cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC S7-1500 AQ 8XU/I HS (6ES7532-5HF00-0AB0)

Siemens · Control & Automation · PLCs · Germany · siemens.com
Part Number
6ES7532-5HF00-0AB0  ·  HS 8538.90
Siemens SIMATIC S7-1500 AQ 8XU/I HS (6ES7532-5HF00-0AB0)

Siemens 6ES7532-5HF00-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. Simatic S7 1500 AQ 8 X U/In/ST, 8 channels in group on 8.

Technical Specifications

Manufacturer part number (MPN)6ES7532-5HF00-0AB0
EAN / GTIN4025515080176
Sales unitpcs
Product type designationAQ 8xU/I HS
HW functional statusfrom FS01
Firmware versionV2.1.0
Product function — I&M dataYes; I&M0 to I&M3
Engineering with — STEP 7 TIA Portal configurable/integrated from versionV14 / -
Engineering with — STEP 7 configurable/integrated from versionV5.5 SP3 / -
Engineering with — PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
Engineering with — PROFINET from GSD version/GSD revisionV2.3 / -
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Current consumption, max.320 mA; with 19.2 V supply
Power consumption from the backplane bus1.15 W
Power loss, typ.7 W
Number of analog outputs8
Voltage output, short-circuit current, max.45 mA
Current output, no-load voltage, max.20 V
Cycle time (all channels), min.125 µs; independent of number of activated channels
Analog output with oversampling — Values per cycle, max.16
Analog output with oversampling — Resolution, min.125 µs
Load impedance (in rated range of output) — with voltage outputs, min.1 kΩ
Load impedance (in rated range of output) — with voltage outputs, capacitive load, max.100 nF
Load impedance (in rated range of output) — with current outputs, max.500 Ω
Load impedance (in rated range of output) — with current outputs, inductive load, max.1 mH
Cable length — shielded, max.200 m
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.16 bit
Integration and conversion time/resolution per channel — Conversion time (per channel)50 µs; independent of number of activated channels
Settling time — for resistive load30 µs; see additional description in the manual
Settling time — for capacitive load100 µs; see additional description in the manual
Settling time — for inductive load100 µs; see additional description in the manual
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.15 %
Temperature error (relative to output range), (+/-)0.002 %/K
Crosstalk between the outputs, max.-100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-)0.05 %
Note regarding accuracyat temperatures below 0 °C, the figures for operating error and temperature error are doubled
Operational error limit in overall temperature range — Voltage, relative to output range, (+/-)0.3 %
Operational error limit in overall temperature range — Current, relative to output range, (+/-)0.3 %
Basic error limit (operational limit at 25 °C) — Voltage, relative to output range, (+/-)0.2 %
Basic error limit (operational limit at 25 °C) — Current, relative to output range, (+/-)0.2 %
Execution and activation time (TCO), min.100 µs
Bus cycle time (TDP), min.250 µs
Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED)Yes; green LED
Potential separation channels — between the channels, in groups of8
Between S- and MANA (UCM)8 V DC
Isolation tested with707 V DC (type test)
Suitable for safety-related tripping of standard modulesYes; from FS04
Highest safety class achievable for safety-related tripping of standard modules — Category according to ISO 13849-1Cat. 3
Highest safety class achievable for safety-related tripping of standard modules — SIL acc. to IEC 62061SIL 2
Highest safety class achievable for safety-related tripping of standard modules — remark on safety-oriented shutdownhttps://support.industry.siemens.com/cs/de/en/view/39198632
Ambient temperature during operation — horizontal installation, min.-30 °C; From FS03
Ambient temperature during operation — horizontal installation, max.60 °C
Ambient temperature during operation — vertical installation, min.-30 °C; From FS03
Ambient temperature during operation — vertical installation, max.40 °C
Altitude during operation relating to sea level — Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity — dew point, min.-60 °C; suitable for dry room applications
Dimensions — Width35 mm
Dimensions — Height147 mm
Dimensions — Depth129 mm
Weight, approx.325 g
Number of analogue outputs8
Analogue inputs configurableNo
Input, currentNo
Input, voltageNo
Input, resistorNo
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableNo
Resolution of the analogue outputs16 Bit
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width35 mm
Height147 mm
Depth129 mm
Country of originGermany

Properties

MOQ1

Cross-References