| Product type | Pedal pressure and emergency stop button |
| Product group | Push buttons and signal units |
| Series | Harmony XB4 |
| Diameter | 40 mm |
| Color | Red |
| Contact type | 2NC |
| Carbon footprint (EPD) | 1.0453 kg CO2e per pcs |
| Country of origin | Czechia |
| Customs tariff code (EU CN) | 85365080 |
| HS code | 8536.50 |
| Manufacturer part number | XB4BS84462 |
| Range of product | Harmony XB4 |
| Product or component type | Emergency switching off push-button; Emergency stop push-button |
| Device short name | XB4 |
| Bezel material | Chromium plated metal |
| Fixing collar material | Zamak |
| Mounting diameter | 22.5 mm |
| Sale per indivisible quantity | 1 |
| Shape of signaling unit head | Round |
| Type of operator | trigger action and mechanical latching |
| Head type | Standard |
| Reset | Turn to release |
| Operator profile | Red mushroom Ø 40 mm, unmarked |
| Contact operation | Slow-break |
| Connections - terminals | Screw clamp terminals, = 1 x 0.34 mm² without cable end conforming to IEC 60947-1 |
| Height | 47 mm |
| Width | 40 mm |
| Depth | 85 mm |
| Product weight | 0.126 kg |
| Device mounting | Fixing hole - diameter: 22.5 mm +/- 0.2 mm |
| Fixing mode | By fixing collar recommended torque: 1 N.m (+/- 0.2 N.m) |
| Contacts usage | Monitoring contact; Standard contacts |
| Positive opening | With conforming to IEC 60947-5-1 appendix K |
| Operating travel | 1.5 mm (NC changing electrical state); 4.3 mm (total travel) |
| Operating force | 47 N |
| Mechanical durability | 300000 cycles |
| Tightening torque | 0.8…1.2 N.m conforming to IEC 60947-1 |
| Shape of screw head | Cross compatible with pozidriv No 1 screwdriver; Slotted compatible with flat Ø 4 mm screwdriver; Slotted compatible with flat Ø 5.5 mm screwdriver |
| Contacts material | Silver alloy (AgNi); Silver alloy (AgSnO2) |
| Short-circuit protection | 6 A cartridge fuse type gG conforming to IEC 60947-5-1 |
| [Ith] conventional free air thermal current | 6 A conforming to IEC 60947-5-1 |
| [Ui] rated insulation voltage | 300 V (pollution degree 3) conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60947-1; 4 kV conforming to 86/188/EEC |
| [Ie] rated operational current | 1.5 A at 240 V, AC-15, B300 conforming to IEC 60947-5-1; 3 A at 120 V, AC-15, B300 conforming to IEC 60947-5-1; 0.11 A at 250 V, DC-13, R300 conforming to IEC 60947-5-1; 0.22 A at 125 V, DC-13, R300 conforming to IEC 60947-5-1 |
| Electrical durability | 300000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 300000 cycles, AC-15, 3 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 300000 cycles, AC-15, 3 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 300000 cycles, DC-13, 0.3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C; 300000 cycles, DC-13, 1 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1 appendix C |
| Electrical reliability | Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4; Λ < 10exp(-8) at 17 V and 3.4 mA in clean environment conforming to IEC 60947-5-4 |
| Device presentation | Complete product |
| Protective treatment | TH |
| Ambient air temperature for storage | -40…70 °C |
| Ambient air temperature for operation | -40…70 °C |
| Electrical shock protection class | Class I conforming to IEC 60536 |
| IP degree of protection | IP66 conforming to IEC 60529; IP67 conforming to IEC 60529; IP69 conforming to IEC 60529; IP69K conforming to ISO 20653; Type 13 conforming to UL 50E; Type 12 conforming to UL 50E; Type 4 conforming to UL 50E; Type 4X conforming to UL 50E |
| IK degree of protection | IK06 conforming to IEC 60068-2-75 |
| Standards | IEC 60947-1; IEC 60947-5-1; IEC 60947-5-5; IEC 60204-1; IEC 60947-5-4; IEC 60364-5-53; ISO 13850; UL 60947-5-1; CSA C22.2 No 60947-5-1; JIS C8201-1; JIS C8201-5-1; GB/T 14048.5; BS EN 60947-5-1; GOST IEC 60947-5-1 |
| Product certifications | CSA; BV; UL listed; LROS (Lloyds register of shipping); DNV; CE; CCC; CB Scheme; UKCA; EAC |
| Vibration resistance | 5 gn (f= 10…500 Hz) conforming to IEC 60068-2-6; 25 mm peak to peak (f= 2…10 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 30 gn (duration = 18 ms) for half its wave acceleration conforming to IEC 60068-2-27; 50 gn (duration = 11 ms) for half its wave acceleration conforming to IEC 60068-2-27; 25 gn (duration = 6 ms) for 1000 shocks on each axis conforming to IEC 60068-2-27 |
| Number of Units in Package 1 | 1 |
| Number of Units in Package 2 | 80 |
| Warranty (in months) | 18 |
| EAN | 3606481068743 |