| Manufacturer part number (MPN) | 6ES7134-6FB00-0BA1 |
| EAN / GTIN | 4047623406662 |
| Sales unit | pcs |
| Product type designation | AI 2xU ST |
| HW functional status | from FS21 |
| Firmware version | V1.0.1 |
| Usable BaseUnits | BU type A0, A1 |
| Color code for module-specific color-coded label | CC00 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | V13 SP1 |
| Engineering with — STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with — PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| Engineering with — PROFINET from GSD version/GSD revision | GSDML V2.3 |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 37 mA |
| Power loss, typ. | 0.9 W |
| Address space per module — Address space per module, max. | 4 byte; + 1 byte for QI information |
| Selection of BaseUnit for connection variants — 1-wire connection | BU type A0, A1 |
| Selection of BaseUnit for connection variants — 2-wire connection | BU type A0, A1 |
| Number of analog inputs | 2 |
| Number of analog inputs — For voltage measurement | 2 |
| Permissible input voltage for voltage input (destruction limit), max. | 30 V |
| Cycle time (all channels), min. | 500 µs |
| Input ranges (rated values), voltages — 0 to +10 V | Yes; 15 bit |
| Input ranges (rated values), voltages — Input resistance (0 to 10 V) | 180 kΩ |
| Input ranges (rated values), voltages — 1 V to 5 V | Yes; 15 bit |
| Input ranges (rated values), voltages — Input resistance (1 V to 5 V) | 180 kΩ |
| Input ranges (rated values), voltages — -10 V to +10 V | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages — Input resistance (-10 V to +10 V) | 180 kΩ |
| Input ranges (rated values), voltages — -5 V to +5 V | Yes; 16 bit incl. sign |
| Input ranges (rated values), voltages — Input resistance (-5 V to +5 V) | 180 kΩ |
| Cable length — shielded, max. | 200 m |
| Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max. | 16 bit |
| Integration and conversion time/resolution per channel — Conversion time (per channel) | 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 250 µs without filter |
| Smoothing of measured values — Number of smoothing levels | 4 |
| Smoothing of measured values — Step | low: Yes; 4x smoothing |
| Linearity error (relative to input range), (+/-) | 0.01 % |
| Temperature error (relative to input range), (+/-) | 0.005 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
| Operational error limit in overall temperature range — Voltage, relative to input range, (+/-) | 0.5 % |
| Basic error limit (operational limit at 25 °C) — Voltage, relative to input range, (+/-) | 0.3 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode voltage, max. | 10 V |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode interference, min. | 90 dB |
| Diagnoses — short-circuit | Yes; at 1 to 5 V |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED — Channel status display | Yes; green LED |
| Between the inputs (UCM) | 10 Vpp |
| Isolation tested with | 707 V DC (type test) |
| Ambient temperature during operation — horizontal installation, min. | -30 °C; < 0 °C as of FS04 |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -30 °C; < 0 °C as of FS04 |
| Ambient temperature during operation — vertical installation, max. | 50 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual |
| Absolute humidity — dew point, min. | -60 °C; suitable for dry room applications |
| Dimensions — Width | 15 mm |
| Dimensions — Height | 73 mm |
| Dimensions — Depth | 58 mm |
| Weight, approx. | 31 g |
| Supporting protocol for EtherCAT | No |
| Voltage type (supply voltage) | DC |
| Resolution of the analogue inputs | 16 Bit |
| Number of analogue inputs | 2 |
| Degree of protection (IP) | IP20 |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | None |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Country of origin | Germany |