cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC S7 automation module 6ES7532-5NB00-0AB0

Siemens · Control & Automation · PLCs · Germany · siemens.com
Part Number
6ES7532-5NB00-0AB0  ·  HS 8538.90
Siemens SIMATIC S7 automation module 6ES7532-5NB00-0AB0

Siemens 6ES7532-5NB00-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC S7-1500, Analog output module AQ 2 X U/In ST; 16-bits resolution.

Technical Specifications

Manufacturer part number (MPN)6ES7532-5NB00-0AB0
EAN / GTIN4047623403487
Sales unitpcs
Product type designationAQ 2xU/I ST
HW functional statusfrom FS01
Firmware versionV1.0.0
FW update possibleYes
I&M dataYes; I&M0 to I&M3
STEP 7 TIA Portal configurable/integrated from versionV13 / V13.0.2
STEP 7 configurable/integrated from versionV5.5 SP3 / -
PROFIBUS from GSD version/GSD revisionV1.0 / V5.1
PROFINET from GSD version/GSD revisionV2.3 / -
MSOYes
Reparameterization possible in RUNYes
Calibration possible in RUNYes
Supply voltage — Rated value (DC)24 V
Supply voltage — permissible range, lower limit (DC)19.2 V
Supply voltage — permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Current consumption, max.110 mA
Power consumption from the backplane bus0.65 W
Power loss, typ.2.7 W
Analog outputs — Number of analog outputs2
Voltage output ranges0 to 10 V, 1 V to 5 V, -10 V to +10 V
Current output ranges0 to 20 mA, -20 mA to +20 mA, 4 mA to 20 mA
Voltage output, short-circuit protectionYes
Voltage output, short-circuit current, max.24 mA
Current output, no-load voltage, max.22 V
Cycle time (all channels), min.3.2 ms; independent of number of activated channels
Connection for voltage output two-wire connectionYes
Connection for voltage output four-wire connectionYes
Connection for current output two-wire connectionYes
Load resistance with voltage outputs, min.1 kΩ; 0.5 kΩ at 1 to 5 V
Load with voltage outputs, capacitive, max.1 µF
Load with current outputs, max.750 Ω
Load with current outputs, inductive, max.10 mH
Cable length shielded, max.800 m for current, 200 m for voltage
Resolution with overrange (bit including sign), max.16 bit
Conversion time (per channel)0.5 ms
Settling time for resistive load1.5 ms
Settling time for capacitive load2.5 ms
Settling time for inductive load2.5 ms
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-)0.02 %
Linearity error (relative to output range), (+/-)0.15 %
Temperature error (relative to output range), (+/-)0.002 %/K
Crosstalk between the outputs, max.-100 dB
Repeat accuracy in steady state at 25 °C (+/-)0.05 %
Operational error limit voltage (relative to output range), (+/-)0.3 %
Operational error limit current (relative to output range), (+/-)0.3 %
Diagnostics functionYes
Substitute values connectableYes
Diagnostic alarmYes
Monitoring the supply voltageYes
Wire break detectionYes; only for output type "current"
Short-circuit detectionYes; only for output type "voltage"
Overflow/Underflow diagnosticsYes
RUN LEDgreen; ERROR LED: red
Channel status displayYes; green LED
Potential separation between the channelsNo; in groups of 2
Potential separation between the channels and backplane busYes
Potential separation between the channels and load voltage L+Yes
Permissible potential difference between S- and MANA (UCM)8 V DC
Isolation tested with707 V DC (type test)
Siemens Eco Profile (SEP)Siemens EcoTech
Suitable for safety-related tripping of standard modulesYes; from FS02
Performance level according to ISO 13849-1PL d
Category according to ISO 13849-1Cat. 3
SILCL according to IEC 62061SIL 2
Ambient temperature horizontal installation, min.-30 °C (from FS04)
Ambient temperature horizontal installation, max.60 °C
Ambient temperature vertical installation, min.-30 °C (from FS04)
Ambient temperature vertical installation, max.40 °C
Installation altitude above sea level, max.5000 m; restrictions above 2000 m
Dimensions — Width25 mm
Dimensions — Height147 mm
Dimensions — Depth129 mm
Weight, approx.200 g
NoteSupplied incl. 40-pole push-in front connectors
Number of analogue outputs2
Analogue inputs configurableNo
Input, currentNo
Input, voltageNo
Input, resistorNo
Input, resistance thermometerNo
Input, thermocoupleNo
Input signal, configurableNo
Resolution of the analogue outputs16 Bit
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width25 mm
Height147 mm
Depth129 mm
Country of originGermany

Properties

MOQ1

Cross-References