| Manufacturer part number (MPN) | 3RA2325-8XB30-2AC2 |
| EAN / GTIN | 4011209836204 |
| Sales unit | pcs |
| Product brand name | SIRIUS |
| Product designation | Reversing contactor assembly |
| Product type designation | 3RA23 |
| Manufacturer's article number — 1 of the supplied contactor | 3RT2025-2AC20 |
| Manufacturer's article number — 2 of the supplied contactor | 3RT2025-2AC20 |
| Manufacturer's article number — of the supplied RH assembly kit | 3RA2923-2AA2 |
| Size of contactor | S0 |
| Product extension auxiliary switch | Yes |
| Shock resistance at rectangular impulse — at AC | 7,5 g / 5 ms, 4,7 g / 10 ms |
| Shock resistance at rectangular impulse — at DC | 10g / 5 ms, 7,5g / 10 ms |
| Shock resistance with its pulse — at AC | 11,8 g / 5 ms, 7,4 g / 10 ms |
| Shock resistance with its pulse — at DC | 15 g / 5 ms, 10 g / 10 ms |
| Mechanical service life (operating cycles) — of contactor typical | 10 000 000 |
| Mechanical service life (operating cycles) — of the contactor with added auxiliary switch block typical | 10 000 000 |
| Reference code according to IEC 81346-2 | Q |
| General technical data — Net Weight | 1.039 kg |
| Installation altitude at height above sea level maximum | 2 000 m |
| Ambient temperature — during operation | -25 ... +60 °C |
| Ambient temperature — during storage | -55 ... +80 °C |
| Number of poles for main current circuit | 3 |
| Number of NO contacts for main contacts | 3 |
| Number of NC contacts for main contacts | 0 |
| Operating voltage — at AC-3 rated value maximum | 690 V |
| Operating voltage — at AC-3e rated value maximum | 690 V |
| At AC-3 — at 400 V rated value | 17 A |
| At AC-3 — at 500 V rated value | 17 A |
| At AC-3 — at 690 V rated value | 13 A |
| At AC-3e — at 400 V rated value | 17 A |
| At AC-3e — at 500 V rated value | 17 A |
| At AC-3e — at 690 V rated value | 13 A |
| At AC-3e — at AC-4 at 400 V rated value | 7.5 kW |
| Operating frequency — at AC-3 maximum | 1 000 1/h |
| Operating frequency — at AC-3e maximum | 1 000 1/h |
| Type of voltage of the control supply voltage | AC |
| Control supply voltage 1 at AC — at 50 Hz rated value | 24 V |
| Control supply voltage 1 at AC — at 60 Hz rated value | 24 V |
| Operating range factor control supply voltage rated value of magnet coil at AC — at 50 Hz | 0.8 ... 1.1 |
| Operating range factor control supply voltage rated value of magnet coil at AC — at 60 Hz | 0.8 ... 1.1 |
| Apparent pick-up power of magnet coil at AC — at 50 Hz | 65 VA |
| Inductive power factor with closing power of the coil — at 50 Hz | 0.82 |
| Apparent holding power of magnet coil at AC — at 50 Hz | 8.5 VA |
| Inductive power factor with the holding power of the coil — at 50 Hz | 0.25 |
| Number of NO contacts for auxiliary contacts — per direction of rotation | 1 |
| Number of NO contacts for auxiliary contacts — instantaneous contact | 2 |
| Contact reliability of auxiliary contacts | < 1 error per 100 million operating cycles |
| Full-load current (FLA) for 3-phase AC motor — at 480 V rated value | 14 A |
| Full-load current (FLA) for 3-phase AC motor — at 600 V rated value | 17 A |
| Yielded mechanical performance [hp] for 3-phase AC motor — at 220/230 V rated value | 5 hp |
| Yielded mechanical performance [hp] for 3-phase AC motor — at 460/480 V rated value | 10 hp |
| Yielded mechanical performance [hp] for 3-phase AC motor — at 575/600 V rated value | 15 hp |
| Contact rating of auxiliary contacts according to UL | A600 / Q600 |
| For short-circuit protection of the main circuit — with type of coordination 1 required | gG NH 3NA, DIAZED 5SB |
| NEOZED 5SE | 63 A |
| For short-circuit protection of the main circuit — with type of coordination 2 required | gG NH 3NA, DIAZED 5SB |
| NEOZED 5SE | 25 A |
| For short-circuit protection of the main circuit — for short-circuit protection of the auxiliary switch required | fuse gG: 10 A |
| Mounting position | +/-180° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 22.5° on vertical mounting surface |
| Fastening method | screw and snap-on mounting onto 35 mm DIN rail |
| Installation/ mounting/ dimensions — height | 114 mm |
| Installation/ mounting/ dimensions — width | 90 mm |
| Installation/ mounting/ dimensions — depth | 97 mm |
| With side-by-side mounting — forwards | 6 mm |
| With side-by-side mounting — backwards | 0 mm |
| With side-by-side mounting — upwards | 6 mm |
| With side-by-side mounting — downwards | 6 mm |
| With side-by-side mounting — at the side | 6 mm |
| For grounded parts — forwards | 6 mm |
| For grounded parts — backwards | 0 mm |
| For grounded parts — upwards | 6 mm |
| For grounded parts — at the side | 6 mm |
| For grounded parts — downwards | 6 mm |
| For live parts — forwards | 6 mm |
| For live parts — backwards | 0 mm |
| For live parts — upwards | 6 mm |
| For live parts — downwards | 6 mm |
| For live parts — at the side | 6 mm |
| Type of electrical connection — for main current circuit | spring-loaded terminals |
| Type of electrical connection — for auxiliary and control circuit | spring-loaded terminals |
| Type of electrical connection — at contactor for auxiliary contacts | Spring-type terminals |
| Type of electrical connection — of magnet coil | Spring-loaded terminal |
| Type of connectable conductor cross-sections for main contacts — solid | 2x (1 ... 10 mm²) |
| Type of connectable conductor cross-sections for main contacts — solid or stranded | 2x (1 ... 10 mm²) |
| Type of connectable conductor cross-sections for main contacts — finely stranded with core end processing | 2x (1 ... 6 mm²) |
| Type of connectable conductor cross-sections for main contacts — finely stranded without core end processing | 2x (1 ... 6 mm²) |
| For auxiliary contacts — solid or stranded | 2x (0.5 ... 2.5 mm²) |
| For auxiliary contacts — finely stranded with core end processing | 2x (0.5 ... 1.5 mm²) |
| For auxiliary contacts — finely stranded without core end processing | 2x (0.5 ... 1.5 mm²) |
| For auxiliary contacts — for AWG cables for auxiliary contacts | 2x (20 ... 14) |
| Product function suitable for safety function | Yes |
| Protection class IP on the front according to IEC 60529 | IP20 |
| Touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front |
| Product function bus communication | Yes |
| Protocol is supported AS-Interface protocol | No |
| Product function control circuit interface with IO link | No |
| Width | 90 mm |
| Function | Reversing contactor |
| Height | 114 mm |
| Depth | 97 mm |
| Rated operation power at AC-3, 400 V | 7.5 kW |
| Number of normally open contacts as main contact | 3 |
| Rated operation current Ie at AC-3, 400 V | 17 A |
| Degree of protection (IP) | IP20 |
| Type of electrical connection of main circuit | Spring clamp connection |
| Voltage type for actuating | AC |
| Rated operation power NEMA | 10 kW |
| Country of origin | Germany |