cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider XACA Hanging pressure 2-Step with emergency stop - Harmony XAC, yellow, 2NO - 2NO - 1NC

Schneider Electric · Control & Automation · Pushbuttons & Pilot Lights · France · se.com
Part Number
XACA2074  ·  HS 8536.50
Schneider XACA Hanging pressure 2-Step with emergency stop - Harmony XAC, yellow, 2NO - 2NO - 1NC

Schneider XACA Hanging pressure 2-step with emergency stop. Hanging pressure (Electrical Engineering / Push buttons and signal units). Principal data: series Harmony XAC, color Yellow, contact type 2NO -2NO -1NC. Supplied under manufacturer part number XACA2074, EAN 3389110559248, HS code 8536.50, country of origin France.

Technical Specifications

Product typeHanging pressure
Product groupPush buttons and signal units
SeriesHarmony XAC
ColorYellow
Contact type2NO -2NO -1NC
Protection class (IP)65
MaterialPP ( Polypropylene )
Number of pressures2
Carbon footprint (EPD)1.8993 kg CO2e per pcs
Country of originFrance
Customs tariff code (EU CN)85365080
HS code8536.50
Manufacturer part numberXACA2074
Range of productHarmony XAC
Product or component typePendant control station
Device short nameXACA pistol grip
Control station typeDouble insulated
Enclosure materialPolypropylene
Control typeIntuitive
Electrical circuit typeControl circuit
enclosure typeComplete ready for use
Control station applicationControl of 2-speed hoist motor
Control station composition2 push-buttons + 1 emergency stop
Control button typeEmergency stop push-button Ø 30 mm 1 NC trigger action; First push-button 2 NO (2 step) raise, slow-fast; Second push-button 2 NO (2 step) lower, slow-fast
Product compatibilityZB2BE102 for emergency stop; ZB2BE101 + ZB2BE201 for each direction
Mechanical interlockingWith mechanical interlocking
Control station colourYellow
Connections - terminalsScrew clamp terminals, 1 x 2.5 mm² with or without cable end; Screw clamp terminals, 2 x 1.5 mm² with or without cable end
StandardsCSA C22.2 No 14; EN/IEC 60204-32; UL 508; EN/IEC 60947-5-1; EN/ISO 13850: 2006; EN/IEC 60947-5-5
Product certificationsUL; CSA
Protective treatmentTH
Ambient air temperature for operation-25…70 °C
Ambient air temperature for storage-40…70 °C
Vibration resistance15 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
Shock resistance100 gn conforming to IEC 60068-2-27
Overvoltage categoryClass II conforming to IEC 61140
IP degree of protectionIP65 conforming to IEC 60529
IK degree of protectionIK08 conforming to EN 50102
Mechanical durability1000000 cycles
Cable entryRubber sleeve with stepped entry 7…15 mm
Contact code designationA600 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A; A600 AC-15, Ue = 600 V, Ie = 1.2 A conforming to IEC 60947-5-1 appendix A; Q600 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A; Q600 DC-13, Ue = 600 V, Ie = 0.1 A conforming to IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current10 A
[Ui] rated insulation voltage600 V (pollution degree 3) conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947-1
Contact operationSlow-break; Staggered
Maximum resistance across terminals25 MOhm
Operating force13…15 N
Short-circuit protection10 A fuse protection by cartridge fuse type gG
Rated operational power in W40 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C; 48 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C; 65 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Terminals description ISO n°1(23-24)NO_CL; (13-14)NO
Terminals description ISO n°2(11-12)NC
Terminal identifier(11-12)NC; (13-14)NO
Product weight0.36 kg
Number of Units in Package 11
Number of Units in Package 215
Number of Units in Package 3120
Warranty (in months)18
EAN3389110559248

Properties

MOQ1

Cross-References

Attached Documents