cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC S7 automation module 6ES7134-6JF00-0CA1

Siemens · Control & Automation · PLCs & Industrial Networking · Germany · siemens.com
Part Number
6ES7134-6JF00-0CA1  ·  HS 8544.42
Siemens SIMATIC S7 automation module 6ES7134-6JF00-0CA1

Siemens 6ES7134-6JF00-0CA1 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. ET200SP AI8x RTD/TC 2-wire HF.

Technical Specifications

Manufacturer part number (MPN)6ES7134-6JF00-0CA1
EAN / GTIN4047623403388
HS code8544.42
Sales unitpcs
Product type designationAI 8xRTD/TC 2-wire HF
HW functional statusFrom FS05
Firmware versionV2.1
Usable BaseUnitsBU type A0, A1
Measuring range scalableYes
Engineering with STEP 7 TIA Portal from versionV16, V17 / V18
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Current consumption, max.35 mA
Power loss, typ.0.75 W
Number of analog inputs8
Permissible input voltage for voltage input (destruction limit), max.30 V
Constant measurement current for resistance-type transmitter, typ.2 mA
Technical unit for temperature measurement adjustableYes; °C/°F/K
Input ranges, voltages-1 V to +1 V, -250 mV, -80 mV, -50 mV (16 bit incl. sign, input resistance 1 MΩ)
Input ranges, thermocouplesType B, C, E, J, K, L, N, R, S, T, U, TXK/TXK(L) (16 bit incl. sign)
Input ranges, resistance thermometersNi 100/120/200/500/1000, LG-Ni 1000, Pt 100/200/500/1000 (16 bit incl. sign)
Input ranges, resistors0 to 150/300/600/3000/6000 ohms, PTC (15 bit)
Thermocouple temperature compensationinternal (BaseUnit A1), reference channel of module/group, fixed reference temperature
Cable length shielded, max.200 m; 50 m with thermocouples
Measurement principleintegrating (Sigma-Delta)
Resolution with overrange (bit including sign), max.16 bit
Interference voltage suppression for interference frequency16.6 / 50 / 60 Hz
Conversion time (per channel)180 / 60 / 50 (67.5 / 22.5 / 18.75) ms
Number of smoothing levels4; None; 4/8/16 times
Linearity error (relative to input range), (+/-)0.01 %; ±0.1 % for resistance thermometers
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-)0.05 %
Operational error limit, voltage, relative to input range, (+/-)0.1 %
Basic error limit at 25 °C, voltage, relative to input range, (+/-)0.05 %
Common mode interference, min.90 dB
Diagnostic alarmYes
Limit value alarmYes; two upper and two lower limit values
Wire break diagnosticsYes; channel by channel
Channel/module status displaygreen/red LEDs
Between the channels and backplane busYes
Between the channels and the power supply of the electronicsYes
Isolation tested with707 V DC (type test)
Ambient temperature during operation, horizontal installation-30 ... 60 °C
Ambient temperature during operation, vertical installation-30 ... 50 °C
Installation altitude above sea level, max.2 000 m
Dimensions — Width15 mm
Dimensions — Height73 mm
Dimensions — Depth58 mm

Properties

MOQ1

Cross-References