Siemens SIMATIC ET 200SP, digital output module, DQ 4X 24 V DC/2A High Speed (6ES7132-6BD20-0DA0)

Siemens · Control & Automation · I/O Modules · Germany · siemens.com
Part Number
6ES7132-6BD20-0DA0  ·  HS 8538.90
Siemens SIMATIC ET 200SP, digital output module, DQ 4X 24 V DC/2A High Speed (6ES7132-6BD20-0DA0)

Siemens 6ES7132-6BD20-0DA0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC ET 200SP, Digital output module, DQ 4X24VDC/2A High speed.

Technical Specifications

Manufacturer part number (MPN)6ES7132-6BD20-0DA0
EAN / GTIN4047623405641
Sales unitpcs
Product type designationDQ 4x24 V DC/2 A HS
HW functional statusFrom FS05
Engineering with — STEP 7 TIA Portal configurable/integrated from versionSTEP 7 V15.1 or higher
Engineering with — STEP 7 configurable/integrated from versionvia GSD as of V5.6 HF4
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Current consumption, max.50 mA; without load
Power loss, typ.2.5 W; at 24 V, 25 °C, DQ mode, 2 A per channel
Address space per module — Inputs1 byte; Max. 14 bytes in the cam control operating mode
Address space per module — Outputs1 byte; Max. 16 bytes in the oversampling operating mode
Selection of BaseUnit for connection variants — 2-wire connectionBU type A0
Selection of BaseUnit for connection variants — 3-wire connectionBU type A0 with AUX terminals or potential distributor module
Selection of BaseUnit for connection variants — 4-wire connectionBU type A0 + Potential distributor module
Number of digital outputs4
Short-circuit protection — Response threshold, typ.6 A
Limitation of inductive shutdown voltage toM (-1 V)
Digital output functions, parameterizable — Number of cam tracks, max.4
Digital output functions, parameterizable — Number of cams per module, max.16
Digital output functions, parameterizable — Number of cams per track, max.16
Digital output functions, parameterizable — Range of values for comparison values, max.-2,147,483,648 to 2,147,483,647 (user-specific within this range)
Digital output functions, parameterizable — Number, max.4
Digital output functions, parameterizable — Cycle duration, parameterizableYes; 0 ms, 0.2 ms, 0.4 ms, 0.93 ms, 1.33 ms, 4.27 ms, 10.67 ms, 21.33 ms, 34.13 ms, 59.73 ms
Digital output functions, parameterizable — Resolution of the duty cycle0.1 %
Digital output functions, parameterizable — Values per cycle, max.32
Digital output functions, parameterizable — Resolution, min.100 µs
Switching capacity of the outputs — with resistive load, max.2 A
Switching capacity of the outputs — on lamp load, max.10 W
Output current — for signal "1" rated value2 A
Output current — for signal "0" residual current, max.0.1 mA
Output delay with resistive load — "0" to "1", max.1 µs
Output delay with resistive load — "1" to "0", max.1 µs
Switching frequency — with resistive load, max.5 kHz
Switching frequency — with inductive load, max.5 kHz
Switching frequency — on lamp load, max.5 kHz
Total current of the outputs — Current per channel, max.2 A
Total current of the outputs — Current per module, max.8 A
Horizontal installation — up to 30 °C, max.8 A; DQ mode
Horizontal installation — up to 40 °C, max.6.9 A; DQ mode
Horizontal installation — up to 50 °C, max.4.7 A; DQ mode
Horizontal installation — up to 60 °C, max.2.5 A; DQ mode
Vertical installation — up to 30 °C, max.7.2 A; DQ mode
Vertical installation — up to 40 °C, max.5.6 A; DQ mode
Vertical installation — up to 50 °C, max.4 A; DQ mode
Cable length — shielded, max.50 m
Cable length — unshielded, max.50 m
Execution and activation time (TCO), min.40 µs
Bus cycle time (TDP), min.125 µs
Jitter, max.1 µs
Isolation tested with707 V DC (type test)
Ambient temperature during operation — horizontal installation, min.-30 °C
Ambient temperature during operation — horizontal installation, max.60 °C
Ambient temperature during operation — vertical installation, min.-30 °C
Ambient temperature during operation — vertical installation, max.50 °C
Altitude during operation relating to sea level — Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity — dew point, min.-60 °C; suitable for dry room applications
Dimensions — Width15 mm
Dimensions — Height73 mm
Dimensions — Depth58 mm
Weight, approx.31 g
Supporting protocol for EtherCATYes
Voltage type (supply voltage)DC
Type of voltage (input voltage)DC
Output current2 A
Type of output voltageDC
Degree of protection (IP)IP20
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width15 mm
Height73 mm
Depth58 mm
Country of originGermany

Properties