cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC S7 automation module 6ES7534-7QE00-0AB0

Siemens · Control & Automation · PLCs · Germany · siemens.com
Part Number
6ES7534-7QE00-0AB0  ·  HS 8538.90
Siemens SIMATIC S7 automation module 6ES7534-7QE00-0AB0

Siemens 6ES7534-7QE00-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC S7-1500, Analog in/output module AI4XU/In/R/RTD/TC; 4 channels.

Technical Specifications

Manufacturer part number (MPN)6ES7534-7QE00-0AB0
EAN / GTIN4047623403326
Sales unitpcs
Product familySM 534 analog input/output modules
UPC887621835590
Customs commodity code (HS)85389091
Packaging dimensions (L x W x H)25.6 x 15.4 x 3.4 cm
Net weight0.424 kg
Country of originGermany
Product type designationAI 4xU/I/RTD/TC / AQ 2xU/I ST
HW functional statusfrom FS01
Firmware versionV1.0.0
FW update possibleYes
I&M dataYes; I&M0 to I&M3
STEP 7 TIA Portal configurable/integrated from versionV13 / V13.0.2
PROFINET from GSD version/GSD revisionV2.3
MSI / MSOYes / Yes
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage rated value (DC)24 V
Supply voltage permissible range (DC)19.2 V to 28.8 V
Reverse polarity protectionYes
Current consumption, max.200 mA
Power consumption from the backplane bus0.7 W
Power loss, typ.3.3 W
Number of analog inputs4
Analog inputs for current / voltage measurement4 / 4
Analog inputs for resistance/RTD / thermocouple measurement2 / 4
Number of analog outputs2
Permissible input voltage for voltage input (destruction limit), max.28.8 V
Permissible input current for current input (destruction limit), max.40 mA
Technical unit for temperature measurement adjustableYes; °C/°F/K
Input cable length shielded, max.800 m for U/I, 200 m for R/RTD, 50 m for TC
Voltage output, short-circuit current, max.24 mA
Current output, no-load voltage, max.22 V
Output cycle time (all channels), min.3.2 ms
Load resistance with voltage outputs, min.1 kΩ
Load resistance with current outputs, max.750 Ω
Measurement principleintegrating
Resolution with overrange (bit including sign), max.16 bit
Integration time (ms)2.5 / 16.67 / 20 / 100 ms
Basic conversion time, including integration time (ms)9 / 23 / 27 / 107 ms
Output conversion time (per channel)0.5 ms
Interference voltage suppression for interference frequency f1 in Hz400 / 60 / 50 / 10
Linearity error, input (relative to input range), (+/-)0.02 %
Linearity error, output (relative to output range), (+/-)0.15 %
Temperature error, input (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, max.-80 dB
Crosstalk between the outputs, max.-100 dB
Operational error limit, input voltage (+/-)0.3 %
Basic error limit at 25 °C, input voltage (+/-)0.1 %
Common mode voltage, max.10 V
Common mode interference, min.60 dB
Diagnostics functionYes
Substitute values connectableYes
Wire break diagnosticsYes; input 1..5 V, 4..20 mA, TC, R, RTD and output current
Potential separation between the channels and backplane busYes
Permissible potential difference between the inputs (UCM)20 V DC
Isolation tested with707 V DC (type test)
Ambient temperature, horizontal installation, min.-25 °C; from FS04
Ambient temperature, horizontal installation, max.60 °C
Ambient temperature, vertical installation, max.40 °C
Installation altitude above sea level, max.5000 m
Width25 mm
Height147 mm
Depth129 mm
Weight, approx.250 g
Number of analogue inputs4
Number of analogue outputs2
Resolution of the analogue inputs16 Bit
Resolution of the analogue outputs16 Bit
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone

Properties

MOQ1

Cross-References

Attached Documents