Siemens SIMATIC ET 200SP, CM 4XIO-LINK ST Communication module IO-Link Master V1.1 (6ES7137-6BD00-0BA0)

Siemens · Control & Automation · Fieldbus I/O · Germany · siemens.com
Part Number
6ES7137-6BD00-0BA0  ·  HS 8517.62
Siemens SIMATIC ET 200SP, CM 4XIO-LINK ST Communication module IO-Link Master V1.1 (6ES7137-6BD00-0BA0)

Siemens 6ES7137-6BD00-0BA0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC ET 200SP, CM 4 X IO-LINK ST Communication Module module IO-Link master V1.1.

Technical Specifications

Manufacturer part number (MPN)6ES7137-6BD00-0BA0
EAN / GTIN4025515082095
Sales unitpcs
Product type designationCM 4 x IO-Link ST
HW functional statusFS20
Firmware versionV2.2.2
Firmware version — FW update possibleYes
Usable BaseUnitsBU type A0
Color code for module-specific color-coded labelCC04
Product function — I&M dataYes; I&M0 to I&M3
Product function — Isochronous modeNo; Only for PROFINET and configuration as version with FW V2.0 or V2.1
Engineering with — STEP 7 TIA Portal configurable/integrated from versionSTEP 7 V15 or higher
Engineering with — STEP 7 configurable/integrated from versionSTEP 7 V5.5 or higher
Engineering with — PROFIBUS from GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
Engineering with — PROFINET from GSD version/GSD revisionGSDML V2.3
Operating mode — IO-LinkYes
Operating mode — DIYes
Operating mode — DQYes; max. 100 mA per channel
Rated value (DC)24 V
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Power supply according to NEC Class 2 requiredNo
Current consumption, max.45 mA; without load
Number of outputs4
Output current — nominal700 mA; Per channel
24 V encoder supply — Short-circuit protectionYes
24 V encoder supply — Output current, max.2.1 A
Power loss, typ.1 W
Cable length — unshielded, max.20 m; Also applies for shielded cables
Number of ports4
Number of ports — of which simultaneously controllable4
IO-Link protocol 1.0Yes
IO-Link protocol 1.1Yes
Transmission rate4.8 kBaud (COM1); 38.4 kBaud (COM2), 230.4 kBaud (COM3)
Cycle time, min.2 ms; dynamic, depending on user data length
Size of process data, input per port32 byte; max.
Size of process data, input per module144 byte; max.
Size of process data, output per port32 byte; max.
Size of process data, output per module128 byte; max.
Memory size for device parameter2 kbyte; for each port
Time Based IO — TIO IO-Link INNo; Only for PROFINET and configuration as version with FW V2.0 or V2.1
Time Based IO — TIO IO-Link OUTNo; Only for PROFINET and configuration as version with FW V2.0 or V2.1
Time Based IO — TIO IO-Link IN/OUTNo; Only for PROFINET and configuration as version with FW V2.0 or V2.1
Connection of IO-Link devices — Port type AYes
Connection of IO-Link devices — Port type BYes; 24 V DC via external terminal
Connection of IO-Link devices — via three-wire connectionYes
Alarms — Diagnostic alarmYes; The port diagnosis is available in the IO-Link mode only.
Diagnoses — Monitoring the supply voltageYes
Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Diagnostics indication LED — Channel status displayYes; one green LED for channel status Qn (SIO mode) and port status Cn (IO-Link mode) per channel
Diagnostics indication LED — for channel diagnosticsYes; red Fn LED
Diagnostics indication LED — for module diagnosticsYes; green/red DIAG LED
Potential separation channels — between the channels and the power supply of the electronicsNo
Isolation tested with707 V DC (type test)
Ambient temperature during operation — horizontal installation, min.-30 °C
Ambient temperature during operation — horizontal installation, max.60 °C
Ambient temperature during operation — vertical installation, min.-30 °C
Ambient temperature during operation — vertical installation, max.50 °C
Altitude during operation relating to sea level — Installation altitude above sea level, max.2 000 m; On request: Installation altitudes greater than 2 000 m
Dimensions — Width15 mm
Dimensions — Height73 mm
Dimensions — Depth58 mm
Weight, approx.30 g
Supporting protocol for EtherCATNo
Voltage type (supply voltage)DC
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSYes
Supporting protocol for ModbusYes
Supporting protocol for DeviceNetNo
Supporting protocol for PROFINET IOYes
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPYes
Supporting protocol for PROFIsafeNo
Supporting protocol for other bus systemsYes
Radio standard WLAN 802.11No
Radio standard eGPRSNo
Radio standard LTENo
Degree of protection (IP)IP20
Suitable for safety functionsNo
Appendant operation agent (Ex ia)No
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width13 mm
Height73 mm
Depth58 mm
Country of originGermany