| Manufacturer part number (MPN) | 6ES7132-6HD01-2BB1 |
| EAN / GTIN | 4047623408734 |
| Sales unit | pcs |
| Package quantity | 10 pcs |
| Product type designation | RQ 4x120 VDC ... 230 VAC/5 A NO ST |
| HW functional status | From FS02 |
| Firmware version | V0.0 |
| Usable BaseUnits | BU type B0, B1 |
| Color code for module-specific color-coded label | CC40 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | V14 |
| Engineering with — STEP 7 configurable/integrated from version | V5.5 SP3 |
| Engineering with — PCS 7 configurable/integrated from version | V8.1 SP1 |
| Engineering with — PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| Engineering with — PROFINET from GSD version/GSD revision | GSDML V2.3 |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption (rated value) | 55 mA; without load |
| Rated value (AC) | 230 V |
| Power loss, typ. | 1.5 W |
| Address space per module — Inputs | + 1 byte for QI information |
| Address space per module — Outputs | 1 byte |
| Selection of BaseUnit for connection variants — 2-wire connection | BU type B1 |
| Selection of BaseUnit for connection variants — 3-wire connection | BU type B0 |
| Type of digital output | Relays |
| Number of digital outputs | 4 |
| Switching frequency — with resistive load, max. | 2 Hz |
| Switching frequency — with inductive load, max. | 0.5 Hz |
| Switching frequency — on lamp load, max. | 2 Hz |
| Total current of the outputs — Current per channel, max. | 5 A |
| Total current of the outputs — Current per module, max. | 20 A |
| Horizontal installation — up to 50 °C, max. | 20 A |
| Horizontal installation — up to 60 °C, max. | 16 A |
| Vertical installation — up to 40 °C, max. | 20 A |
| Vertical installation — up to 50 °C, max. | 16 A |
| Relay outputs — Number of relay outputs | 4 |
| Relay outputs — Rated supply voltage of relay coil L+ (DC) | 24 V |
| Relay outputs — Current consumption of relays (coil current of all relays), max. | 40 mA |
| Relay outputs — external protection for relay outputs | Yes, with 6A |
| Relay outputs — Number of operating cycles, max. | 7 000 000; see additional description in the manual |
| Switching capacity of contacts — with inductive load, max. | 2 A; see additional description in the manual |
| Switching capacity of contacts — with resistive load, max. | 5 A; see additional description in the manual |
| Switching capacity of contacts — Thermal continuous current, max. | 5 A; Max. 1 385 VA, 150 W |
| Switching capacity of contacts — Switching current, min. | 100 mA; 5 V DC |
| Switching capacity of contacts — Rated switching voltage (DC) | 24 V DC to 120 V DC |
| Switching capacity of contacts — Rated switching voltage (AC) | 24V AC to 230V AC |
| Cable length — shielded, max. | 1 000 m |
| Cable length — unshielded, max. | 200 m |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED — Channel status display | Yes; green LED |
| Between channels and backplane bus/supply voltage | 240 V AC |
| Isolation tested with | 2 500 V DC (type test) |
| Tested with — between channels and backplane bus/supply voltage | 2 500 V DC |
| Tested with — between backplane bus and supply voltage | 707 V DC (type test) |
| Ambient temperature during operation — horizontal installation, min. | -30 °C |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -30 °C |
| Ambient temperature during operation — vertical installation, max. | 50 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 2 000 m; On request: Installation altitudes greater than 2 000 m |
| Dimensions — Width | 20 mm |
| Dimensions — Height | 73 mm |
| Dimensions — Depth | 58 mm |
| Weight, approx. | 40 g |
| Supporting protocol for EtherCAT | Yes |
| Supply voltage AC 50 Hz | 230 V |
| Voltage type (supply voltage) | DC |
| Digital inputs configurable | No |
| Type of voltage (input voltage) | DC |
| Permitted voltage at output | 20.4–264 V |
| Type of output voltage | AC/DC |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFIsafe | No |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Spring clamp connection |
| Explosion safety category for gas | None |
| Explosion safety category for dust | None |
| Width | 20 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Country of origin | Germany |