cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-08
sales@cballast.com
cballast.com

Siemens SIMATIC ET 200SP AI 2XU Standard (6ES7134-6FB00-0BA1)

Siemens · Control & Automation · PLCs & Industrial Networking · Germany · siemens.com
Part Number
6ES7134-6FB00-0BA1  ·  HS 8538.90
Siemens SIMATIC ET 200SP AI 2XU Standard (6ES7134-6FB00-0BA1)

Siemens 6ES7134-6FB00-0BA1 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC ET 200SP, Analog input module, AI 2XU standard, packaging unit.

Technical Specifications

Manufacturer part number (MPN)6ES7134-6FB00-0BA1
EAN / GTIN4047623406662
Sales unitpcs
Product type designationAI 2xU ST
HW functional statusfrom FS21
Firmware versionV1.0.1
Usable BaseUnitsBU type A0, A1
Color code for module-specific color-coded labelCC00
Product function — I&M dataYes; I&M0 to I&M3
Engineering with — STEP 7 TIA Portal configurable/integrated from versionV13 SP1
Engineering with — STEP 7 configurable/integrated from versionV5.5 SP3 / -
Engineering with — PROFIBUS from GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
Engineering with — PROFINET from GSD version/GSD revisionGSDML V2.3
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Current consumption, max.37 mA
Power loss, typ.0.9 W
Address space per module — Address space per module, max.4 byte; + 1 byte for QI information
Selection of BaseUnit for connection variants — 1-wire connectionBU type A0, A1
Selection of BaseUnit for connection variants — 2-wire connectionBU type A0, A1
Number of analog inputs2
Number of analog inputs — For voltage measurement2
Permissible input voltage for voltage input (destruction limit), max.30 V
Cycle time (all channels), min.500 µs
Input ranges (rated values), voltages — 0 to +10 VYes; 15 bit
Input ranges (rated values), voltages — Input resistance (0 to 10 V)180 kΩ
Input ranges (rated values), voltages — 1 V to 5 VYes; 15 bit
Input ranges (rated values), voltages — Input resistance (1 V to 5 V)180 kΩ
Input ranges (rated values), voltages — -10 V to +10 VYes; 16 bit incl. sign
Input ranges (rated values), voltages — Input resistance (-10 V to +10 V)180 kΩ
Input ranges (rated values), voltages — -5 V to +5 VYes; 16 bit incl. sign
Input ranges (rated values), voltages — Input resistance (-5 V to +5 V)180 kΩ
Cable length — shielded, max.200 m
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.16 bit
Integration and conversion time/resolution per channel — Conversion time (per channel)50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 250 µs without filter
Smoothing of measured values — Number of smoothing levels4
Smoothing of measured values — Steplow: Yes; 4x smoothing
Linearity error (relative to input range), (+/-)0.01 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit in overall temperature range — Voltage, relative to input range, (+/-)0.5 %
Basic error limit (operational limit at 25 °C) — Voltage, relative to input range, (+/-)0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode voltage, max.10 V
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode interference, min.90 dB
Diagnoses — short-circuitYes; at 1 to 5 V
Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Diagnostics indication LED — Channel status displayYes; green LED
Between the inputs (UCM)10 Vpp
Isolation tested with707 V DC (type test)
Ambient temperature during operation — horizontal installation, min.-30 °C; < 0 °C as of FS04
Ambient temperature during operation — horizontal installation, max.60 °C
Ambient temperature during operation — vertical installation, min.-30 °C; < 0 °C as of FS04
Ambient temperature during operation — vertical installation, max.50 °C
Altitude during operation relating to sea level — Installation altitude above sea level, max.5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual
Absolute humidity — dew point, min.-60 °C; suitable for dry room applications
Dimensions — Width15 mm
Dimensions — Height73 mm
Dimensions — Depth58 mm
Weight, approx.31 g
Supporting protocol for EtherCATNo
Voltage type (supply voltage)DC
Resolution of the analogue inputs16 Bit
Number of analogue inputs2
Degree of protection (IP)IP20
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width15 mm
Height73 mm
Depth58 mm
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents