| Manufacturer part number (MPN) | 6ES7132-6BH01-2BA0 |
| EAN / GTIN | 4047623408581 |
| Sales unit | pcs |
| Package quantity | 10 pcs |
| Product type designation | DQ 16x24VDC/0.5 ST |
| HW functional status | from FS21 |
| Firmware version | V0.0 |
| Usable BaseUnits | BU type A0 |
| Color code for module-specific color-coded label | CC00 |
| Product function — I&M data | Yes; I&M0 to I&M3 |
| Engineering with — STEP 7 TIA Portal configurable/integrated from version | STEP 7 TIA V14 with HSP0222 / integrated as of TIA V15 |
| Engineering with — STEP 7 configurable/integrated from version | V5.5 SP3 with HSP0230 V7.0 / integrated as of V5.6 SP1 |
| Engineering with — PCS 7 configurable/integrated from version | V8.1 SP1 |
| Engineering with — PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher |
| Engineering with — PROFINET from GSD version/GSD revision | GSDML V2.3 |
| Rated value (DC) | 24 V |
| Permissible range, lower limit (DC) | 19.2 V |
| Permissible range, upper limit (DC) | 28.8 V |
| Current consumption, max. | 30 mA; without load |
| Power loss, typ. | 1 W |
| Address space per module — Address space per module, max. | 2 byte; + 2 bytes for QI information |
| Selection of BaseUnit for connection variants — 1-wire connection | BU type A0 |
| Selection of BaseUnit for connection variants — 2-wire connection | BU type A0 with AUX terminals or potential distributor module |
| Selection of BaseUnit for connection variants — 3-wire connection | BU type A0 with AUX terminals or potential distributor module |
| Type of digital output | Source output (PNP, current-sourcing) |
| Number of digital outputs | 16 |
| Short-circuit protection | Yes; Electronic |
| Short-circuit protection — Response threshold, typ. | 1 A; 0.7 to 1.3 A |
| Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) |
| Switching capacity of the outputs — with resistive load, max. | 0.5 A |
| Switching capacity of the outputs — with inductive load, max. | 0.5 A |
| Switching capacity of the outputs — on lamp load, max. | 5 W |
| Load resistance range — lower limit | 48 Ω |
| Load resistance range — upper limit | 12 kΩ |
| Output current — for signal "1" rated value | 0.5 A |
| Output current — for signal "1" permissible range, max. | 0.5 A |
| Output current — for signal "0" residual current, max. | 0.1 mA |
| Output delay with resistive load — "0" to "1", typ. | 50 µs |
| Output delay with resistive load — "1" to "0", typ. | 100 µs |
| Switching frequency — with resistive load, max. | 100 Hz |
| Switching frequency — with inductive load, max. | 0.1 Hz; higher frequencies are possible, see Equipment Manual "Maximum permitted switching frequency of inductive loads" |
| Switching frequency — on lamp load, max. | 10 Hz |
| Total current of the outputs — Current per channel, max. | 0.5 A |
| Total current of the outputs — Current per module, max. | 8 A; see Equipment Manual "Derating curve" |
| Horizontal installation — up to 40 °C, max. | 8 A |
| Horizontal installation — up to 50 °C, max. | 6 A |
| Horizontal installation — up to 60 °C, max. | 4 A |
| Vertical installation — up to 30 °C, max. | 8 A |
| Vertical installation — up to 40 °C, max. | 6 A |
| Vertical installation — up to 50 °C, max. | 4 A |
| Cable length — shielded, max. | 1 000 m |
| Cable length — unshielded, max. | 600 m |
| Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED |
| Diagnostics indication LED — Channel status display | Yes; green LED |
| Isolation tested with | 707 V DC (type test) |
| Ambient temperature during operation — horizontal installation, min. | -30 °C; < 0 °C as of FS03 |
| Ambient temperature during operation — horizontal installation, max. | 60 °C |
| Ambient temperature during operation — vertical installation, min. | -30 °C; < 0 °C as of FS03 |
| Ambient temperature during operation — vertical installation, max. | 50 °C |
| Altitude during operation relating to sea level — Installation altitude above sea level, max. | 5 000 m; restrictions for installation altitudes > 2 000 m, see ET 200SP system manual |
| Dimensions — Width | 15 mm |
| Dimensions — Height | 73 mm |
| Dimensions — Depth | 58 mm |
| Weight, approx. | 30 g |
| Supporting protocol for EtherCAT | Yes |
| Voltage type (supply voltage) | DC |
| Digital inputs configurable | No |
| Type of voltage (input voltage) | DC |
| Output current | 0.5 A |
| Permitted voltage at output | 19.2–28.8 V |
| Type of output voltage | DC |
| Supporting protocol for PROFIBUS | No |
| Supporting protocol for PROFINET IO | No |
| Supporting protocol for PROFIsafe | No |
| Degree of protection (IP) | IP20 |
| Type of electric connection | Spring clamp connection |
| SIL according to IEC 61508 | 2 |
| Performance level according to EN ISO 13849-1 | Level d |
| Explosion safety category for gas | ATEX gas-ex-protection, Cat. 3G |
| Explosion safety category for dust | None |
| Width | 15 mm |
| Height | 73 mm |
| Depth | 58 mm |
| Country of origin | Germany |