| Manufacturer part number (MPN) | 6ES7138-7EA01-0AA0 |
| EAN / GTIN | 4019169142915 |
| Sales unit | pcs |
| Product type designation | PS 24 V DC |
| Redundancy — Redundancy capability | Yes |
| Type of supply voltage | DC |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 30 V |
| Reverse polarity protection | Yes |
| External protection for power supply lines (recommendation) | protection with 6 A miniature circuit breaker and tripping characteristic C (per ET 200iSP station) |
| Mains buffering — bridging time for backplane bus, min. | 0.25 ms |
| Mains buffering — buffering time for powerbus, min. | 0.25 ms |
| Mains buffering — buffering time for IM 152 CPU, min. | 15 ms |
| From supply voltage L+, max. | 4 A |
| Type of output voltage | DC |
| Current output, max. | 5 A |
| Horizontal installation — up to 70 °C, max. | 5 A |
| Vertical installation — up to 50 °C, max. | 5 A |
| Power loss, typ. | 20 W; for more information on power loss, see "Limitation of connectable electronic modules" section |
| Status indicator | Yes |
| Alarms | No |
| Diagnoses — Diagnostic information readable | Yes; via IM 152 |
| Diagnostics indication LED — Group error SF (red) | No |
| Primary/secondary | Yes |
| Between supply voltage and electronics | Yes |
| Tested with — between supply voltage and output voltage | 600 V DC |
| IP degree of protection | IP30 |
| CE mark | CE 0344 |
| UKCA mark | DEKRA 21UKEX0027 Importer UK: Siemens plc Manchester M20 2UR |
| CULus | LISTED E334384 |
| FM approval | CLASSIFIED 3025852 |
| BIS | Yes |
| Suitable for safety functions | Yes |
| INMETRO certificate | UL-BR 12.0051 |
| Reference designation according to IEC 81346-2 (2009) | K |
| Use in hazardous areas — ATEX marking | II 2 G Ex db eb [ib] IIC T4 Gb I M2 Ex db eb [ib] I Mb |
| Use in hazardous areas — ATEX certificate | KEMA 04 ATEX 2263 |
| Use in hazardous areas — IECEx | IECEx KEM 05.0004 |
| Use in hazardous areas — CCC Ex | 2020322310002880 |
| Use in hazardous areas — EAC Ex | 1Ex d e [ib] IIC T4 Gb PII Ex d e [ib Mb] I Mc |
| Use in hazardous areas — FM marking | Class I, Zone 1 AEx d e [ib] IIC T4 NI, Class I, DIV.2, GP. A,B,C,D T4 DIP, Class II, III, GP. E,F,G |
| Use in hazardous areas — Explosion protection category for gas | ATEX gas explosion protection, Zone 1 |
| Use in hazardous areas — Explosion protection category for dust | ATEX dust explosion protection, Zone 21 always install in corresponding enclosure |
| Use in hazardous areas — associated equipment (Ex ia) | No |
| Use in hazardous areas — associated equipment (Ex ib) | Yes |
| Marine approval — Germanischer Lloyd (GL) | Yes |
| Marine approval — American Bureau of Shipping (ABS) | Yes |
| Marine approval — Bureau Veritas (BV) | Yes |
| Marine approval — It Norske Veritas (DNV) | Yes |
| Ambient temperature during operation — min. | -20 °C |
| Ambient temperature during operation — max. | 70 °C |
| Dimensions — Width | 60 mm |
| Dimensions — Height | 190 mm |
| Dimensions — Depth | 136.5 mm |
| Weight, approx. | 2 700 g |
| Width | 60 mm |
| Height | 190 mm |
| Depth | 136.5 mm |
| Type of voltage (input voltage) | DC |
| Output voltage DC | 19.2 V |
| Max. output current DC | 5 A |
| Max. input current DC | 4 A |
| Country of origin | Germany |