cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC, electronic module for ET200ISP, 4 AI HART, 4-Wire transducer, for connecting HART 4-Wire transmitters (6ES7134-7TD50-0AB0)

Siemens · Control & Automation · PLCs & Industrial Networking · Germany · siemens.com
Part Number
6ES7134-7TD50-0AB0  ·  HS 8544.42
Siemens SIMATIC, electronic module for ET200ISP, 4 AI HART, 4-Wire transducer, for connecting HART 4-Wire transmitters (6ES7134-7TD50-0AB0)

Siemens 6ES7134-7TD50-0AB0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform.

Technical Specifications

Manufacturer part number (MPN)6ES7134-7TD50-0AB0
EAN / GTIN4019169131674
HS code8544.42
Sales unitpcs
Product type designation4AI I 4WIRE HART
HW functional status15
Firmware versionV3.0.4
Rack mountingNo
Type of supply voltageDC
Permissible range, lower limit (DC)20.4 V
Permissible range, upper limit (DC)28.8 V
Current consumption, typ.27 mA
From load voltage (power bus), max.30 mA
Power loss, typ.0.4 W
Number of analog inputs4
Permissible input current for current input (destruction limit), max.50 mA
Cycle time (all channels) max.120 ms; 30 ms basic conversion time x4 channels with 60 Hz, 50 Hz interference frequency suppression
Input ranges (rated values), currents — Input resistance (4 mA to 20 mA)295 Ω
Cable length — shielded, max.500 m
Integration and conversion time/resolution per channel — Resolution with overrange (bit including sign), max.12 bit; + sign
Integration and conversion time/resolution per channel — Basic conversion time, including integration time (ms)30 ms
Smoothing of measured values — ParameterizableYes; in 4 stages
Smoothing of measured values — StepNone: Yes; 1x cycle time
Linearity error (relative to input range), (+/-)0.015 %
Temperature error (relative to input range), (+/-)0.005 %/K
Crosstalk between the inputs, min.-50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.01 %
Operational error limit in overall temperature range — Current, relative to input range, (+/-)0.15 %
Basic error limit (operational limit at 25 °C) — Current, relative to input range, (+/-)0.1 %
Number of PROFINET interfaces0
Diagnoses — Wire breakYes; I load < 3.6 mA
Module for Ex(i) protectionYes; for more Co/Lo combinations, see certificate IECEx KEM 05.0007
Maximum values for connecting terminals for gas group IIC — Uo (no-load voltage), max.0.9 V
Maximum values for connecting terminals for gas group IIC — Io (short-circuit current), max.0.8 mA
Maximum values for connecting terminals for gas group IIC — Po (power output), max.0.2 mW
Maximum values for connecting terminals for gas group IIC — Co (permissible external capacity), max.1 000 µF
Maximum values for connecting terminals for gas group IIC — Lo (permissible external inductivity), max.1 000 mH
Maximum values for connecting terminals for gas group IIC — Ui (intrinsically safe input voltage), max.30 V
Maximum values for connecting terminals for gas group IIC — Ii (intrinsically safe input current), max.150 mA
Maximum values for connecting terminals for gas group IIC — Pi (intrinsically safe input power), max.1.2 W
IP degree of protectionIP30
CE markCE 0344
UKCA markDEKRA 21UKEX0090 Importer UK: Siemens plc Manchester M20 2UR
CULusLISTED E334384
FM approvalCLASSIFIED 3025852
INMETRO certificateUL-BR 12.0074
Use in hazardous areas — ATEX markingII 2 G (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G (1) D Ex ib [ia IIIC Da] IIC T4 Gb I M2 Ex ib [ia] I Mb
Use in hazardous areas — ATEX certificateKEMA 04 ATEX 1245
Use in hazardous areas — IECExIECEx KEM 05.0007
Use in hazardous areas — CCC Ex2020322316002942
Use in hazardous areas — EAC ExPB Ex ib [ia] I Mb 1Ex ib [ia Ga] IIC T4 Gb [Ex ia Da] IIIC
Use in hazardous areas — FM markingClass I, Zone 1 AEx ib [ia] IIC T4 Ex ib IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 AIS, Class I, DIV.1, GP. A,B,C,D T4 DIP Class II, III, GP. E,F,G
Use in hazardous areas — Explosion protection category for gasATEX gas explosion protection, Zone 1
Use in hazardous areas — Explosion protection category for dustATEX dust explosion protection, Zone 21 always install in corresponding enclosure
Design of electrical connectionScrew/spring-type terminal
Dimensions — Width30 mm
Dimensions — Height129 mm
Dimensions — Depth136.5 mm
Weight, approx.230 g

Properties

MOQ1

Cross-References

Attached Documents