cBallast
Industrial Parts Catalog
Datasheet generated 2026-10-07
sales@cballast.com
cballast.com

Schneider ACTI9 IC60 RCBO Combination switch HPFI - ACTI9 IC60 RCBO, 30A, 2P, C, Asi, 30MA

Schneider Electric · Electrical Components · Miniature Circuit Breakers · France · se.com
Part Number
A9D27225  ·  HS 8536.20
Schneider ACTI9 IC60 RCBO Combination switch HPFI - ACTI9 IC60 RCBO, 30A, 2P, C, Asi, 30MA

Schneider Acti9 iC60 RCBO Combination switch HPFI. Residual current devices (RCD, PFI, Combo) (Electrical Engineering / Components for panels and boxes). Principal data: series Acti9 iC60 RCBO, current rating 30 A, number of poles 2P, tripping characteristic C. Supplied under manufacturer part number A9D27225, EAN 3606481157454, HS code 8536.20, country of origin Portugal.

Technical Specifications

Product typeResidual current devices (RCD, PFI, Combo)
Product groupComponents for panels and boxes
SeriesActi9 iC60 RCBO
Current rating30 A
Number of poles2P
Tripping characteristicC
ClassAsi
Rated residual current30 mA
REACH SVHC substance above 0.1%Lead, Diboron-trioxide, Lead tetroxide, Lead-monoxide, Octrizole
Carbon footprint (EPD)1.4809 kg CO2e per pcs
Country of originPortugal
Customs tariff code (EU CN)85362010
HS code8536.20
Manufacturer part numberA9D27225
RangeActi9
Product nameActi9 iC60 RCBO
Product or component typeResidual current breaker with overcurrent protection (RCBO)
Device short nameiC60 RCBO
Device applicationDistribution
Poles description2P
Number of protected poles2
[In] rated current25 A
Network typeAC
Network frequency50 Hz
Trip unit technologyThermal-magnetic
Curve codeC
Earth-leakage sensitivity30 mA
Suitability for isolationNo conforming to IEC 60947-1
Quality labelsVDE; NF; IMQ; KEMA-KEUR
Device location in systemOutgoer
[Ue] rated operational voltage220...240 V AC 50 Hz
Magnetic tripping limit5...10 x In
Residual current tripping technologyVoltage independent
Earth-leakage protection time delayInstantaneous
Earth-leakage protection classType A-SI (Super Immunised)
Breaking capacity10000 A Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1; 15 kA Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2
[Ics] rated service breaking capacity7500 A 75 % x Icn at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1; 7.5 kA 50 % x Icu at 220...240 V AC 50 Hz conforming to EN/IEC 60947-2
Rated breaking and making capacityIdm 6000 A at 220...240 V AC 50 Hz conforming to EN/IEC 61009-2-1
Limitation class3 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage500 V AC 50 Hz
[Uimp] rated impulse withstand voltage4 kV
Surge current3000 A
Contact position indicatorNo
Control typeToggle
Local signallingON, OFF, fault trip
mounting modeClip-on
Mounting supportDIN rail
Comb busbar and distribution block compatibilityTop or bottom: YES; Bottom: biconnect
Connection pitch9 mm between poles
9 mm pitches4
Height86 mm
Width36 mm
Depth78 mm
Product weight273 g
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Connections - terminalsTunnel type terminal top or bottom 1…35 mm² rigid; Tunnel type terminal top or bottom 1…25 mm² flexible; Tunnel type terminal top or bottom 1…25 mm² flexible with ferrule
Wire stripping length12 mm for top or bottom connection
Tightening torque2 N.m
Earth-leakage protectionIntegrated
StandardsEN/IEC 60947-2; EN/IEC 61009-2-1
IP degree of protectionIP40 (distribution enclosure) conforming to IEC 60529; IP20 conforming to IEC 60529
Overvoltage categoryIII conforming to IEC 60364
Electromagnetic compatibility8/20 µs impulse withstand, 3000 A conforming to EN/IEC 61009-2-1
Tropicalisation2
Relative humidity95 % at 55 °C
Ambient air temperature for operation-25…60 °C
Ambient air temperature for storage-40…70 °C
Warranty (in months)18
EAN3606481157454

Properties

MOQ1

Cross-References

Attached Documents