| Manufacturer part number (MPN) | 6ES7134-6JF00-0CA1 |
| EAN / GTIN | 4047623403388 |
| HS code | 8544.42 |
| Sales unit | pcs |
| Product type designation | AI 8xRTD/TC 2-wire HF |
| HW functional status | From FS05 |
| Firmware version | V2.1 |
| Usable BaseUnits | BU type A0, A1 |
| Measuring range scalable | Yes |
| Engineering with STEP 7 TIA Portal from version | V16, V17 / V18 |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Current consumption, max. | 35 mA |
| Power loss, typ. | 0.75 W |
| Number of analog inputs | 8 |
| Permissible input voltage for voltage input (destruction limit), max. | 30 V |
| Constant measurement current for resistance-type transmitter, typ. | 2 mA |
| Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
| Input ranges, voltages | -1 V to +1 V, -250 mV, -80 mV, -50 mV (16 bit incl. sign, input resistance 1 MΩ) |
| Input ranges, thermocouples | Type B, C, E, J, K, L, N, R, S, T, U, TXK/TXK(L) (16 bit incl. sign) |
| Input ranges, resistance thermometers | Ni 100/120/200/500/1000, LG-Ni 1000, Pt 100/200/500/1000 (16 bit incl. sign) |
| Input ranges, resistors | 0 to 150/300/600/3000/6000 ohms, PTC (15 bit) |
| Thermocouple temperature compensation | internal (BaseUnit A1), reference channel of module/group, fixed reference temperature |
| Cable length shielded, max. | 200 m; 50 m with thermocouples |
| Measurement principle | integrating (Sigma-Delta) |
| Resolution with overrange (bit including sign), max. | 16 bit |
| Interference voltage suppression for interference frequency | 16.6 / 50 / 60 Hz |
| Conversion time (per channel) | 180 / 60 / 50 (67.5 / 22.5 / 18.75) ms |
| Number of smoothing levels | 4; None; 4/8/16 times |
| Linearity error (relative to input range), (+/-) | 0.01 %; ±0.1 % for resistance thermometers |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) | 0.05 % |
| Operational error limit, voltage, relative to input range, (+/-) | 0.1 % |
| Basic error limit at 25 °C, voltage, relative to input range, (+/-) | 0.05 % |
| Common mode interference, min. | 90 dB |
| Diagnostic alarm | Yes |
| Limit value alarm | Yes; two upper and two lower limit values |
| Wire break diagnostics | Yes; channel by channel |
| Channel/module status display | green/red LEDs |
| Between the channels and backplane bus | Yes |
| Between the channels and the power supply of the electronics | Yes |
| Isolation tested with | 707 V DC (type test) |
| Ambient temperature during operation, horizontal installation | -30 ... 60 °C |
| Ambient temperature during operation, vertical installation | -30 ... 50 °C |
| Installation altitude above sea level, max. | 2 000 m |
| Dimensions — Width | 15 mm |
| Dimensions — Height | 73 mm |
| Dimensions — Depth | 58 mm |