Siemens SIMATIC ET 200SP, Digital output module, DQ 8X 24V DC/0,5A Sink Basic, Sink output (NPN, M-switching) (6ES7132-6BF61-0AA0)

Siemens · Control & Automation · I/O Modules · Germany · siemens.com
Part Number
6ES7132-6BF61-0AA0  ·  HS 8538.90
Siemens SIMATIC ET 200SP, Digital output module, DQ 8X 24V DC/0,5A Sink Basic, Sink output (NPN, M-switching) (6ES7132-6BF61-0AA0)

Siemens 6ES7132-6BF61-0AA0 — SIMATIC S7 automation module. Compact controller or expansion module for the S7-1200 or S7-1500 PLC platform. SIMATIC ET 200SP, Digital output module, DQ 8X24VDC/0,5A Sink Basic.

Technical Specifications

Manufacturer part number (MPN)6ES7132-6BF61-0AA0
EAN / GTIN4047623408741
Sales unitpcs
Product type designationDQ 8x24VDC/0,5A SNK BA
HW functional statusFrom FS02
Firmware versionV0.0
Firmware version — FW update possibleNo
Usable BaseUnitsBU type A0
Color code for module-specific color-coded labelCC01
Product function — I&M dataYes; I&M0 to I&M3
Engineering with — STEP 7 TIA Portal configurable/integrated from versionV14
Engineering with — STEP 7 configurable/integrated from versionV5.5 SP3
Engineering with — PROFIBUS from GSD version/GSD revisionOne GSD file each, Revision 3 and 5 and higher
Engineering with — PROFINET from GSD version/GSD revisionGSDML V2.3
Rated value (DC)24 V
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Current consumption (rated value)30 mA
Current consumption, max.30 mA
Power loss, typ.1.5 W
Address space per module — Outputs1 byte
Type of digital outputSink output (NPN)
Number of digital outputs8
Current-sinkingYes
Current-sourcingNo
Digital outputs, parameterizableYes
Short-circuit protectionYes
Short-circuit protection — Response threshold, typ.1.5 A
Limitation of inductive shutdown voltage toTyp. 47 V
Controlling a digital inputYes
Switching capacity of the outputs — with resistive load, max.0.5 A
Switching capacity of the outputs — on lamp load, max.5 W
Load resistance range — lower limit48 Ω
Load resistance range — upper limit3 400 Ω
Output current — for signal "1" rated value0.5 A
Output current — for signal "1" permissible range, max.0.5 A
Output current — for signal "0" residual current, max.5 µA
Output delay with resistive load — "0" to "1", max.300 µs
Output delay with resistive load — "1" to "0", max.600 µs
Parallel switching of two outputs — for upratingNo
Parallel switching of two outputs — for redundant control of a loadYes
Switching frequency — with resistive load, max.100 Hz
Switching frequency — with inductive load, max.0.5 Hz
Switching frequency — on lamp load, max.10 Hz
Total current of the outputs — Current per channel, max.0.5 A
Total current of the outputs — Current per module, max.4 A
Horizontal installation — up to 60 °C, max.4 A
Vertical installation — up to 50 °C, max.4 A
Cable length — shielded, max.1 000 m
Cable length — unshielded, max.600 m
Diagnostics indication LED — Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Diagnostics indication LED — Channel status displayYes; green LED
Isolation tested with707 V DC (type test)
Ambient temperature during operation — horizontal installation, min.-25 °C
Ambient temperature during operation — horizontal installation, max.60 °C
Ambient temperature during operation — vertical installation, min.-25 °C
Ambient temperature during operation — vertical installation, max.50 °C
Altitude during operation relating to sea level — Installation altitude above sea level, max.5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Absolute humidity — dew point, min.-60 °C; suitable for dry room applications
Dimensions — Width15 mm
Dimensions — Height73 mm
Dimensions — Depth58 mm
Weight, approx.30 g
Supporting protocol for EtherCATYes
Supply voltage DC19.2–28.8 V
Voltage type (supply voltage)DC
Digital inputs configurableNo
Digital outputs configurableYes
Type of voltage (input voltage)DC
Output current0.5 A
Permitted voltage at output19.2–28.8 V
Type of output voltageDC
Short-circuit protection, outputs availableYes
With optical interfaceNo
Supporting protocol for TCP/IPNo
Supporting protocol for PROFIBUSNo
Supporting protocol for CANNo
Supporting protocol for INTERBUSNo
Supporting protocol for ASINo
Supporting protocol for KNXNo
Supporting protocol for ModbusNo
Supporting protocol for Data-HighwayNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for LONNo
Supporting protocol for PROFINET IONo
Supporting protocol for PROFINET CBANo
Supporting protocol for SERCOSNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for EtherNet/IPNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for DeviceNet SafetyNo
Supporting protocol for INTERBUS-SafetyNo
Supporting protocol for PROFIsafeNo
Supporting protocol for SafetyBUS pNo
Supporting protocol for other bus systemsNo
Radio standard BluetoothNo
Radio standard WLAN 802.11No
Radio standard GPRSNo
Radio standard GSMNo
Mobile communications standard 3G (UMTS)No
IO link masterNo
System accessoryYes
Degree of protection (IP)IP20
Type of electric connectionSpring clamp connection
Time delay at signal change0.3–0.6 ms
Fieldbus connection over separate bus coupler possibleYes
Suitable for rail mountingYes
Wall mounting/direct mountingNo
Front built-in possibleYes
Rack-assembly possibleYes
Suitable for safety functionsNo
Appendant operation agent (Ex ia)No
Explosion safety category for gasATEX gas-ex-protection, Cat. 3G
Explosion safety category for dustNone
Width15 mm
Height73 mm
Depth58 mm
Country of originGermany

Properties

MOQ1

Cross-References

Attached Documents