| Manufacturer part number (MPN) | 6ES7137-6BD00-0BA0 |
| EAN / GTIN | 4025515082095 |
| Sales unit | pcs |
| Product type designation | CM 4 x IO-Link ST |
| HW functional status | FS20 |
| Firmware version | V2.2.2 |
| Firmware version — FW update possible | Yes |
| Usable BaseUnits | BU type A0 |
| Color code for module-specific color-coded label | CC04 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Product function — Isochronous mode | No; Only for PROFINET and configuration as version with FW V2.0 or V2.1 |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | STEP 7 V15 or higher |
| Engineering with — STEP 7 configurable/integrated from version | STEP 7 V5.5 or higher |
| Engineering with — PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| Engineering with — PROFINET from GSD version/GSD revision | GSDML V2.3 |
| Operating mode — IO-Link | Yes |
| Operating mode — DI | Yes |
| Operating mode — DQ | Yes; max. 100 mA per channel |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 20.4 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Power supply according to NEC Class 2 required | No |
| Current consumption, max. | 45 mA; without load |
| Number of outputs | 4 |
| Output current — nominal | 700 mA; Per channel |
| 24 V encoder supply — Short-circuit protection | Yes |
| 24 V encoder supply — Output current, max. | 2.1 A |
| Power loss, typ. | 1 W |
| Cable length — unshielded, max. | 20 m; Also applies for shielded cables |
| Number of ports | 4 |
| Number of ports — of which simultaneously controllable | 4 |
| IO-Link protocol 1.0 | Yes |
| IO-Link protocol 1.1 | Yes |
| Transmission rate | 4.8 kBaud (COM1); 38.4 kBaud (COM2), 230.4 kBaud (COM3) |
| Cycle time, min. | 2 ms; dynamic, depending on user data length |
| Size of process data, input per port | 32 byte; max. |
| Size of process data, input per module | 144 byte; max. |
| Size of process data, output per port | 32 byte; max. |
| Size of process data, output per module | 128 byte; max. |
| Memory size for device parameter | 2 kbyte; for each port |
| Time Based IO — TIO IO-Link IN | No; Only for PROFINET and configuration as version with FW V2.0 or V2.1 |
| Time Based IO — TIO IO-Link OUT | No; Only for PROFINET and configuration as version with FW V2.0 or V2.1 |
| Time Based IO — TIO IO-Link IN/OUT | No; Only for PROFINET and configuration as version with FW V2.0 or V2.1 |
| Connection of IO-Link devices — Port type A | Yes |
| Connection of IO-Link devices — Port type B | Yes; 24 V DC via external terminal |
| Connection of IO-Link devices — via three-wire connection | Yes |
| Alarms — Diagnostic alarm | Yes; The port diagnosis is available in the IO-Link mode only. |
| Diagnoses — Monitoring the supply voltage | Yes |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED — Channel status display | Yes; one green LED for channel status Qn (SIO mode) and port status Cn (IO-Link mode) per channel |
| Diagnostics indication LED — for channel diagnostics | Yes; red Fn LED |
| Diagnostics indication LED — for module diagnostics | Yes; green/red DIAG LED |
| Potential separation channels — between the channels and the power supply of the electronics | No |
| Isolation tested with | 707 V DC (type test) |
| Ambient temperature during operation — horizontal installation, min. | -30 °C |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -30 °C |
| Ambient temperature during operation — vertical installation, max. | 50 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 2 000 m; On request: Installation altitudes greater than 2 000 m |
| Dimensions — Width | 15 mm |
| Dimensions — Height | 73 mm |
| Dimensions — Depth | 58 mm |
| Weight, approx. | 30 g |
| Supporting protocol for EtherCAT | No |
| Voltage type (supply voltage) | DC |
| Supporting protocol for TCP/IP | No |
| Supporting protocol for PROFIBUS | Yes |
| Supporting protocol for Modbus | Yes |
| Supporting protocol for DeviceNet | No |
| Supporting protocol for PROFINET IO | Yes |
| Supporting protocol for Foundation Fieldbus | No |
| Supporting protocol for EtherNet/IP | Yes |
| Supporting protocol for PROFIsafe | No |
| Supporting protocol for other bus systems | Yes |
| Radio standard WLAN 802.11 | No |
| Radio standard eGPRS | No |
| Radio standard LTE | No |
| Degree of protection (IP) | IP20 |
| Suitable for safety functions | No |
| Appendant operation agent (Ex ia) | No |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | None |
| Width | 13 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Country of origin | Germany |