| Manufacturer part number (MPN) | 6ES7211-1BE40-0XB0 |
| HS code | 8536.90 |
| Sales unit | pcs |
| Product type designation | CPU 1211C AC/DC/relay |
| Firmware version | V4.7 |
| Permissible range, lower limit (AC) | 85 V |
| Permissible range, upper limit (AC) | 264 V |
| Line frequency — permissible range, lower limit | 47 Hz |
| Line frequency — permissible range, upper limit | 63 Hz |
| Current consumption (rated value) | 60 mA at 120 V AC; 30 mA at 240 V AC |
| Current consumption, max. | 180 mA at 120 V AC; 90 mA at 240 V AC |
| Inrush current, max. | 20 A; at 264 V |
| I²t | 0.8 A²·s |
| For backplane bus (5 V DC), max. | 750 mA; Max. 5 V DC for CM |
| 24 V encoder supply — 24 V | 20.4 to 28.8V |
| Power loss, typ. | 10 W |
| Work memory — integrated | 75 kbyte |
| Load memory — integrated | 1 Mbyte |
| For bit operations, typ. | 0.08 µs; / instruction |
| For word operations, typ. | 1.7 µs; / instruction |
| For floating point arithmetic, typ. | 2.3 µs; / instruction |
| Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
| Retentive data area (incl. timers, counters, flags), max. | 14 kbyte |
| Flag — Size, max. | 4 kbyte; Size of bit memory address area |
| Local data — per priority class, max. | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB |
| Process image — Inputs, adjustable | 1 kbyte |
| Process image — Outputs, adjustable | 1 kbyte |
| Number of modules per system, max. | 3 communication modules, 1 signal board |
| Input voltage — Rated value (DC) | 24 V |
| Input voltage — for signal "0" | 5 V DC at 1 mA |
| Input voltage — for signal "1" | 15 V DC at 2.5 mA |
| Input current — for signal "1", typ. | 4 mA; nominal |
| For standard inputs — parameterizable | 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms |
| For standard inputs — at "0" to "1", min. | 0.2 ms |
| For standard inputs — at "0" to "1", max. | 12.8 ms |
| Cable length — shielded, max. | 500 m; 50 m for technological functions |
| Cable length — unshielded, max. | 300 m; for technological functions: No |
| Switching capacity of the outputs — with resistive load, max. | 2 A |
| Switching capacity of the outputs — on lamp load, max. | 30 W with DC, 200 W with AC |
| Output delay with resistive load — "0" to "1", max. | 10 ms; max. |
| Output delay with resistive load — "1" to "0", max. | 10 ms; max. |
| Number of connections — overall | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; To... |
| Traces — Memory size per trace, max. | 512 kbyte |
| Counter — Counting frequency, max. | 100 kHz |
| Potential separation digital inputs — Potential separation digital inputs | 500 V AC for 1 minute |
| Interference immunity against discharge of static electricity — Test voltage at air discharge | 8 kV |
| Interference immunity against discharge of static electricity — Test voltage at contact discharge | 6 kV |
| Free fall — Fall height, max. | 0.3 m; five times, in product package |
| Ambient temperature during operation — min. | -20 °C |
| Ambient temperature during operation — max. | 60 °C |
| Ambient temperature during operation — horizontal installation, min. | -20 °C |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -20 °C |
| Ambient temperature during operation — vertical installation, max. | 50 °C |
| Ambient temperature during storage/transportation — min. | -40 °C |
| Ambient temperature during storage/transportation — max. | 70 °C |
| Altitude during operation relating to sea level — Installation altitude, min. | -1 000 m |
| Altitude during operation relating to sea level — Installation altitude, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Relative humidity — Operation, max. | 95 %; no condensation |
| Dimensions — Width | 90 mm |
| Dimensions — Height | 100 mm |
| Dimensions — Depth | 75 mm |
| Weight, approx. | 420 g |
| EAN | 4047623402695 |