cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC ET 200SP, Analog input module, AI 8XU Basic (6ES7134-6FF00-0AA1)

Siemens · Control & Automation · PLCs & Industrial Networking · Germany · siemens.com
Part Number
6ES7134-6FF00-0AA1  ·  HS 8538.90
Siemens SIMATIC ET 200SP, Analog input module, AI 8XU Basic (6ES7134-6FF00-0AA1)

Siemens 6ES7134-6FF00-0AA1 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC ET 200SP, Analog input module, AI 8XU basic.

Technical Specifications

Manufacturer part number (MPN)6ES7134-6FF00-0AA1
EAN / GTIN4047623405528
Sales unitpcs
Product type designationAI 8xU BA
HW functional statusFS23 or higher
Firmware versionV2.0.0
Firmware version — FW update possibleYes
Usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC02
Product function — I&M dataYes; I&M0 to I&M3
Engineering with — STEP 7 TIA Portal configurable/integrated from versionTIA Portal V21
Engineering with — STEP 7 configurable/integrated from versionV5.7 SP3
Engineering with — PROFIBUS from GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
Engineering with — PROFINET from GSD version/GSD revisionGSDML V2.45
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Current consumption (rated value)25 mA
Current consumption, max.25 mA
Power loss, typ.0.7 W
Address space per module — Address space per module, max.16 byte
Selection of BaseUnit for connection variants — 1-wire connectionBU type A0, A1
Selection of BaseUnit for connection variants — 2-wire connectionBU type A0, A1
Number of analog inputs8; Single-ended
Number of analog inputs — For voltage measurement8
Permissible input voltage for voltage input (destruction limit), max.30 V
Cycle time (all channels), min.1 ms; per channel
Input ranges (rated values), voltages — 0 to +10 VYes; 15 bit
Input ranges (rated values), voltages — Input resistance (0 to 10 V)100 kΩ
Input ranges (rated values), voltages — -10 V to +10 VYes; 16 bit incl. sign
Input ranges (rated values), voltages — Input resistance (-10 V to +10 V)100 kΩ
Cable length — shielded, max.200 m
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.16 bit
Integration and conversion time/resolution per channel — Conversion time (per channel)180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms
Smoothing of measured values — Number of smoothing levels4
Smoothing of measured values — Steplow: Yes; 4x smoothing
Connection of signal encoders — for voltage measurementYes
Connection of signal encoders — for current measurement as 4-wire transducerNo
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range — Voltage, relative to input range, (+/-)0.5 %
Basic error limit (operational limit at 25 °C) — Voltage, relative to input range, (+/-)0.3 %
Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Diagnostics indication LED — Channel status displayYes; green LED
Isolation tested with707 V DC (type test)
Signed firmware updateYes; firmware V2.0.0 or higher
Safely removing dataYes; firmware V2.0.0 or higher
Data integrityYes; firmware V2.0.0 or higher
Ambient temperature during operation — horizontal installation, min.-30 °C; < 0 °C as of FS04
Ambient temperature during operation — horizontal installation, max.60 °C
Ambient temperature during operation — vertical installation, min.-30 °C; < 0 °C as of FS04
Ambient temperature during operation — vertical installation, max.50 °C
Altitude during operation relating to sea level — Installation altitude above sea level, max.5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual
Absolute humidity — dew point, min.-60 °C; suitable for dry room applications
Dimensions — Width15 mm
Dimensions — Height73 mm
Dimensions — Depth58 mm
Weight, approx.31 g
Supporting protocol for EtherCATNo
Voltage type (supply voltage)DC
Resolution of the analogue inputs16 Bit
Output, currentNo
Output, voltageNo
Output signal configurableNo
Number of analogue inputs8
Analogue outputs configurableNo
Degree of protection (IP)IP20
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width15 mm
Height73 mm
Depth58 mm
Country of originGermany

Properties

MOQ1

Cross-References