Siemens SIMATIC S7-1200F CPU 1214 FC, DC/DC/DC, 14DI/10DO/2AI (6ES7214-1AF40-0XB0)

Siemens · Control & Automation · PLCs · Germany · siemens.com
Part Number
6ES7214-1AF40-0XB0  ·  HS 8537.10
Siemens SIMATIC S7-1200F CPU 1214 FC, DC/DC/DC, 14DI/10DO/2AI (6ES7214-1AF40-0XB0)

Siemens 6ES7214-1AF40-0XB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC S7-1200F, CPU 1214 FC, Compact-CPU Fail-Safe, DC/DC/DC.

Technical Specifications

Manufacturer part number (MPN)6ES7214-1AF40-0XB0
EAN / GTIN4025515082910
Sales unitpcs
Product type designationCPU 1214FC DC/DC/DC
Firmware versionV4.7
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Load voltage L+ — Rated value (DC)24 V
Load voltage L+ — permissible range, lower limit (DC)20.4 V
Load voltage L+ — permissible range, upper limit (DC)28.8 V
Current consumption (rated value)500 mA; CPU only
Current consumption, max.1 500 mA; CPU with all expansion modules
Inrush current, max.12 A; at 28.8 V
I²t0.5 A²·s
For backplane bus (5 V DC), max.1 600 mA; Max. 5 V DC for SM and CM
24 V encoder supply — 24 VL+ minus 4 V DC min.
Power loss, typ.12 W
Work memory — integrated200 kbyte
Load memory — integrated4 Mbyte
Retentive data area (incl. timers, counters, flags), max.14 kbyte
Process image — Inputs, adjustable1 kbyte
Process image — Outputs, adjustable1 kbyte
Input voltage — Rated value (DC)24 V
Input voltage — for signal "0"5 V DC at 1 mA
Input voltage — for signal "1"15 V DC at 2.5 mA
For standard inputs — parameterizable0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
For standard inputs — at "0" to "1", min.0.2 ms
For standard inputs — at "0" to "1", max.12.8 ms
Cable length — shielded, max.500 m; 50 m for technological functions
Cable length — unshielded, max.300 m; for technological functions: No
Number of digital outputs — of which high-speed outputs4; 100 kHz Pulse Train Output
Limitation of inductive shutdown voltage toL+ (-48 V)
Switching capacity of the outputs — with resistive load, max.0.5 A
Switching capacity of the outputs — on lamp load, max.5 W
Output voltage — for signal "0", max.0.1 V; with 10 kOhm load
Output voltage — for signal "1", min.20 V
Output current — for signal "1" rated value0.5 A
Output current — for signal "0" residual current, max.0.1 mA
Output delay with resistive load — "0" to "1", max.1 µs
Output delay with resistive load — "1" to "0", max.5 µs
Switching frequency — of the pulse outputs, with resistive load, max.100 kHz
Number of connections — overallPG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; To...
Traces — Memory size per trace, max.512 kbyte
Counter — Counting frequency, max.100 kHz
Limit frequency (pulse)100 kHz
Interference immunity against discharge of static electricity — Test voltage at air discharge8 kV
Interference immunity against discharge of static electricity — Test voltage at contact discharge6 kV
Free fall — Fall height, max.0.3 m; five times, in product package
Ambient temperature during operation — min.0 °C
Ambient temperature during operation — max.55 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical
Ambient temperature during operation — horizontal installation, min.0 °C
Ambient temperature during operation — horizontal installation, max.55 °C
Ambient temperature during operation — vertical installation, min.0 °C
Ambient temperature during operation — vertical installation, max.45 °C
Ambient temperature during storage/transportation — min.-40 °C
Ambient temperature during storage/transportation — max.70 °C
Altitude during operation relating to sea level — Installation altitude, min.-1 000 m
Altitude during operation relating to sea level — Installation altitude, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Relative humidity — Operation, max.95 %; no condensation
Dimensions — Width110 mm
Dimensions — Height100 mm
Dimensions — Depth75 mm
Weight, approx.415 g
Width110 mm
ModelCompact
Height100 mm
Depth75 mm
Number of digital inputs14
Number of digital outputs10
Number of analogue inputs2
Voltage type (supply voltage)DC
Type of memoryRAM
Memory size125 kByte
Processing time (1K, binary operation)0.08 ms
Max. number of addressable analogue I/O-ports2
Max. number of addressable digital I/O-ports24
Number of HW-interfaces industrial Ethernet1
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Number of interfaces PROFINET1
Performance level according to EN ISO 13849-1Level e
SIL according to IEC 615083
Mobile communications standard 4G (LTE)No
Supporting protocol for EtherCATNo
Country of originGermany