| Manufacturer part number (MPN) | 6ES7136-6DB00-0CA0 |
| EAN / GTIN | 4025515082750 |
| Sales unit | pcs |
| Product type designation | F-DQ 4x24VDC/2A PM HF |
| Usable BaseUnits | BU type A0 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | V12 |
| Engineering with — STEP 7 configurable/integrated from version | V5.5 SP3 / - |
| Engineering with — PROFINET from GSD version/GSD revision | V2.31 |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Reverse polarity protection | Yes |
| Power supply according to NEC Class 2 required | No |
| Current consumption (rated value) | 75 mA; without load |
| Current consumption, max. | 21 mA; From the backplane bus |
| Power consumption from the backplane bus | 70 mW |
| Power loss, typ. | 4 W |
| Address space per module — Inputs | 5 byte |
| Address space per module — Outputs | 5 byte |
| Type of digital output | Transistor |
| Number of digital outputs | 4 |
| Digital outputs, parameterizable | Yes |
| Short-circuit protection | Yes |
| Short-circuit protection — Response threshold, typ. | > 3.3 A |
| Open-circuit detection — Response threshold, typ. | 8 mA |
| Overload protection | Yes |
| Overload protection — Response threshold, typ. | 2.9 A |
| Limitation of inductive shutdown voltage to | Typ. -2x 47 V |
| Controlling a digital input | Yes; digital output, according to IEC 61131-2, type 2 |
| Switching capacity of the outputs — with resistive load, max. | 2 A |
| Switching capacity of the outputs — on lamp load, max. | 10 W |
| Load resistance range — lower limit | 12 Ω |
| Load resistance range — upper limit | 2 000 Ω |
| Output voltage — for signal "1", min. | 24 V; L+ (-0.5 V) |
| Output current — for signal "1" rated value | 2 A |
| Output current — for signal "0" residual current, max. | 0.5 mA |
| Switching frequency — with resistive load, max. | 30 Hz; Symmetrical |
| Switching frequency — with inductive load, max. | 0.1 Hz; according to IEC 60947-5-1, DC-13, symmetrical |
| Switching frequency — on lamp load, max. | 10 Hz; Symmetrical |
| Total current of the outputs — Current per channel, max. | 2 A; note derating data in the manual |
| Total current of the outputs — Current per module, max. | 6 A; note derating data in the manual |
| Cable length — shielded, max. | 1 000 m |
| Cable length — unshielded, max. | 500 m |
| Diagnostics function | Yes; See Chapter "Alarms/diagnostic messages" in the manual |
| Diagnostics indication LED — RUN LED | Yes; green LED |
| Diagnostics indication LED — ERROR LED | Yes; red LED |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED — Channel status display | Yes; green LED |
| Diagnostics indication LED — for channel diagnostics | Yes; red LED |
| Diagnostics indication LED — for module diagnostics | Yes; green/red DIAG LED |
| Potential separation channels — between the channels and the power supply of the electronics | No |
| Isolation tested with | 707 V DC (type test) |
| Highest safety class achievable in safety mode — SIL acc. to IEC 61508 | SIL 3 |
| Ambient temperature during operation — horizontal installation, min. | 0 °C |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | 0 °C |
| Ambient temperature during operation — vertical installation, max. | 50 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 4 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
| Dimensions — Width | 15 mm |
| Dimensions — Height | 73 mm |
| Dimensions — Depth | 58 mm |
| Weight, approx. | 57 g |
| Supporting protocol for EtherCAT | Yes |
| Voltage type (supply voltage) | DC |
| Digital inputs configurable | Yes |
| Type of voltage (input voltage) | DC |
| Output current | 2 A |
| Permitted voltage at output | 19.2–28.8 V |
| Type of output voltage | DC |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Spring clamp connection |
| SIL according to IEC 61508 | 3 |
| Performance level according to EN ISO 13849-1 | Level e |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | None |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Country of origin | Germany |