| Manufacturer part number (MPN) | 6ES7134-6FF00-0AA1 |
| EAN / GTIN | 4047623405528 |
| Sales unit | pcs |
| Product type designation | AI 8xU BA |
| HW functional status | FS23 or higher |
| Firmware version | V2.0.0 |
| Firmware version — FW update possible | Yes |
| Usable BaseUnits | BU type A0, A1 |
| Color code for module-specific color-coded label | CC02 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | TIA Portal V21 |
| Engineering with — STEP 7 configurable/integrated from version | V5.7 SP3 |
| Engineering with — PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| Engineering with — PROFINET from GSD version/GSD revision | GSDML V2.45 |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Current consumption (rated value) | 25 mA |
| Current consumption, max. | 25 mA |
| Power loss, typ. | 0.7 W |
| Address space per module — Address space per module, max. | 16 byte |
| Selection of BaseUnit for connection variants — 1-wire connection | BU type A0, A1 |
| Selection of BaseUnit for connection variants — 2-wire connection | BU type A0, A1 |
| Number of analog inputs | 8; Single-ended |
| Number of analog inputs — For voltage measurement | 8 |
| Permissible input voltage for voltage input (destruction limit), max. | 30 V |
| Cycle time (all channels), min. | 1 ms; per channel |
| Input ranges (rated values), voltages — 0 to +10 V | Yes; 15 bit |
| Input ranges (rated values), voltages — Input resistance (0 to 10 V) | 100 kΩ |
| Input ranges (rated values), voltages — -10 V to +10 V | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages — Input resistance (-10 V to +10 V) | 100 kΩ |
| Cable length — shielded, max. | 200 m |
| Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max. | 16 bit |
| Integration and conversion time/resolution per channel — Conversion time (per channel) | 180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms |
| Smoothing of measured values — Number of smoothing levels | 4 |
| Smoothing of measured values — Step | low: Yes; 4x smoothing |
| Connection of signal encoders — for voltage measurement | Yes |
| Connection of signal encoders — for current measurement as 4-wire transducer | No |
| Linearity error (relative to input range), (+/-) | 0.01 % |
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
| Operational error limit in overall temperature range — Voltage, relative to input range, (+/-) | 0.5 % |
| Basic error limit (operational limit at 25 °C) — Voltage, relative to input range, (+/-) | 0.3 % |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED — Channel status display | Yes; green LED |
| Isolation tested with | 707 V DC (type test) |
| Signed firmware update | Yes; firmware V2.0.0 or higher |
| Safely removing data | Yes; firmware V2.0.0 or higher |
| Data integrity | Yes; firmware V2.0.0 or higher |
| Ambient temperature during operation — horizontal installation, min. | -30 °C; < 0 °C as of FS04 |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -30 °C; < 0 °C as of FS04 |
| Ambient temperature during operation — vertical installation, max. | 50 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual |
| Absolute humidity — dew point, min. | -60 °C; suitable for dry room applications |
| Dimensions — Width | 15 mm |
| Dimensions — Height | 73 mm |
| Dimensions — Depth | 58 mm |
| Weight, approx. | 31 g |
| Supporting protocol for EtherCAT | No |
| Voltage type (supply voltage) | DC |
| Resolution of the analogue inputs | 16 Bit |
| Output, current | No |
| Output, voltage | No |
| Output signal configurable | No |
| Number of analogue inputs | 8 |
| Analogue outputs configurable | No |
| Degree of protection (IP) | IP20 |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | None |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Country of origin | Germany |