| Manufacturer part number (MPN) | 6EP1961-3BA01 |
| EAN / GTIN | 4025515152576 |
| Sales unit | pcs |
| Supply voltage at DC rated value | 24 V |
| Input voltage at DC | 24 ... 28.8 V |
| Design of the mains power cut bridging-connection | Backup time: with 40 A load current: 200 ms; with 20 A load current: 400 ms; with 10 A load current: 800 ms; with 5 A load current: 1.6 s. Reduces the backup time by 100 ms in combination with 6EP1 437-3BA10. Maximum backup time 100 ms i... |
| Buffering time in the event of power failure | 0.16 min |
| Formula for output voltage | Vin - approx. 1 V |
| Output current — rated value | 40 A |
| Display version — for normal operation | Green LED for "supply voltage > 20.5 V" |
| Product component PC interface | No |
| Product function communication function | No |
| Design of the interface | without |
| Galvanic isolation between input and output | Yes |
| Operating resource protection class | Class III |
| Protection class IP | IP20 |
| Standard — for emitted interference | EN 55022 Class B |
| Standard — for interference immunity | EN 61000-6-2 |
| Shipbuilding approval | Yes |
| Ambient temperature — during operation | -25 ... +70 °C; with natural convection |
| Ambient temperature — during transport | -40 ... +85 °C |
| Ambient temperature — during storage | -40 ... +85 °C |
| Type of electrical connection | screw terminal |
| Connection method — at input | +: 1 screw terminal for 0.5 ... 10 mm² |
| Connection method — at output | -: 1 screw terminal for 0.5 ... 10 mm² |
| Width × height × depth of the enclosure | 70 × 125 × 121 mm |
| Installation width × mounting height | 70 mm × 225 mm |
| Fastening method | Snaps onto DIN rail EN 60715 35x7.5/15 |
| Housing can be lined up | Yes |
| Mechanical data — net weight | 1.2 kg |
| Country of origin | Germany |