Siemens SIMATIC DP, Electronics module f. ET200SP, F-RQ 1X 24 V DC/24..230VAC/5A ST, 20 mm overall width (6ES7136-6RA00-0BF0)

Siemens · Control & Automation · I/O Modules · Germany · siemens.com
Part Number
6ES7136-6RA00-0BF0  ·  HS 8538.90
Siemens SIMATIC DP, Electronics module f. ET200SP, F-RQ 1X 24 V DC/24..230VAC/5A ST, 20 mm overall width (6ES7136-6RA00-0BF0)

Siemens 6ES7136-6RA00-0BF0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC DP, Electron. Module for ET200SP, F-RQ 1X24VDC/24.230VAC/5A ST.

Technical Specifications

Manufacturer part number (MPN)6ES7136-6RA00-0BF0
EAN / GTIN4047623402596
Sales unitpcs
Product type designationF-RQ 24 ... 48VDC/24 ... 230VAC/5A ST
Usable BaseUnitsBU type F0
Color code for module-specific color-coded labelCC42
Product function — I&M dataYes; I&M0 to I&M3
Engineering with — STEP 7 TIA Portal configurable/integrated from versionV13
Engineering with — STEP 7 configurable/integrated from versionV5.5 SP4 and higher
Engineering with — PROFINET from GSD version/GSD revisionV2.31
Rated value (DC)24 V; Coil voltage
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Power supply according to NEC Class 2 requiredNo
Power consumption from the backplane bus100 mW
Power loss, typ.1 W
Address space per module — Inputs1 byte
Type of digital outputRelays
Number of digital outputs1
Limitation of inductive shutdown voltage toNo
Controlling a digital inputYes
Switching capacity of the outputs — with resistive load, max.5 A
Switching capacity of the outputs — on lamp load, max.25 W
Switching frequency — with resistive load, max.2 Hz
Switching frequency — with inductive load, max.0.1 Hz; See data in manual
Switching frequency — with inductive load (acc. to IEC 60947-5-1, DC13), max.0.1 Hz
Switching frequency — with inductive load (acc. to IEC 60947-5-1, AC15), max.2 Hz
Horizontal installation — up to 40 °C, max.5 A; note derating data in the manual
Horizontal installation — up to 50 °C, max.4 A; note derating data in the manual
Horizontal installation — up to 60 °C, max.3 A; note derating data in the manual
Vertical installation — up to 50 °C, max.3 A; note derating data in the manual
Relay outputs — Number of relay outputs1; 2 NO contacts
Relay outputs — Rated supply voltage of relay coil L+ (DC)24 V
Relay outputs — Current consumption of relays (coil current of all relays), max.70 mA
Relay outputs — external protection for relay outputsyes; 6 A, see data in manual
Relay outputs — Relay approved acc. to UL 508Yes; Pilot Duty B300, R300
Switching capacity of contacts — with inductive load, max.see additional description in the manual
Switching capacity of contacts — with resistive load, max.see additional description in the manual
Switching capacity of contacts — Thermal continuous current, max.5 A
Switching capacity of contacts — Switching current, min.1 mA
Switching capacity of contacts — Switching current after exceeding 300 mA, min.10 mA
Switching capacity of contacts — Switching current after exceeding 300 mA, max.5 A
Switching capacity of contacts — Rated switching voltage (DC)24 V
Switching capacity of contacts — Rated switching voltage (AC)230 V
Cable length — shielded, max.500 m; for load contacts
Cable length — unshielded, max.300 m; for load contacts
Cable length — Control cable (input), max.10 m
Diagnostics indication LED — Channel status displayYes; green LED
Between channels and backplane bus/supply voltage250 V AC (reinforced insulation)
Isolation tested with2 545 V DC/2 s (routine test)
Overvoltage categoryIII (according to IEC/EN 61131-2:2007 and EN 298:2022), II (according to IEC 61131-2:2017 and IEC 61010-2-201)
Tested with — between channels and backplane bus/supply voltageDC 2 545 V 2 s (routine test), impulse voltage test DC 7 200 V / 5 positive and 5 negative pulses (type test)
Tested with — between backplane bus and supply voltage707 V DC (type test)
Highest safety class achievable in safety mode — Category according to ISO 13849-14
Highest safety class achievable in safety mode — SIL acc. to IEC 61508SIL 3
Ambient temperature during operation — horizontal installation, min.0 °C
Ambient temperature during operation — horizontal installation, max.60 °C
Ambient temperature during operation — vertical installation, min.0 °C
Ambient temperature during operation — vertical installation, max.50 °C
Dimensions — Width20 mm
Dimensions — Height73 mm
Dimensions — Depth58 mm
Weight, approx.56 g
Supporting protocol for EtherCATYes
Voltage type (supply voltage)DC
Digital inputs configurableNo
Type of voltage (input voltage)DC
Permitted voltage at output20.4–264 V
Type of output voltageAC/DC
Degree of protection (IP)IP20
Type of electric connectionSpring clamp connection
SIL according to IEC 615083
Performance level according to EN ISO 13849-1Level e
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width20 mm
Height73 mm
Depth58 mm
Country of originGermany