Contacts material | Silver alloy (Ag/Ni) |
| Terminals description ISO n°1 | (3-4)NO |
| Product weight | 0.004 kg |
| Positive opening | With conforming to IEC 60947-5-1 appendix K |
| Operating travel | 2 mm (NO changing electrical state); 3.5 mm (total travel) |
| Operating force | 1.6 N NO changing electrical state |
| Mechanical durability | 5000000 cycles |
| Short-circuit protection | 6 A cartridge fuse type gG |
| [Ui] rated insulation voltage | 250 V (pollution degree 3) conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60947-1 |
| [Ie] rated operational current | 3 A at 120 V, AC-15, B300; 1.5 A at 240 V, AC-15, B300; 0.1 A at 250 V, DC-13, R300; 0.22 A at 125 V, DC-13, R300 |
| Electrical durability | 1000000 cycles, AC-15 at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 1000000 cycles, DC-13 at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C |
| Electrical reliability | Λ = 10exp(-8) at 5 V and 1 mA with confidence level of 90 % conforming to IEC 60947-5-4 |
| Protective treatment | TC |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -25…70 °C |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Standards | IEC 60947-1; IEC 60947-5-4; JIS C 852; IEC 60947-5-1; CSA C22.2 No 14; JIS C 4520; UL 508 |
| Product certifications | GOST; CSA; CCC; UL |
| Vibration resistance | +/- 3 mm (f= 2…500 Hz) conforming to IEC 60068-2-6; 5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 30 gn (duration = 18 ms) for half its wave acceleration conforming to IEC 60068-2-27; 50 gn (duration = 11 ms) for half its wave acceleration conforming to IEC 60068-2-27 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 10 |
| Number of Units in Package 3 | 400 |
| Country of origin | FR |
| Warranty (in months) | 18 |