Schneider LC1SK Contactor - TeSys SK, 3P, 230V

Schneider Electric · Electrical Components · Contactors · France · se.com
Part Number
LC1SKGC310P7  ·  HS 8536.49
Schneider LC1SK Contactor - TeSys SK, 3P, 230V

Schneider LC1SK Contactor. Contactors and thermal relays motor control (Electrical Engineering / Components for panels and boxes). Principal data: series TeSys SK, number of poles 3P, voltage 230 V. Supplied under manufacturer part number LC1SKGC310P7, EAN 3389110563689, HS code 8536.49, country of origin Czechia.

Technical Specifications

Product typeContactors and thermal relays motor control
Product groupComponents for panels and boxes
SeriesTeSys SK
Number of poles3P
Voltage230 V
REACH SVHC substance above 0.1%Lead
Carbon footprint (EPD)0.9493 kg CO2e per pcs
Country of originCzechia
Customs tariff code (EU CN)85364900
HS code8536.49
Manufacturer part numberLC1SKGC310P7
RangeTeSys
Product nameTeSys SK
Product or component typeMini contactor
Device short nameLC1SKGC
Contactor applicationMotor control; Resistive load
Utilisation categoryAC-1; AC-3
power pole contact composition3P
Pole contact composition3 NO
Auxiliary contact composition1 NO
[Ie] rated operational current20 A (at <50 °C) AC AC-1; 9 A at <= 400 V AC AC-3
[Ue] rated operational voltagePower circuit: 690 V AC 50/60 Hz; Signalling circuit: 690 V AC <= 400 Hz
Control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage230 V AC 50/60 Hz
Motor power kW4 kW at 380...415 V AC 50/60 Hz; 4 kW at 660...690 V AC 50/60 Hz; 1.1 kW at 220...230 V AC 50/60 Hz
[Ith] conventional free air thermal current20 A (at 55 °C) for power circuit; 10 A (at 55 °C) for signalling circuit
Irms rated making capacity85 A AC conforming to NF C 63-110; 85 A AC conforming to IEC 60947
Rated breaking capacity68 A at <= 400 V conforming to NF C 63-110; 68 A at <= 400 V conforming to IEC 60947
[Icw] rated short-time withstand current60 A 55 °C for power circuit
Associated fuse rating20 A gI at <= 440 V for power circuit; 10 A gI for signalling circuit conforming to IEC 60947; 10 A gI for signalling circuit conforming to VDE 0660
Average impedance4 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 690 V conforming to BS 5424; Power circuit: 690 V conforming to IEC 60947; Power circuit: 690 V conforming to UL 508; Power circuit: 690 V conforming to VDE 0110 group C; Power circuit: 690 V conforming to CSA C22.2 No 14
Mounting supportPanel; Rail
StandardsEN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1
Product certificationsCB Scheme; CE; UKCA; EAC; cULus
Connections - terminalsConnector 1 cable(s) 1.5…6 mm²solid; Connector 2 cable(s) 1.5…4 mm²solid; Connector 1 cable(s) 0.5…6 mm²flexible without cable end; Connector 2 cable(s) 0.35…2.5 mm²flexible without cable end; Connector 1 cable(s) 0.35…6 mm²flexible with cable end; Connector 2 cable(s) 0.35…1.5 mm²flexible with cable end
Tightening torquePower circuit: 0.8 N.m - on connector - with screwdriver pozidriv No 1
Operating time6...8 ms coil de-energisation and NO opening; 7...14 ms coil energisation and NO closing
Mechanical durability10 Mcycles
Maximum operating rate1200 cyc/h
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 50/60 Hz (at <55 °C); Drop-out: 0.2...0.75 Uc at 50/60 Hz (at <55 °C)
Inrush power in VA23 VA 50/60 Hz (at 20 °C)
Hold-in power consumption in VA4.9 VA 50/60 Hz (at 20 °C)
Heat dissipation1.5 W at 50/60 Hz
Signalling circuit frequency<= 400 Hz
IP degree of protectionIP2X conforming to VDE 0106
Protective treatmentTC conforming to IEC 60068; TC conforming to DIN 50015
Ambient air temperature for operation-20…50 °C
Ambient air temperature for storage-50…70 °C
Operating altitude2000 m without derating
Height58 mm
Width45 mm
Depth56 mm
Product weight0.175 kg
Warranty (in months)18
EAN3389110563689