Siemens SIMATIC, electronic module for ET200ISP, 4 AI, TC: for connection of thermocouples (voltage measurement) (6ES7134-7SD00-0AB0)

Siemens · Control & Automation · PLCs & Industrial Networking · Germany · siemens.com
Part Number
6ES7134-7SD00-0AB0  ·  HS 8538.90
Siemens SIMATIC, electronic module for ET200ISP, 4 AI, TC: for connection of thermocouples (voltage measurement) (6ES7134-7SD00-0AB0)

Siemens 6ES7134-7SD00-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC ET 200iSP 4AI TC.

Technical Specifications

Manufacturer part number (MPN)6ES7134-7SD00-0AB0
EAN / GTIN4019169132077
Sales unitpcs
Product type designation4AI TC
HW functional status7
Firmware versionV1.0.1
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Current consumption, typ.17 mA
From load voltage (power bus), max.30 mA
Power loss, typ.0.4 W
Number of analog inputs4
Cycle time (all channels) max.320 ms; 66 ms basic conversion time x 4 channels with interference frequency suppression 60 Hz, 80 ms basic conversion time x 4 channels with interference frequency suppression 50 Hz
Input ranges (rated values), voltages — Input resistance (-80 mV to +80 mV)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type B)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type C)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type E)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (type J)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type K)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type L)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type N)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type R)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type S)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type T)1 000 kΩ
Input ranges (rated values), thermocouples — Input resistance (Type U)1 000 kΩ
Temperature compensation — external temperature compensation with compensations socketYes; via temperature value, acquired by an analog module of the same ET 200iSP station
Cable length — shielded, max.50 m
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.16 bit
Integration and conversion time/resolution per channel — Basic conversion time, including integration time (ms)80 ms at 50 Hz; 66 ms at 60 Hz
Integration and conversion time/resolution per channel — additional conversion time for wire-break monitoring5 ms
Smoothing of measured values — ParameterizableYes; in 4 stages
Smoothing of measured values — StepNone: Yes; 1x cycle time
Linearity error (relative to input range), (+/-)0.015 %
Temperature error (relative to input range), (+/-)0.02 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.01 %
Operational error limit in overall temperature range — Voltage, relative to input range, (+/-)0.15 %
Basic error limit (operational limit at 25 °C) — Voltage, relative to input range, (+/-)0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency — Common mode interference, min.90 dB
Number of PROFINET interfaces0
Diagnoses — Wire breakYes; R > 1.7 kOhm
Module for Ex(i) protectionYes; for more Co/Lo combinations, see certificate IECEx KEM 05.0008
Maximum values for connecting terminals for gas group IIC — Uo (no-load voltage), max.5.9 V
Maximum values for connecting terminals for gas group IIC — Io (short-circuit current), max.15 mA
Maximum values for connecting terminals for gas group IIC — Po (power output), max.23 mW
Maximum values for connecting terminals for gas group IIC — Co (permissible external capacity), max.43 µF
Maximum values for connecting terminals for gas group IIC — Lo (permissible external inductivity), max.100 mH
IP degree of protectionIP30
CE markCE 0344
UKCA markDEKRA 21UKEX0086 Importer UK: Siemens plc Manchester M20 2UR
CULusLISTED E334384
FM approvalCLASSIFIED 3025852
INMETRO certificateUL-BR 12.0071
Use in hazardous areas — ATEX markingII 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
Use in hazardous areas — Explosion protection category for gasATEX gas explosion protection, Zone 1
Use in hazardous areas — Explosion protection category for dustATEX dust explosion protection, Zone 21 always install in corresponding enclosure
Dimensions — Width30 mm
Dimensions — Height129 mm
Dimensions — Depth136.5 mm
Weight, approx.230 g
Voltage type (supply voltage)DC
Resolution of the analogue inputs16 Bit
Number of analogue inputs4
Degree of protection (IP)IP30
Type of electric connectionScrew-/spring clamp connection
SIL according to IEC 61508None
Performance level according to EN ISO 13849-1None
Explosion safety category for gasATEX gas-ex-protection, Cat. 2G
Explosion safety category for dustATEX dust-ex-protection, Cat. 2D
Width30 mm
Height129 mm
Depth136.5 mm
Country of originGermany