| Manufacturer part number (MPN) | 6ES7134-7SD00-0AB0 |
| EAN / GTIN | 4019169132077 |
| Sales unit | pcs |
| Product type designation | 4AI TC |
| HW functional status | 7 |
| Firmware version | V1.0.1 |
| Permissible range, lower limit (DC) | 20.4 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption, typ. | 17 mA |
| From load voltage (power bus), max. | 30 mA |
| Power loss, typ. | 0.4 W |
| Number of analog inputs | 4 |
| Cycle time (all channels) max. | 320 ms; 66 ms basic conversion time x 4 channels with interference frequency suppression 60 Hz, 80 ms basic conversion time x 4 channels with interference frequency suppression 50 Hz |
| Input ranges (rated values), voltages — Input resistance (-80 mV to +80 mV) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type B) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type C) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type E) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (type J) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type K) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type L) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type N) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type R) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type S) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type T) | 1 000 kΩ |
| Input ranges (rated values), thermocouples — Input resistance (Type U) | 1 000 kΩ |
| Temperature compensation — external temperature compensation with compensations socket | Yes; via temperature value, acquired by an analog module of the same ET 200iSP station |
| Cable length — shielded, max. | 50 m |
| Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max. | 16 bit |
| Integration and conversion time/resolution per channel — Basic conversion time, including integration time (ms) | 80 ms at 50 Hz; 66 ms at 60 Hz |
| Integration and conversion time/resolution per channel — additional conversion time for wire-break monitoring | 5 ms |
| Smoothing of measured values — Parameterizable | Yes; in 4 stages |
| Smoothing of measured values — Step | None: Yes; 1x cycle time |
| Linearity error (relative to input range), (+/-) | 0.015 % |
| Temperature error (relative to input range), (+/-) | 0.02 %/K |
| Crosstalk between the inputs, min. | -50 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.01 % |
| Operational error limit in overall temperature range — Voltage, relative to input range, (+/-) | 0.15 % |
| Basic error limit (operational limit at 25 °C) — Voltage, relative to input range, (+/-) | 0.1 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode interference, min. | 90 dB |
| Number of PROFINET interfaces | 0 |
| Diagnoses — Wire break | Yes; R > 1.7 kOhm |
| Module for Ex(i) protection | Yes; for more Co/Lo combinations, see certificate IECEx KEM 05.0008 |
| Maximum values for connecting terminals for gas group IIC — Uo (no-load voltage), max. | 5.9 V |
| Maximum values for connecting terminals for gas group IIC — Io (short-circuit current), max. | 15 mA |
| Maximum values for connecting terminals for gas group IIC — Po (power output), max. | 23 mW |
| Maximum values for connecting terminals for gas group IIC — Co (permissible external capacity), max. | 43 µF |
| Maximum values for connecting terminals for gas group IIC — Lo (permissible external inductivity), max. | 100 mH |
| IP degree of protection | IP30 |
| CE mark | CE 0344 |
| UKCA mark | DEKRA 21UKEX0086 Importer UK: Siemens plc Manchester M20 2UR |
| CULus | LISTED E334384 |
| FM approval | CLASSIFIED 3025852 |
| INMETRO certificate | UL-BR 12.0071 |
| Use in hazardous areas — ATEX marking | II 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb |
| Use in hazardous areas — Explosion protection category for gas | ATEX gas explosion protection, Zone 1 |
| Use in hazardous areas — Explosion protection category for dust | ATEX dust explosion protection, Zone 21 always install in corresponding enclosure |
| Dimensions — Width | 30 mm |
| Dimensions — Height | 129 mm |
| Dimensions — Depth | 136.5 mm |
| Weight, approx. | 230 g |
| Voltage type (supply voltage) | DC |
| Resolution of the analogue inputs | 16 Bit |
| Number of analogue inputs | 4 |
| Degree of protection (IP) | IP30 |
| Type of electric connection | Screw-/spring clamp connection |
| SIL according to IEC 61508 | None |
| Performance level according to EN ISO 13849-1 | None |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 2G |
| Explosion safety category for dust | ATEX dust-ex-protection, Cat. 2D |
| Width | 30 mm |
| Height | 129 mm |
| Depth | 136.5 mm |
| Country of origin | Germany |