cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Siemens SIMATIC, power supply module 24 V DC for ET200ISP, Ex db eb [ib] IIC T4 Gb, Ex db eb [ib] I Mb (6ES7138-7EA01-0AA0)

Siemens · Switchgear & Protection · DIN Rail Power Supplies · Germany · siemens.com
Part Number
6ES7138-7EA01-0AA0  ·  HS 8504.40
Siemens SIMATIC, power supply module 24 V DC for ET200ISP, Ex db eb [ib] IIC T4 Gb, Ex db eb [ib] I Mb (6ES7138-7EA01-0AA0)

Siemens 6ES7138-7EA01-0AA0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform.

Technical Specifications

Manufacturer part number (MPN)6ES7138-7EA01-0AA0
EAN / GTIN4019169142915
Sales unitpcs
Product type designationPS 24 V DC
Redundancy — Redundancy capabilityYes
Type of supply voltageDC
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)30 V
Reverse polarity protectionYes
External protection for power supply lines (recommendation)protection with 6 A miniature circuit breaker and tripping characteristic C (per ET 200iSP station)
Mains buffering — bridging time for backplane bus, min.0.25 ms
Mains buffering — buffering time for powerbus, min.0.25 ms
Mains buffering — buffering time for IM 152 CPU, min.15 ms
From supply voltage L+, max.4 A
Type of output voltageDC
Current output, max.5 A
Horizontal installation — up to 70 °C, max.5 A
Vertical installation — up to 50 °C, max.5 A
Power loss, typ.20 W; for more information on power loss, see "Limitation of connectable electronic modules" section
Status indicatorYes
AlarmsNo
Diagnoses — Diagnostic information readableYes; via IM 152
Diagnostics indication LED — Group error SF (red)No
Primary/secondaryYes
Between supply voltage and electronicsYes
Tested with — between supply voltage and output voltage600 V DC
IP degree of protectionIP30
CE markCE 0344
UKCA markDEKRA 21UKEX0027 Importer UK: Siemens plc Manchester M20 2UR
CULusLISTED E334384
FM approvalCLASSIFIED 3025852
BISYes
Suitable for safety functionsYes
INMETRO certificateUL-BR 12.0051
Reference designation according to IEC 81346-2 (2009)K
Use in hazardous areas — ATEX markingII 2 G Ex db eb [ib] IIC T4 Gb I M2 Ex db eb [ib] I Mb
Use in hazardous areas — ATEX certificateKEMA 04 ATEX 2263
Use in hazardous areas — IECExIECEx KEM 05.0004
Use in hazardous areas — CCC Ex2020322310002880
Use in hazardous areas — EAC Ex1Ex d e [ib] IIC T4 Gb PII Ex d e [ib Mb] I Mc
Use in hazardous areas — FM markingClass I, Zone 1 AEx d e [ib] IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 DIP, Class II, III, GP. E,F,G
Use in hazardous areas — Explosion protection category for gasATEX gas explosion protection, Zone 1
Use in hazardous areas — Explosion protection category for dustATEX dust explosion protection, Zone 21 always install in corresponding enclosure
Use in hazardous areas — associated equipment (Ex ia)No
Use in hazardous areas — associated equipment (Ex ib)Yes
Marine approval — Germanischer Lloyd (GL)Yes
Marine approval — American Bureau of Shipping (ABS)Yes
Marine approval — Bureau Veritas (BV)Yes
Marine approval — It Norske Veritas (DNV)Yes
Ambient temperature during operation — min.-20 °C
Ambient temperature during operation — max.70 °C
Dimensions — Width60 mm
Dimensions — Height190 mm
Dimensions — Depth136.5 mm
Weight, approx.2 700 g
Width60 mm
Height190 mm
Depth136.5 mm
Type of voltage (input voltage)DC
Output voltage DC19.2 V
Max. output current DC5 A
Max. input current DC4 A
Country of originGermany

Properties

MOQ1

Cross-References