| Manufacturer part number (MPN) | 6ES7532-5HF00-0AB0 |
| EAN / GTIN | 4025515080176 |
| Sales unit | pcs |
| Product type designation | AQ 8xU/I HS |
| HW functional status | from FS01 |
| Firmware version | V2.1.0 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | V14 / - |
| Engineering with — STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with — PROFIBUS from GSD version/GSD revision | V1.0 / V5.1 |
| Engineering with — PROFINET from GSD version/GSD revision | V2.3 / - |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 320 mA; with 19.2 V supply |
| Power consumption from the backplane bus | 1.15 W |
| Power loss, typ. | 7 W |
| Number of analog outputs | 8 |
| Voltage output, short-circuit current, max. | 45 mA |
| Current output, no-load voltage, max. | 20 V |
| Cycle time (all channels), min. | 125 µs; independent of number of activated channels |
| Analog output with oversampling — Values per cycle, max. | 16 |
| Analog output with oversampling — Resolution, min. | 125 µs |
| Load impedance (in rated range of output) — with voltage outputs, min. | 1 kΩ |
| Load impedance (in rated range of output) — with voltage outputs, capacitive load, max. | 100 nF |
| Load impedance (in rated range of output) — with current outputs, max. | 500 Ω |
| Load impedance (in rated range of output) — with current outputs, inductive load, max. | 1 mH |
| Cable length — shielded, max. | 200 m |
| Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max. | 16 bit |
| Integration and conversion time/resolution per channel — Conversion time (per channel) | 50 µs; independent of number of activated channels |
| Settling time — for resistive load | 30 µs; see additional description in the manual |
| Settling time — for capacitive load | 100 µs; see additional description in the manual |
| Settling time — for inductive load | 100 µs; see additional description in the manual |
| Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) | 0.02 % |
| Linearity error (relative to output range), (+/-) | 0.15 % |
| Temperature error (relative to output range), (+/-) | 0.002 %/K |
| Crosstalk between the outputs, max. | -100 dB |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) | 0.05 % |
| Note regarding accuracy | at temperatures below 0 °C, the figures for operating error and temperature error are doubled |
| Operational error limit in overall temperature range — Voltage, relative to output range, (+/-) | 0.3 % |
| Operational error limit in overall temperature range — Current, relative to output range, (+/-) | 0.3 % |
| Basic error limit (operational limit at 25 °C) — Voltage, relative to output range, (+/-) | 0.2 % |
| Basic error limit (operational limit at 25 °C) — Current, relative to output range, (+/-) | 0.2 % |
| Execution and activation time (TCO), min. | 100 µs |
| Bus cycle time (TDP), min. | 250 µs |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green LED |
| Potential separation channels — between the channels, in groups of | 8 |
| Between S- and MANA (UCM) | 8 V DC |
| Isolation tested with | 707 V DC (type test) |
| Suitable for safety-related tripping of standard modules | Yes; from FS04 |
| Highest safety class achievable for safety-related tripping of standard modules — Category according to ISO 13849-1 | Cat. 3 |
| Highest safety class achievable for safety-related tripping of standard modules — SIL acc. to IEC 62061 | SIL 2 |
| Highest safety class achievable for safety-related tripping of standard modules — remark on safety-oriented shutdown | https://support.industry.siemens.com/cs/de/en/view/39198632 |
| Ambient temperature during operation — horizontal installation, min. | -30 °C; From FS03 |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -30 °C; From FS03 |
| Ambient temperature during operation — vertical installation, max. | 40 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Absolute humidity — dew point, min. | -60 °C; suitable for dry room applications |
| Dimensions — Width | 35 mm |
| Dimensions — Height | 147 mm |
| Dimensions — Depth | 129 mm |
| Weight, approx. | 325 g |
| Number of analogue outputs | 8 |
| Analogue inputs configurable | No |
| Input, current | No |
| Input, voltage | No |
| Input, resistor | No |
| Input, resistance thermometer | No |
| Input, thermocouple | No |
| Input signal, configurable | No |
| Resolution of the analogue outputs | 16 Bit |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | None |
| Width | 35 mm |
| Height | 147 mm |
| Depth | 129 mm |
| Country of origin | Germany |